Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-AOC 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | ₹1.5 Cr Quoted ₹1.6 Cr | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹1.7 Cr+₹5.9 L (3.56%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | ₹1.7 Cr+₹5.9 L (3.56%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹1.8 Cr+₹11.6 L (7.06%)Rejected-Finance OPP SHRI NAVNIKETAN H S SCHOOL CHHOLA KANCHI BHOPAL M P | BHOPAL | MADHYA PRADESH | 462010 | ₹1.8 Cr+₹11.6 L (7.06%) | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹1.8 Cr+₹13.1 L (7.98%)Rejected-Finance 3 1 4 GOPINATH BAZAR DELHI CANTT 110 010 | NEW DELHI | DELHI | 110010 | ₹1.8 Cr+₹13.1 L (7.98%) | L4 | Rejected-Finance Other than lowest bidder |
| 5 | L5₹1.8 Cr+₹18.9 L (11.5%)Rejected-Finance | ₹1.8 Cr+₹18.9 L (11.5%) | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹2.4 Cr
EMD Value
₹3.1 L
Closing Date
13 Jan 2024, 6:00 pmClosed
Chief Engineer , Bhopal Zone, MES Bhopal
HQ , Chief Engineer , Bhopal Zone, Military Engineer Services ,Bhopal-462001
CONVERSION OF LT OVER HEAD LINE TO LT UNDER GROUND CABLE AT DHANA MIL STN
2023_MES_631985_1
CA NO. CEBZ / DHA / TOKEN / 06 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Dhana
As per NIT
4 documents required · 4 mandatory
₹2,000
AGE (I) DHANA
₹3.1 L
Bhopal
5 Apr 2024
9 Dec 2023
15 Jan 2024
9 Dec 2023
13 Jan 2024
6 Jan 2024
19 Dec 2023
Amount
Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department.
Dismantling of ACSR or AAC Conductor etc complete all as specified and directed.
Dismantling of cross-arms from pole / structures of M.S. channel or angle sections etc complete all as specified and directed.
Dismantling of insulator any type, any size etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 10sqmm, 2 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 16sqmm, 2 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 10sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 16sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 25sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 35sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 50 sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 70 sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 95 sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 120 sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 150 sqmm, 4 core etc complete all as specified and directed.
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 185 sqmm, 4 core etc complete all as specified and directed.
Dismantling of old unserviceable panel of any size including MCCB's/switchgears etc complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed..
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4.0 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4.0 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4.0 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 2.0 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) ISI Marked with valid CML No., 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2.0 core complete all as specified and directed.
Supply, installation, commissioning and testing of main LT panel Made out of CRCA sheet 3.15mm thick sheet steel, outdoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection class IP 54), (front & back opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey pure polyester or as directed by AGE (I) / GE, adopting 8 tank pretreatment of fabricated job before powder coating & including One Danger notice plate 1.6mm thick, main aluminum bus bar of 400A TPN, all inter connections to outgoing feeders shall be made with TPN alumium bus bar of rating not less than the current carrying capacity of respective feeder, all bus bar shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75X40mm, length of leg not less than 90cm including 30cm grouting duly painted with black enamel paint. Digital ammeter (0-400) with ASS-1No., current transformer of rating 400/5A-3No., Digital voltmeter with VSS (0-500)V - 1No., RYB LED set-1, including suitable size of cable lugs and PCC (1:2:4) type B1 foundation complete all as specified and directed by Engr-in-charge. the panel shall consist of the following switchgear :- Incomer - MCCB 4P 315A 36kA breaking capacity - 1 No Out Going - MCCB 3P 160A 25kA breaking capacity - 1 No, MCCB 3P 100A 25kA breaking capacity - 1 No., MCCB 3P 32A 16kA breaking capacity - 8 Nos, MCCB 3P 16A 16kA breaking capacity - 4Nos NOTE (Applicable to Item No. 30.00 to 61.00) - All MCCBs shall be adjustable thermal & fixed magnetic release type, Ics=100% Icu.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-1) Incoming - (a) MCCB 4P 160A, 25kA breaking capacity - 1 No. Out Going - (b) MCCB 3P 32A, 16kA breaking capacity - 5 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-2) Incoming - (a) MCCB 4P 100A, 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A, 16kA breaking capacity - 1 No. (b) MCCB 3P 32A, 16kA breaking capacity - 1 No. (c) MCCB 3P 16A, 16kA breaking capacity - 4 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-3) Incoming - (a) MCCB 4P 63A ,16kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A , 16kA breaking capacity - 1 No. (b) MCCB 3P 16A , 16kA breaking capacity - 4 No.
All as per item 30.00 above but 525 Amps rated bus bar & comprising the following switchgear for (LTP-2) (T-2) Incoming :- (a) MCCB 4P 400A, 36kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 160A, 25kA breaking capacity - 1 No. (b) MCCB 3P 125A, 25kA breaking capacity - 2 No. (c) MCCB 3P 32A, 16kA breaking capacity - 3 No. (d) MCCB 3P 16A, 16kA breaking capacity - 3 No. (e) MCCB 3P 100A, 25kA breaking capacity - 2 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-4) Incoming :- (a) MCCB 4P 160A, 25kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A, 16kA breaking capacity - 9 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-5) Incoming :- (a) MCCB 4P 125A, 25kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A, 16kA breaking capacity - 1 No. (b) MCCB 3P 16A ,16kA breaking capacity - 5 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-6) Incoming :- (a) MCCB 4P 125A , 25kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A , 16kA breaking capacity - 1 No. (b) MCCB 3P 16A , 16kA breaking capacity - 8 No.
All as per item 30.00 above but 525 Amps rated bus bar & comprising the following switchgear for (LTP-3) (T-3) Incoming :- (a) MCCB 4P 400A, 36kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 160A, 25kA breaking capacity - 1 No. (b) MCCB 3P 125A, 25kA breaking capacity - 1 No. (c) MCCB 3P 63A, 16kA breaking capacity - 1 No. (d) MCCB 3P 32A, 16kA breaking capacity - 8 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-7) Incoming :- (a) MCCB 4P 160A ,25kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A, 16kA breaking capacity - 11 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-8) Incoming :- (a) MCCB 4P 125A , 25kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A , 16kA breaking capacity - 1 No. (b) MCCB 3P 16A ,16kA breaking capacity - 6 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-9) Incoming :- (a) MCCB 4P 63A ,16kA breaking capacity - 1 No. Out Going - . (a) MCCB 3P 32A ,16kA breaking capacity - 6 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-4) (T-4) Incoming :- (a) MCCB 4P 100A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 125A , 25kA breaking capacity - 1 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-10) Incoming :- (a) MCCB 4P 125A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 100A , 25kA breaking capacity - 1 No. (b) MCCB 3P 32A , 16kA breaking capacity - 1 No. (c) MCCB 3P 16A , 16kA breaking capacity - 3 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following for (FP-11) Incoming :- (a) MCCB 4P 100A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A ,16kA breaking capacity - 1 No. (b) MCCB 3P 32A , 16kA breaking capacity - 1 No. (c) MCCB 3P 16A ,16kA breaking capacity - 3 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following for (FP-12) Incoming :- (a) MCCB 4P 63A , 16kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 50A , 16kA breaking capacity - 1 No. (b) MCCB 3P 32A , 16kA breaking capacity - 1 No. (c) MCCB 3P 16A , 16kA breaking capacity - 3 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-13) Incoming :- (a) MCCB 4P 50A , 16kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 40A , 16kA breaking capacity - 1 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No. (c) MCCB 3P 16A, 16kA breaking capacity - 3 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-14) Incoming :- (a) MCCB 4P 40A ,16kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A, 16kA breaking capacity - 1 No. (b) MCCB 3P 16A ,16kA breaking capacity - 3 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (LTP-5),(T-5) Incoming :- (a) MCCB 4P 100A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A ,16kA breaking capacity - 2 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-6),(T-6) Incoming :- (a) MCCB 4P 160A, 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 125A, 25kA breaking capacity - 1 No. (b) MCCB 3P 100A, 25kA breaking capacity - 1 No. (C) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-15) Incoming :- (a) MCCB 4P 100A ,25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A ,16kA breaking capacity - 3 No.
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-16) Incoming :- (a) MCCB 4P 63A ,16kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A, 16kA breaking capacity - 8 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-7),(T-7) Incoming :- (a) MCCB 4P 160A ,25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 125A ,25kA breaking capacity - 1 No. (b) MCCB 3P 32A , 16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-17) Incoming :- (a) MCCB 4P 100A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A , 16kA breaking capacity - 1 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No. (c) MCCB 3P 16A ,16kA breaking capacity - 7 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-18) Incoming :- (a) MCCB 4P 125A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A ,16kA breaking capacity - 7 No. (b) MCCB 3P 16A , 16kA breaking capacity - 6 No.
All as per item 30.00 above but 100 Amps rated bus bar comprising the following switchgear for (FP-19) Incoming :- (a) MCCB 4P 63A ,16kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A ,16kA breaking capacity - 3 No. (b) MCCB 3P 16A ,16kA breaking capacity - 2 No.
All as per item 30.00 above but 400 Amps rated bus bar & comprising the following switchgear for (LTP-8),(T-8) Incoming :- (a) MCCB 4P 250A ,36kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 125A ,25kA breaking capacity - 1 No. (b) MCCB 3P 100A, 25kA breaking capacity - 1 No. (C) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-20) Incoming :- (a) MCCB 4P 100A, 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 63A, 16kA breaking capacity - 3 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-21) Incoming :- (a) MCCB 4P 125A ,25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 100A, 25kA breaking capacity - 2 No. (b) MCCB 3P 32A ,16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-22) Incoming :- (a) MCCB 4P 100A ,25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A ,16kA breaking capacity - 3 No. (b) MCCB 3P 16A, 16kA breaking capacity - 6 No.
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-9),(T-9) Incoming :- (a) MCCB 4P 250A, 36kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 100A ,25kA breaking capacity - 2 No. (b) MCCB 3P 63A ,16kA breaking capacity - 1 No. (C) MCCB 3P 32A, 16kA breaking capacity - 1 No.
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-23) & (FP-24) Incoming :- (a) MCCB 4P 100A , 25kA breaking capacity - 1 No. Out Going - (a) MCCB 3P 32A ,16kA breaking capacity - 4 No. (b) MCCB 3P 16A ,16kA breaking capacity - 2 No.
M&L for earthing complete with galvanised steel earth plate 60cmx60cmx3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanised mild steel earthing lead strip 32X6mm by means of bolts nuts check-nuts and washers of galvanized iron or steel as shown in electrical plate No 3 of MES schedule Part-I connecting to earthing test point and testing on completion with and including 40mm bore light grade GI protection pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work in any type of soil & disposal of soil, providing alternate layers of charcoal and common salt, construction of PCC earth chamber in 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out oof 8mm dia bars, watering arrangement with funnel & wire mesh, complete all as specified and directed. Note:- (i) The concrete pit shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) The unit rate includes the cost of GI pipe light grade for protection of earth strip and earh strip upto 7.5 M. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself
M&L for earthing complete with galvanised steel earth plate 60cmx60cmx3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to earth lead of 4.0mm dia. galvanished mild steel wire by means of bolts nuts check-nuts and washers of galvanized iron or steel as shown in electrical plate No 3 of MES schedule Part-I connecting to earthing test point and testing on completion with including 15mm bore light grade GI protection pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work in any type of soil & disposal of soil, providing alternate layers of charcoal and common salt, construction of PCC earth chamber in 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out oof 8mm dia bars, watering arrangement with funnel & wire mesh, complete all as specified and directed. Note:- (i) The concrete pit shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) The unit rate includes the cost of GI pipe light grade for protection of earth strip and earh strip upto 7.5 M. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself
Supply & Fixing 100mm bore GI tubing Medium grade ISI Marked with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. Note - Excavation & Earthwork shall be measured & paid Separetely
Supply & Fixing 80mm bore GI tubing Medium grade ISI Marked with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. Note - Excavation & Earthwork shall be measured & paid Separetely
Supply & Fixing 50mm bore GI tubing Medium grade ISI Marked with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed. Note - Excavation & Earthwork shall be measured & paid Separetely
M & L for Factory made SMC junction box of size not less than 250 mm X 200mm X105mm as per sample & make approval by Engr in Charge with 4 Nos. aluminium busbar of size 20X3 mm thick mounted on porcelain insulators with and including MCB, 'C' curve, SP, 06 Amp-01 No. including incoming and out going connections with necessary welding work, clamps and mounting on poles etc complete all as specified & directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4 mpa working pressure complete all as specified & directed. NOTE- The Depth of bore from top of road / pavement surface shall not be less than 600mm.
Excavation in trenches not exceeding 1.5 mtrs wide & not exceeding 1.5 mtr in depth in soft or loose soil & getting out complete all as specified & directed.
Returning , filling in spreading, levelling, watering & well Ramming in layers not exc 25cm thick complete all as specified & directed.
Removing excavated material not exceeding 50mtr &deposited where directed at a level not exceeding 1.5 mtr above the ground level complete all as specified & directed.
M & L For sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8cm below cable & 15cm above cable) complete all as specified and directed. Note: Compacted/punned thickness shall be measured & paid.
Supplying and laying un- reinforced precast concrete cable cover, class LV, type 2 with peak, size 300mm x 180mm x 40mm for laying in trenches for cable protection laid adjacent to each other length wise perpendicular to the central axix of cable complete all as specified and directed. NOTE : Above Item is applicable for Item No. 18 to Item No. 25
M&L for bricks old size sub class B designation for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed. NOTE : Above Item is applicable for Item No. 26 to Item No. 29
M & L Cement Concrete (1:2:4) type B-1(20mm Graded Stone Aggregate) for repair of floors / hardstanding / paving /roads after laying of cables etc. including Formwork (as required), complete all as specified & directed.
Demolition of cement concrete un reinforced in ground floors and paving n exc 15cm thickness below or above GL complete all as specified and directed.
M & L for two coats of aluminium paint over a coat of primer to steel tubular LT Poles after dismantling of cross arms,bracing etc. for the portion 60cm from the top of pole including preparation of steel surfaces complete all as specified & directed.
GUPTA ENGINEERING WORKS
NIHAL ENTERPRISES
RAVINDRA BROTHERS
PARAS BROTHERS
VEENUS ENGINEERS
POONAM ELECTRIC INDUSTRY
M/S RAKESH TRADERS
Commercial Traders
M/s Shrangi Rishi Construction
M/S SHIVA TRADERS
Electricals India
Raja enterprises
M/s Prem Associates
R D Bansal
K N RAJ CONSTRUCTIONS
BHARAT MULTITECH INDUSTRIES PVT LTD
stage.html
html • 0.10 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .