Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance SKALZANGLING AIR PORT ROAD LEH LADAKH 194101 | LEH | LEH | LADAKH | 194101 | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
30 Jun 2021, 2:00 pmClosed
Executive Engineer EDD leh
Office of the Executive Engineer EDD Leh
Supply, Installation, testing and Commissioning for Shifting Replacement of DW Poles and DT frame at various locations of Shey section under Improvement of HT LT Line of UT Capex 2021-22.
2021_PDNRE_3427_1
NIT No 23 of ED Leh of 2021-22
Open Tender
Electrical Works
Works
90 days
LEH
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Payable To Executive Engineer EDD Leh
Exempted
5 Jan 2022
18 Jun 2021
1 Jul 2021
19 Jun 2021
30 Jun 2021
19 Jun 2021
Amount
Gapless Surge Arrestor,9 kV, 10kA, LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A (as per REC Standard).
120 mm² Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type for 100KVA DTs
9 Mtr. Long Pole,ST-410 SP33)
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps( As per REC Standard).
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
LT Distribution Box Out door mounting type for 3 Ph 100kVA DTR having 200A TPN isolator, 200A HRC fuse (incomer) and 6 Nos 90A SP MCCB (outgoing)
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole including muffing 0.2Mtr above the ground level plaster and curing of concrete as per drawing/Annexure "D"
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
3-Ø, 4-Wire Trivector Meter with CT(LTCT AMR compatible)
Sundry items like aluminium lugs, Jumpers, binding Tape etc
Chain link Fencing for Transformer with dimension (10'x10'x6') using Angle Iron 40x40x6mm with mesh wire of 2"x2" having door facility of dimension (3'x6')
Dismantling,carriage and re-installation of existing xmer to new ST frame
Replacement of DW poles and Shifting of HT Line
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm (75x40x6mm) with GI top Bracket (50x8 mm) including GI clamp (50x8)mm the standard as per enclosed drawing and specification as per Annexure "A").
GI Channel X-arm including clamps and braces (the detail specification of x-arms for DP structure attached as annexure to this NIT)
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Spiral/Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole including muffing 0.2Mtr above the ground level plaster and curing of concrete as per drawing/Annexure "D"
Guard Netting complete with earthing connection on both sides using cradle gurad wire 8 SWG GI wire and lacing of 10SWG GI wire including GI X-arms with clamps and braces, threaded eye bolts, turn buckles and binding wire, nut bolts etc.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
11KV Link Set 200Amp as per REC Standard.
Dismantling,carriage and Writeback of existing DW poles (60Nos) to Divisional Store Choglamsar.
Dismantling of existing 0.03ACSR conductor(14.3Km), carriage to the newly errected ST poles(250mtr average distance) and re-stringing of the same on the newly errected ST poles
M/S LOBZANG GURMET GOVT CONTRACTOR
DRUK ELECTRICALS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .