Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 79 MAHATMA GANDHI MARKET SRI VIJAYA PURAM 744101 | SRI VIJAYA PURAM | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | Admitted-Finance |
| 2 | Admitted-Finance B 33 171 PATEL NAGAR GURDASPUR ROAD PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹27,000
Closing Date
18 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Shri Abhay Manglik, SE, IDSE
HQ Commander works Engineer No 2, Brichgunj, Junglighat Post, Port Blair-744 103
PERIODICAL MAINTENANCE AND REPAIRS TO HT ELECTRIC DISTRIBUTION NETWORK UNDER GE BRICHGUNJ, PORT BLAIR
2020_MES_396321_1
80197/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
PORT BLAIR
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE Brichgunj
₹27,000
Yes
24 Dec 2020
20 Nov 2020
24 Dec 2020
20 Nov 2020
18 Dec 2020
4 Dec 2020
20 Nov 2020 - 1 Dec 2020
60 days
Amount
Material and Labour for Jointing straight through joint, heat shrinkable, suitable for HT, XLPE cable with aluminium conductor of size 50 to 95 Sqmm, 11 KV rating and testing after jointing complete all as specified including dismantling old cable joint of any description complete including earth work all as specified and as directed.
Material and Labour for Jointing cable straight through joint, heat shrinkable, suitable for HT, XLPE cable with aluminium conductor of size 120 to 185 Sqmm, 11 KV rating and testing after jointing complete all as specified including dismantling old cable joint of any description complete including earth work all as specified and as directed.
Material and Labour for Jointing cable end termination kit, heat shrikable, outdoor type, suitable for HT, XLPE cable with aluminium conductor of size 50 to 95 Sqmm, 11 KV rating and testing after jointing complete all as specified including dismantling old cable joint of any description complete including earth work all as specified and as directed.
Material and Labour for Jointing cable end termination kit, heat shrikable, outdoor type, suitable for HT, XLPE cable with aluminium conductor of size 120 to 185 Sqmm, 11 KV rating and testing after jointing complete all as specified including dismantling old cable joint of any description complete including earth work all as specified and as directed.
Material and Labour for Jointing cable end termination kit, heat shrikable, indoor type, suitable for HT, XLPE cable with aluminium conductor of size 50 to 95 Sqmm, 11 KV rating and testing after jointing complete all as specified including dismantling old cable joint of any description complete including earth work all as specified and as directed.
Material and Labour for identifying the earth pits, improving the resistance of existing earth pit by pouring salt water in earth pit to improve resistance up to 2 Ohms and measuring the earth resistance and making record complete all as specified and as directed.
Material and Labour in repairs Silica Gel breather suitable for transformer of any capacity all as specified and as directed.
Material and Labour for preparation of old surfaces of 11 mtr high RCC Poles and applying one coat of cement based paint on RCC poles including painting black and yellow strips of 30 cm each on poles upto 1.0 m from the bottom and numbering with 60mm sized letter with synthetic enamel paint complete all as specified and as directed.
Material and Labour for preparation of old surfaces of 9 mtr high RCC Poles and applying one coat of cement based paint on RCC poles including painting black and yellow strips of 30 cm each on poles upto 1.0 m from the bottom and numbering with 60mm sized letter with synthetic enamel paint complete all as specified and as directed.
Dismantling of Insulators HT, 11 KV pin, post, disc type and removing from its locations, making good the disturbed surfaces to match with the existing surfaces, and taken as credit all as directed and as specified
Supply and fix in porcelain/Polymer post insulator suitable for 11 KV grade complete all as specified and as directed.
Supply and fix in Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11 KV grade complete all as specified and as directed.
Supply and fix in repairs 33 KV post- top insulator porcelain vitreous white or Brown or green including galvanised mild steel straps as per sample all as specified and as directed.
Material and Labour for loose filling of 40 mm graded stone aggregates in electrical switch gear yard out door complete all as specified and as directed.
Material and Labour for cement concrete 1:2:4, type B-1 using 20mm graded stone aggregate including necessary form work and finishing to exposed concrete surfaces even and fair complete all as specified and as directed.
Supply and fill Silica Gel in breathers of transformers complete including removing old silica gel all as specified and as directed.
Material and Labour for repairs to 33 KV single phase Oil cooled current transformer (CT) conforming to IS-2765, Ratio:100-75/1-1-1A, Burden 15VA/15VA/-, class of accuracy - 0.5/5P-10 / PS, Frequency:50 Hz, INS level: 36/70/170 Kvp, STC:26kA for 15 sec, INS class-A,Vk> 50V complete including first fill of transformer oil all as specified and as directed.
Material and Labour for repairs to 33 KV single phase Oil cooled current transformer (CT) conforming to IS-2765, Ratio:50/1-1-1A, Burden 15VA/15VA/-, class of accuracy - 0.2/5P-10 / PS, Frequency:50 Hz, INS level: 36/70/170 Kvp, STC:26kA for 15 sec, INS class-A,Vk> 50V for core 3 complete including first fill of transformer oil all as specified and as directed.
Online Filtration of transformer oil including checking Dielectric strength before and after filtration of oil for transformers located in Brichgunj area with suitable equipment having filtration, heating and pumping facility to improve the dielectric strength / insulation value of transformer oil complete all as specified and as directed. Note : Dielectric strength of transformer oil after filtration/dehydration shall not be less than 50 KV when tested with 2.5 mm gap electrode complete. Oil for topping up shall be measured and paid for seperately as supply only under relevant items of this schedule.
Material and Labour for dismantling Oil filled CT/PT from structure at 33 KV Switchyard after switching off supply and carefully removing electrical connection, draining oil, refilling the oil, cleaning terminals, scrapping thoroughly the existing corroded paint / rust, filling the cavities with suitable filler material & painting with one coat of silicon acrylic heat resistant paint of approved quality and colour, mounting back the PT/CT and giving necessary electrical connection all as directed and as specified. NOTE : Transformer oil required shall be measured & paid separatly under relevant item.
Filling fresh new EHV grade-II transformer oil duly filtered for topping up, ISI marked as per IS:335/93 with amdt. No.1 (Reaffirmed : 2005) dehydrated to give BDV value not less than 50 KV when tested with 2.5 mm gap electrode complete all as specified and as directed
Supplying, laying, Jointing, testing and commissioning of HT UG cable, XLPE insulated, screened insulated, armoured and PVC bedded, 11 KV grade (heavy duty) suitable for earthed system with aluminium conductor of size 3 core 95 sqmm conforming to IS-7098 Part II laid in trenches, fixed to walls or passing through pipes and connecting up including taking out unserviceable cable complete all as specified and as directed. Note : Earth work excavation shall be measured and paid seperately under relevant item
Material and Labour for repair and overhauling of HT 11KV vertical Air Break switch, Outdoor type by cleaning the contacts, applying grease and replacement of defective unserviceable spare parts for easy operation on ground level complete all as specified and as directed. Note : i) All spares required to be replaced shall be measured and paid separately under relevant items of this schedule. ii) Minor items like nut, bolts, washers etc are deemed to be included in the quoted rate.
Supply only Male contact/Moving contact blade suitable for 11KV complete all as specified and directed.
Supply only Female contact/Fixed contact Jaw suitable for 11KV complete all as specified and as directed.
Supply only MS jumper carrier complete all as specified and as directed.
Supply only Tinned Copper flexible Jumper 200 amps complete all as specified and as directed.
Supply only repairs top contact/ L contact for drop out fuse suitable for 11 KV all as directed by the Engineer in Charge.
Supply only bottom contact for drop out fuse suitable for 11 KV all as directed by the Engineer in Charge.
Material & Labour for Earthing complete with galvanised iron earth plate electrode of size 60cmx60cm× 6mm thick, buried directly in ground vertically at a depth not less than 2.25 metres deep below normal ground level with top edge of the earth plate not less'than 1.5 metres below normal ground level and surrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip of size 32X6 mm by means of bolts, nuts, check nuts and washers made up of galvanised iron or steel and protected by light grade 40mm dia galvanised iron pipe connected to main switch board or main control board and GI pipe light grade 20mm bore for watering including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B1, including necessary excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and as shown in electrical plate No. 3 connected to test point terminal all as specified or indicated including testing new earthing on completion all as specified and as directed. Note:- (a) The unit rate shall include for protection pipe, GI water pipe, wire mesh, funnel, excavation, RCC pit cover, PCC chamber pit, test point terminal block, 32X6 mm GI strip from top of earth plate upto 5 mtr above ground level and if GI protection pipe is less than 5 meters, no price adjustment shall be made.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes, foundation for poles etc., and getting out in hard/dense soil complete all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified. Note : A deduction of 10% shall be made from total computed volume of filling to cater in bulkage irrespective of machinery used for ramming.
Removing surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as directed
Supply and filling pulverized stone dust to the full witdth of trenches for protection of cables including spreading, punning down & consolidation complete all as specified & directed NOTE : Punned thickness of stone dust after cushioning shall be measured & paid.
Supplying and laying unreinforced precast cement concrete cable cover, class HV, type 1 flat, size 300mm x 180mm x 40mm made out of M-20 grade PCC as per IS 5820:1970 for cable protection, embossed with "ELECTRIC" on top surface complete incl taking down old all as specified and as directed.
Material and Labour for decarbonsing/cleaning complete HT panels board, 11 KV cubicle type, consists of bus bar chamber, circuit chamber and metering chambers, by opening the spout/bus covers inspecting the bus bar joints, cleaning of bus bars, checking the bus bar spouts and circuit spouts for any flash overs/tracks, applying Becktol (red) solution to the bus bars and spouts having moderate tracking, replacement of bus bar/circuit spouts in case of spouts subjects to heavy tracking, applying HT insulated red compounds/Monoplist compound at the bus bar joints after tightening of joints, cleaning of bus bar insulators and bus bars with CTC and ensure proper decarbonisation and re-assembling complete all as directed by Engineer-in-Charge.
Material and Labour for decarbonsing/cleaning the cable compartment of Ring Main Unit 3 Way, 11 KV, consists of End joints,Current transformers, cable boots, bushings, by opening compartment cover by carefully switching off the main input cable supply and necessary switching ON of Earth switch of RMU thereby inspecting the end joints, current transformer, bushings and cable boots, checking the bushings for any flash overs/tracks, applying Becktol red solution to the bushings having moderate tracking, applying suitable HT insulated tape over anti tracking tube to prevent further tracking on, cleaning of end joints, CTs & cable boots with CTC and ensure proper decarbonisation and re-assembling complete all as directed by Engineer-in-Charge.
Taking down the HT vacuum circuit breaker of capacity up to 800A, of any make, 11 KV, for servicing and re-assembling complete, comprising of the following including testing and commissioning to the entire satisfaction of Engineer-in-Charge. Note: Quoted rate is inclusive for the following services:- (i)Taking out the VCB from the enclosure & checking the serviceability of the following parts carefully including cleaning, adjustments and re-assembling the unit complete. (ii) Cleaning the external surface of bushings with CTC/CRC or Liquid ammonia to remove the accumulation of dirt or any other deposits. Inspection of bushings and make sure that vibration due to breaker operation have not caused the bushings to move resulting misallignment of contacts. (iii) Checking the breaker bushing of bus bar and circuit side inspecting the internal surface carefully for any charging/trackings,replacement of bushings. (iv) Dismantling the spring charging mechanism of the VCB, checking the operations of the closing/tripping trough closing/tripping coils electrically as well as manual charging including cleaning adjustments complete for the following. (v) Checking the condition of the spring charging motor along with gear box including servicing to the motor commulator bushes, lubrication of bearing surfaces etc. (vi) Cost of additional hardware like, bolts, nuts , washers and spring washers, petrolium jelly ctc, to put the breaker in serviceable condition is deemed to be included in the rates quoted.
Supply only spring charging motor suitable for operating in 240 V, AC supply to be fixed in 11 KV, VCB all as specified and as directed.
Supply only Trip circuit coil 30V, DC for VCBs all as directed and as specified.
Supply only space heaters 230 V, 80 W suitable for fixing inside VCB chamber along with necessary wiring for all as directed and as specified.
Supply only thermostat for space heaters of range 30- 110 degree suitable for fixing inside VCB chamber including wiring all as directed and as specified.
Supply and fix in repairs right angled cold applied cable boot suitable to cover the end connections of HT cable of size 95 Sqmm 3 core connected to 11 KV, 630 A Siemens Make 8DJ HST Model RMU all as directed and as specified.
Material and Labour for hiring fault finding machine from AED duly mounted on vehicle to locate fault of HT cable 11KV, 3 core XLPE cable of size upto 185 sqmm by thumping and echo instrument/computer aided fault finding kit and finding out exact location of the fault, including necessary earth work to expose the faulty HT cable, cutting the piece of faulty HT cable, meggering the left out HT cable to ascertain the serviceability complete all as specified and as directed.
Material and Labour for repairs to lightening arrestor Non linear type, with all fittings, transmission class, discharge capacity 10KA suitable for rated system voltage 12KV self supporting station class type complete all as specified and as directed.
Material and labour for taking down old deteriorated Earth chamber pit by making new concrete pit in PCC (1:3:6) type C1, pre cast RCC (1:2:4) type B1 as in cover slab 54 x 54 x 5 cm including 8mm dia MS TMT bars @ 150 mm c/c as in reinforcement with one handle for lifting made out of 8 mm dia MS bar, funnel for watering including taking down old deteriorated earth pits along with necessary excavation earth work in any type of soil complete all as specified and directed.
Supply and fix in repair digital type three phase ampere meter with programmable CT accuracy class 0.5 complete all as specified and as directed. Make : Cat No WL1310200000 of L&T or equivalent as approved by GE.
Supply and fix in replacement voltage presence indication system (VPIS) in Siemens RMU Model 8DJHST including changing the wiring and terminations complete all as directed and as specified.
Supply and fix PVC cable duct FRLS type of size 75x75 mm including taking down damaged duct cover all as specied and as specified.
M&L for preparation of old surfaces of 9m high steel tubular pole & applying one coat of Aluminium paint including painting black & yellow strip of 30 cm each on poles upto 1m from bottom & numbering with 60mm sized litter with synthetic enamel paint complete all as directed by E-in-Charge
M&L for preparation of old surface for cross arms & applying one coat of Aluminium paint complete all as specified & directed.
Gulmarg Electrical Service
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .