Tender Value
₹34 Cr
EMD Value
₹15 L
Closing Date
24 Sept 2020, 6:00 pmClosed
SR DDG AND CE
Sr DDG and CE DGNP mumbai naval dockyard SBS marg mumbai 400023
AUGMENTATION OF INNER BREAK WATER JETTY AT NAVAL DOCKYARD MUMBAI (MAINLY E/M PORTION)
2020_MES_365425_1
DGNP MB 8490A 2
Open Tender
Electrical and Maintenance Works
750 days
MUMBAI
Contractors enlisted with MES/DGNP in Class SS and above and category a i b i and b ii with no adverse remarks in WLR. For further details NIT provisions to be referred. Or contractor meeting the criterion of enlistment.
8 documents required · 8 mandatory
₹3,000
DGNP MUMBAI
₹15 L
Yes
24 Nov 2020
31 Jul 2020
1 Oct 2020
31 Jul 2020
24 Sept 2020
28 Aug 2020
Amount
SCHEDULE 'A' PART-I (BUILDINGS/STRUCTURES)
Construction of TY TRANSFORMER SHED AND TOILET BLOCK complete all as shown on drawings and as specified. NOTE :- Excavated materials shall be removed from the site simultaneously & continuously while doing excavation work as space is not available for storing the excavated earth at site. Excavated materials shall be removed and deposited out side MD land at the tenderers cost. Unit rate quoted shall be deemed to be included for this work also.
Total amount of Schedule 'A' Part I C/o to General Summary on Ser Page No.
SCHEDULE 'A' PART-II-B (EXCAVATION AND EARTHWORK FOR ITEMS UNDER SCHEDULE 'A' PART III TO PART X)
Removing excavated material (soil) to a place outside defence land including loading, unloading, transportation , levelling and any other charges complete all as specified.
Removing demolished building materials etc. (other than soil considered above and items under Schedule of Credit) to place outside defence land including loading, unloading, transportation , levelling and any other charges complete all as specified. NOTE :- Demolished concrete of 0.45 Cum shall be considered as one load.
Total amount of Schedule 'A' Part II-B C/o to General Summary on Ser Page No.
Schedule 'A' Part IV-B (INTERNAL ELECTRIFICATION)
Supply and fixing LED Industrial type light fitting 2 x 24 Watt, 4' aluminium, extruded channel, powder coated with diffuser for glare free light complete with all accessories connected with 3 core flexible copper cable PVC insulated of size 1.5 Sqmm suspended from ceiling with 2 nos of 19mm dia 16 gauge stove enameled steel conduit of required length (minimum 1.00 Mtr) with ball and socked at end for self aligning complete all as specified and as directed. Make: Shakti Model No SZSIBM x 2 x 24 Watt or equivalent model in Havells/ Wipro
Supply and fixing LED linear 2' surface/wall mounted 1 x 10 watt mirror light fitting aluminium extruded channel, powder coated with diffuser for glare free light complete with all accessories connected with 3 core flexible copper cable PVC insulated of size 1.5 Sqmm complete all as specified and as directed. Make: Shakti Model No SZSLAM x 010 Watt or equivalent model in Havells/ Wipro
Supply and fixing industrial type exhaust fan 240 volts, 50Hz, AC, 300mm sweep, 900 RPM single phase with louvers and shutters mounting MS rag and bolts etc. and provision with PVC insulated and PVC sheathed 3 core 1.5 sqmm flexible copper conductor cable FRLSH of suitable length from ceiling rose complete all as specifIed and as directed.
Total amount of Schedule 'A' Part IV-B C/o to General Summary on Ser Page No.
Schedule 'A' Part V-B (EXTERNAL WATER SUPPLY)
Material and labour for ductile iron flanged pipe including specials, Class "K-9", of size 150 mm dia conforming to IS : 8329 including bend, tee, socket, elbow, reducers etc. including jointing and jointing materials complete all as specified and as directed.
Material and labour for ductile iron flanged pipe including specials, Class "K-9", of size 100 mm dia conforming to IS : 8329 including bend, tee, socket, elbow, reducers etc. including jointing and jointing materials complete all as specified and as directed.
Material and labour for making holes of 300 mm dia on RCC/stone floor/wall surface not exceeding 210 cm thick surface with boring machine for passing DI/CI/GI tubing complete all as specified and as directed.
Total amount of Schedule 'A' Part V-B C/o to General Summary on Ser Page No.
SCHEDULE 'A' PART VI-B (EXTERNAL ELECTRIFICATION)
Disconnecting of HT panel and Bus Coupler (6.6/11 KV VCB) consisting of following and handing over to users complete all as specified and as directed:- (a) VCB 630A -02 Nos (Incoming) (b) VCB 630 Amps -04 Nos (Outgoing) (c) Bus coupler-1 No
Supply, installation, testing and commissioning HT dual voltage 11/6.6 KV indoor type VCB panel board, consisting of 02 incomer, 07 Outgoing and 01 bus coupler, made out of 2.0 mm thick CRCA sheet, dust and vermin proof, locking arrangement, duly powder coated totally enclosed free standing floor mounting type, compartment based with truck mounted VCB spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCB with copper busbars, back entry type complete VCB panel confirming to IS and IP 54 class of protection comprising necessary busbar extensions for connecting with existing HT switch gears and following protective and control devices including breakers complete all as specified and as directed :-
(g) Self powered microprocessor based numeric relay comprising of 3 O/C, 1 E/F protection relay with high set low set for phase and earth fault memory, universal auxiliary supply-09 Nos. (for all VCB panels except bus coupler). (h) Master trip relay -09 Nos (for all VCB panels except bus coupler). (j) Trip circuit supervision relay (VAX) - 09 Nos (for all VCB panels except bus coupler). (k) PT fuse failure relay (MVAPM-32) -02 Nos (only for incomer). (l) Anti pumping relay (VAA11) -10 Nos (for each VCB panels) (m) Air insulated rear end bottom entry cable box suitable for termination HT cable - 10 Nos (for each VCB panel) (n) Manual closing/tripping of CB with compartment door closed -10 Nos (for each VCB panel) (o) Trip and closing coil - 09 Nos (for all VCB panels except bus couplers). (p) Sufficient Nos of push button and standard colour coding of indication lamp LED type with back up fuses (for all VCB).
(q) Motor operated spring charge stored energy trip for closing and opening of breaker (for all VCB panels). (r) Manual charging/operating arrangement(for all VCB panels). (s) RS 485 port for communication. (for all VCB panels except bus couplers). (t) One No of space heater with thermostat(for all VCB panels). (u) One No of inside lamp with switch. (for all VCB panels). (v) One No plug point with switch (5A, 230v). (for all VCB panels). (w) Copper busbar common for outgoing and bus coupler with PVC sleeve. (x) Foundation, PCC and any other civil work as per manufacturer instructions. (y) Control wiring with multi stranded copper conductor PVC insulated of suitable size and core as per manufacturer instructions all as required at site. (z) Transformer fault alarm/Trip Aux. relay-07 Nos (for outgoing VCB panels) (aa) Indication lamps for Transformer alarm and trip -07 Nos (for outgoing VCB panels)
(iv) Necessary marking on VCBs for feeders, incomer, outgoing, bus coupler and CTs connected, percentage CT calibrated etc. shall be provided without any extra cost. (v) Necessary bus adaptor compartment for bus coupling shall be provided without any extra cost. (vi) The VCB Horizontal draw out shall be as per IS/IEC-62271-100. (vii) Type test of HT panel shall be conforming to IS/IEC-6227 1-200 (viii) Any other item required to complete the above job but not specified here shall be deemed to be included in the rate quoted by the contractor. (ix) Pre dispatch inspection shall be carried out by the authorised representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorised representative of Accepting Officer. (x) Manufacture for HT Panel shall have Channel Partnership certificate from OEM of VCB/RMU as specified
Supply, installation, testing and commissioning 6.6 KV/ 11 KV, 630Amps, Right extensible, Outdoor, 4 way RMU panel with two Isolators & 2 VCB, SF6 insulated, 11 KV Ring Main unit contained within Stainless steel tank suitable for outdoor use free standing complete all as specified and as directed and comprising of following :- (a) 630 Amp triple pole, manually operated vacuum circuit breaker encapsulated in SF6 Stainless steel tank with independent spring mechanism and fully rated earth switch with provision for earth of the cable - 2 Nos. (b) Air insulated cable boxes with split gland plate suitable for front side bottom entry 3 core cable up to 300 Sq mm -2 Nos. (c) 630 Amp triple pole, single break, 3-position ('ON', 'OFF 'and "EARTH') ring main switches, each with independent manual charged spring mechanism and fully rated earth switch, with provision for earth and test of the cable - 2 Nos. (d) Air insulated cable boxes and glands suitable for front and bottom cable entry 3-core up to 300 Sq mm - 2 Nos.
(xiv) 4 Nos. local ' PULL TO TRIP' mechanism. (xv) 1 No. operating handles. (xvi) 1 Set Copper bus bars common for outgoing feeders (xvii) Manual charging for operation arrangement. (xviii) Fuses for metering and protection system. (xix) Front bottom entry of HT cables. (xx) All standard metering/accessories and compatible to SCADA/ PLC System. (2) Paint finish -All steel work shall be fmished painted in Dark grey shaded 632 as per IS. (3) RMU Panel should have following general characteristics :- (i) Enclosure degree of protection -IP54 (ii) Type of Ventilation -Natural (iii) Rated Enclosure -K10 (iv) Rated power frequency withstand -28/38 KV Voltage KV RMS/min (v) Rated lighting impulse withstand -75/95 KV Voltage KV, 1.2/ 50 micro sec (vi) Short time current rating KA, for sec -20kA/3sec (vii) Rated short ckt making current -50kA (viii) Reference standard -IEC 62271-202
Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 500 KVA capacity and handing over to user all as specified and as directed.
Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 750 KVA capacity and handing over to user all as specified and as directed.
Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 1000 KVA capacity and handing over to user all as specified and as directed.
Designing, Supplying, handling, assembling, installation, testing and commissioning in correct assigned position, effecting proper connection Distribution Transformer step down, outdoor type SCADA compatible of capacity 1.60 MVA, dual ratio 11 KV-6.6 KV/0.440 KV , 3 phase, 50 cycles AC, Ester oil filled type with On Load Tap Changing arrangements with remote control panel operation (RTCC) on 11/6.6 KV/ sides to vary secondary voltage from (+)5% to (-) 15% in steps of 1.25% (16 steps), impedance not less than 6.50% at normal / common tap No.7 including suitable marshalling box and primary side terminals 3 Nos, outdoor bare bushings with arching horn and secondary side terminal extended copper bus bar with cable box on secondary side additional Neutral with one No. solid porcelain type out door bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-1180, primary side delta and secondary side star connected, neutral grounded losses of the transformer as per IS :1180 Level-2 complete all as specified and as directed and having following features :-
(a) Transformer shall be Dyn -11 vector group ester oil immersed, naturally cooled, double wound copper winding core type, Radiator cooled MS tank complete with first fill of ester oil as per relevant IS with ONAN cooling system. The temperature of oil shall not rise 50oC to ambient temperature, of winding shall not rise 60oC. Transformer shall be painted with two coats of epoxy paint as per IS 632. (A) Standard Fittings : (i) Rating and diagram plate alongwith levels where ever necessary, non detachable (ii) Earthing terminals with lugs -2 Nos. (iii) Lifting lugs for main tank & top cover (iv) Thermometer pocket with cap along with thermometer. (v) Air release hole with plug. (vi) Oil conservator tank with oil filling hole, drain plugs Prismatic oil level indicator and maximum oil level marking. (vii) Dehydrating breather charged with silica gel - 01 No.
(viii) LV Bushing - 04 Nos. (ix) Sampling valves, top and bottom. (x) HV Bushing-03 Nos. (xi) Arching Horn on HT side - 03 Nos. (xii) Additional neutral separately brought out side, LV cable end box with bush insulator for neutral earthing. (xiii) First oil fill. (xiv) Drain cum bottom filter valve with plug. (xv) Top filter valve with plug. (xvi) Explosion vent with diaphragm and equalizer pipe (Pressure release valve). (xvii) Jacking lugs and hauling holes. (xviii) Inspection cover. (xix) Detachable radiators with shut off valves between radiators and tank. (xx) Radiator with air release hole and plug. Oil drain hole with plug and lifting eye all as per manufacturer's standards.
(xxi) Base channel 100x50 mm, 460 mm long with hole to make them suitable for fixing on Platform or plinth. (xxii) 150mm dia oil temperature indicator stems type. (xxiii) Double float Bucholtz relay with two sets of contacts and isolating valves. (xxiv) 150mm dia winding temperature indicator with maximum indicating pointer and resetting device. (xxv) 100mm dia magnetic oil level gauge with low level alarm. (xxvi) Terminal connection on the HV bushing (xxvii) Unidirectional reversible roller -04 Nos (width distance should be as per Broad Gauge rails). (xxviii) Marshalling box. (xxix) Neutral Grounding Resister suitable for 1.60 MVA transformer in out door floor mounted enclosure suitable for 45 Degree centigrade ambient temperature and temperature rise 90 Degree centigrade all as approved by GE. (xxx) Indoor type Remote Tap Changer Centre Panel (RTCC) with Automatic Voltage regulator and necessary indications
(xii) Insulated terminal board (with connector) for transformer tap leads. (xiii) Mechanical tap position indicator with handle. (xiv) Tap changing operation counter. (xv) Rating plate. (xvi) Driving mechanism chamber locking arrangement. (xvii) Un-drilled gland plate for cable entry. (xviii) Terminal strips. (xix) Drain cum filter valves. (xx) Stoppers to prevent over travelling of mechanism. (xxi) Indoor floor mounted remote control cubicals (RTCC Panel, AVR relay) with rear accessories with wiring and followings :- (a) Remote tap position indicating meter digital type. (b) Tap change in progress signal lamps with belt (c) Raise / lower push buttons for remote operation (d) Inside illuminating lamp with door switch. (e) Supply on signals.
(m) RTCC and AV shall be suitable for automatic voltage regulation with master follower scheme with tap position indicator as per tap indication in the OLTC mechanism. RTCC shall also be provided with contol gear in respect of fan ON/OFF indication, auto and manual control switch AC supply on and tap changer in progress Indication lamp tap struck indication and alarm. (n) The erection of the transformer shall be done under the Supervision of manufacturer's authorized representative. Certificate in this regard shall be submitted by the contractor duly signed by authorized representative of manufacturer and Engineer-in-Charge/ GE. (o) Transformer order and delivering schedule to be confirmed before dismantling existing transformer.
Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following items from the Sub station (IBW Jetty) complete all as specified and as directed :- (a) ACB 4P 1600A 50KA -1 No (Incoming) (b) ACB (B/C) 1600A -1 No (c) ACB 800A 4 Pole 50 KA - 4 Nos (Out going) Note : The complete dismantled items shall be handed over to user.
Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following items from the Sub station( IBW Jetty) complete all as specified and as directed (a) ACB 4 P 800 A 50 KA -2 Nos (Incoming) (b) Bus coupler ACB 800 A, 50 KA -1 No (c) MCCB 4 Pole 400 A 50 KA -7 Nos (outgoing) Note : The complete dismantled items shall be handed over to user.
Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following items from the Sub station (IBW Jetty) complete all as specified and as directed (a) ACB 4 P, 800 A, 50 KA -1 Nos (Incoming) (b) ACB 800 A, 50 KA -2 Nos (c) MCCB 4 P, 400 A, 50 KA -2 Nos Note : The complete dismantled items shall be handed over to user.
Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, Indoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, front openable, made out of 2 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved color including suitable frame work/ support made out of suitable size of angle iron/ flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sqmm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :- BUSBAR CHAMBER : Electrically grade copper shrouded busbar tinned of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators.
OUTGOING (i) Microprocessor based ACB, 1600 Amps, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = lcw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories. - 05 Nos (ii) Microprocessor based ACB, 1000 Amps, 4 pole, drawout type (EOD), breaking capacity Icu =Ics =Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories - 06 Nos (iii) Microprocessor based ACB, 800 Amps, 4 pole, drawout type (EOD), breaking capacity Icu =Ics = Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories -01 No
Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :- BUSBAR CHAMBER : Electrically grade copper shrouded busbar tinned of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, ftxed on DMC insulators .
(d) Phase Indication lamps (RYB), LED type - 01 No (set of three). (e) MCB SP 2 Amps,"C" series for control protection RYB phases (set of 3) - 01 set. OUTGOING (i) MCCB 320 Amps, 4 pole, 50 Hz, 35 KA with micro processor base release, and adjustable current setting , in built instantaneous protection, Ics =100%Icu (1 sec) complete all as specified and directed. - 02 Nos
Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :- BUSBAR CHAMBER : Electrically grade copper shrouded busbar tinned of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators .
Notes for 6.11 to 6.13: ( Note (a) & (b) are not applicable for item No 6.11) (a) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer. (b) The panel manufacturer should have following certification:
(i) CPRI certification & Degree of protection IP-54 should be in accordance to IEC:60439 /IEC:61439 as applicable’ (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA. (iii) CPRI certification rated current for short circuit not less than 5000A (c) MCCB (Microprocessor based)/ ACBs provided should be capable for on line setting of the current. (d) ACBs provided should be capable for on line setting to the time delay. (e) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make. (f) All incomer ACBs and MCCBs should be compatable with SCADA through communication port for monitoring purpose only. (g) Drawing of panel board should be got approved from GE before fabrication. (h) Panel board should be fully compartmentalized in accordance to form 4 b of lEC 61439-1-2. (j)The copper busbar should be tinned & current density should not be more than 1.6Amp/mm²
Dismantling existing APFC panel 1 & 2 suitable for 1000KVA and 500 KVA transformer and handing over to user complete all as specified and as directed.
Dismantling existing capacitor bank 26 KVAR for 750 KVA Transformer and handing over to user complete all as specified and as directed.
Supply, installation, testing and commissioning electronic based APFC panel outdoor type having aggregate capacity 600 KVAR in 17 stage, microprocessor based along with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out ofStainless steel 2.00 mm thick of grade 316 L including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick having bus bar of aluminum 1250 Amps capacity ,(current density should not be more than 0.8Amp/mm²), three phase and one neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment , all the cover having suitable locking arrangements, fully internally wired with suitable size of thimbles, incoming/outgoing internal connection with PVC insulated PVC sheathed multi stranded copper wire of suitable size all as specified and as directed and comprising of the following :-
(a) Power supply: 3 phase 4 wire line (b) Power rating: 600 KVAR (c) Rated system voltage: 440volts, 50Hz (d) Duty: continuous (e) Main incoming ACB 1250 Amp , 65 KA 4 pole, draw out type (EOD) - 01 No. (f) Power factor corrector relay 17 stages-01 No (g) Capacitor duty contactor for 100 KVAR -04 Nos (h) Capacitor duty contactor for 40 KVAR -04 Nos (j) Capacitor duty contactor for 10 KVAR -02 Nos (k) Power contactor 18 Amp for 5 KVAR -02 Nos (l) Power contactor 18 Amp for 2 KVAR -05 Nos (m) MCCB 360 A, 50 KA TP for 100 KVAR-04 Nos (n) MCB 100 A, 25KA TP for 40 KVAR-04 Nos (o) MCB 25 A, 10 KA TP for 10 KVAR-02 Nos (p) MCB 16 A, 10 KA TP for 5 & 2 KVAR-07 Nos
(ab) Protection fuse 16 A with HRC -03 Nos (ac) Capacitor 5 KVAR fixed with busbar with MCB 20 A TP protection 1 set NOTES :- (a) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.
(b) The panel manufacturer should have following certification: (i)CPRI certification & Degree of protection IP-54 should be in accordance to IEC:60439 /IEC:61439 as applicable (ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA. (iii) CPRl certification rated current for short circuit not less than 5000A (c) ACBs provided should be capable for on line setting to the time delay. (d) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make. (e) All incomer ACBs and MCCBs shall becapabile with SCADA through communication port for monitoring purpose only. (f) Drawing of panel board should be got approved from GE before fabrication. (g) Panel board should be fully compartmentalized in accordance to form 4 b of lEC 61439-1-2. (h) Any item technically required for project functioning of APFC panel but not mnetioned in the item is deemed to be included in item rate.
Dismantling and taking out MS angle iron / flat / channels / plate of any size and thickness and shape for cable supports/ pipe support / structure to feeder pillars/cope boxes/ ladder from existing trench/duct including cutting, bending, drilling, unscrewing & making good existing wall structure and handing over to user complete all as specified & as directed.
Dismantling old unserviceable out door type switch gear panel / feeder pillar box (60 Hz) floor mounted, cubical type, of size of feeder pillar 2000mm (H), 1500 mm (W) and depth1500 mm(D) alongwith associated bus bar, metering , fuses , MCCBs (U/S) switches, indication lamps including disconnecting power cables all as specified and as directed. Note : The complete dismantled items shall be handed over to user.
Dismantling old unserviceable out door type switch gear panel / feeder pillar box (60 Hz) floor mounted, cubical type, of size of feeder pillar 1350mm (H), 1000 mm (W) and depth 650 mm(D) alongwith associated bus bar, metering , fuses , MCCBs (U/S) switches, indication lamps including disconnecting power cables all as specified and as directed. Note : The complete dismantled items shall be handed over to user.
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/ C and O/G feeders form the remote location, including the required civil works/ anchoring bolts for fixing, PCC foundation etc. with and including following complete all as specified and as directed
(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/ off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. (e) Phase Indication lamps (RYB), LED type -01 No (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYE phases (set of 3) -01 set OUTGOING (i) Microprocessor based ACB, 800 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (l sec), 50 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories - 02 Nos
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 60 Hz, AC supply system, fully compartmentalized, both side openable,fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/C and O/G feeders from the remote location, including the required civil works/ anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.
(e) Phase Indication lamps (RYB), LED type -01 No. (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) - 01 set. OUTGOING (i) Microprocessor based ACB, 630 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu= Ics= Icw (1 sec), 50KA, 60 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with ISI marked complete with all accessories -02 Nos Note: All accessories provided shall be suitable for operation on 60 Hz.
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable,fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :-
(d) AC three phase LT/CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/ off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. (e) Phase Indication lamps (RYB), LED type -01 No (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3 ) -01 set. OUTGOING (i) MCCB 400 Amps, 415Volts, 4 pole, 50 HZ, 50 KA with micro processor base release, and adjustable current setting, inbuilt instantaneous protection, Ics=100%Icu (1sec) complete all as specified and directed -02 Nos
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable,fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/ C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :-
(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. (e) Phase Indication lamps (RYB), LED type -01 No. (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) -01 set. OUTGOING (i) MCCB 400 Amps, 415Volts, 4 pole, 50 HZ, 50 KA with micro processor base release, and adjustable current setting, inbuilt instantaneous protection, Ics = 100%Icu (1 sec) complete all as specified and directed -01 No.
Material and Labour for design, supply, fabrication, Installation, testing and commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :-
(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. (e) Phase Indication lamps (RYB), LED type -01 No.(set of three) (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3 ) -01 set. OUTGOING (a) MCCB 63 Amps, 415 Volts, 4 pole, 50 Hz, 25 KA with micro processor base release, adjustable overload, and adjustable current setting , inbuilt instantaneous protection, Ics =100%Icu(1sec) complete all as specified and directed - 05 Nos
Notes for 6.20to 6.24: (a) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.
(b) The panel manufacturer should have following certification :- (i) CPRI certification & Degree of protection IP-54 should be in accordance to IEC:60439 /IEC:61439 as applicable (ii) CPRI certification short circuit withstand strength shall be 50KA RMS for 1sec with initial peak of 105KA. (iii) CPRI certification rated current for short circuit not less than 5000A (c) MCCB’S (Microprocessor based ) /ACB’S provided should be capable for on line setting of the current. (d) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make. (e) All incomer ACBs and MCCBs should be compatible with SCADA through communication port. (f) Drawing of panel board should be got approved from GE before fabrication. (g) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. (h)The copper busbar should be tinned & current density should not be more than 1.6Amp/mm²
Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 3.5 core not exceeding 400Sqmm aluminium/copper conductors and handing over to user all as specified and as directed.
Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 1 core 300Sqmm aluminium conductors and handing over to user all as specified and as directed.
Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 1 core 630Sqmm aluminium conductors and handing over to user all as specified and as directed.
Disconnecting and removing HT 11000V grade cable, PVC insulated heavy duty, size from 3 core 185 Sqmm to 240 Sqmm with aluminium conductors and handing over to user all as specified and as directed.
Dismantling and taking out MS angle iron / flat / channels / plate of any size and thickness and shape for cable supports/ pipe support / structure to feeder pillars/cope boxes/ ladder from existing trench/duct including cutting, bending, drilling, unscrewing & making good existing wall structure and handing over to user complete all as specified & as directed.
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable,fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system formonitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :-
(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete - 01 No. (e) Phase Indication lamps (RYB), LED type -01 No. (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) -01 set. OUTGOING (i) MCCB 160 Amps, 415 Volts, 4 pole, 50 Hz, 25 KA with micro processor base release, adjustable overload, and adjustable current setting , inbuilt instantaneous protection, Ics =100%Icu (1 sec) complete all as specified and directed - 06Nos (ii) MCB 16/25 Amps, SP, 230 Volt, 10 KA, 50Hz with thermal magnetic release i.e. thermal setting 80 -100 % In and magnetic setting 3 -6 In, Ics= 100% Icu -10 Nos
Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specilled and as directed :-
(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No (e) Phase Indication lamps (RYB), LED type -01 No (set of three). (f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) - 01 set. OUTGOING (i) MCCB 40 Amps, 415 Volts, 4 pole, 50 Hz,25KA with micro processor base release, and adjustable current setting, inbuilt instantaneous protection, Ics=100%Icu(1 sec) complete all as specified and directed - 02 Nos
(ii) MCB 40 Amps, 230 Volts, 2 pole, 50 Hz, 16 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics=100%Icu(1 sec) complete all as specified and directed - 02 Nos Notes 6.30 and 6.31 : (a) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer
(b) The panel manufacturer should have following certification :- (i) CPRI certification & Degree of protection IP-54 should be in accordance to IEC:60439 /IEC:61439 as applicable (ii) CPRI certification short circuit withstand strength shall be 50KA RMS for 1sec with initial peak of 105KA. (iii) CPRI certification rated current for short circuit not less than 5000A (c) MCCB’S (Microprocessor based ) /ACB’S provided should be capable for on line setting of the current. (d) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make.
(e) All incomer ACB’S and MCCB’S should be compatible with SCADA through communication port for monitoring purpose only. (f) Drawing of panel board should be got approved from GE before fabrication. (g) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. (h)The copper busbar should be tinned & current density should not be more than 1.6Amp/mm²
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 300 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 240 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 120 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 3 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 2 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 300 Sqmm, 2 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 4 Sqmm, 4 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 1.5 Sqmm, 2 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed
Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 240 Sqmm, 1 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed.
Notes 6.32 to 6.41:- (i) Predispatch inspection and testing shall be done by the officer detailed by the Accepting Officer. All testing shall be performed as per relevant IS. (ii) Testing for IR and continuity shall be recorded before and after laying of cable. (iii) Suitable glands and copper lugs for end termination of cables shall be provided by the contractor without any extra cost to the dept. (iv) No straight through joint shall be permitt if the joint becomes inescapable, the same to be provided by the contractor without any extra cost to the department with written approval of GE. (v) Excavation, Earth work, sand cushioning, cable cover and GI pipe required shall be measured and paid separately.
Laying and connecting retrieved LT cable of size 3.5/3 core 300 to 400 Sqmm with Aluminium/ Copper conductor complete all as specified and as directed.
Dismantling of existing unserviceable DB including MCB's & Supply and fixing MCB Distribution board SPN 8 way, 240V including following MCB's and fixed with 200 Amps rated copper neutral link and earth link complete all as specified and as as directed. (a) MCB SPN, 16A, 10KA-01 No (b) MCB SP, 6-32A, 10KA-06 Nos Note: Complete dismantled items shall be handed over to user.
Supply and fix LED flood light fitting 120Watt with cast alumumium housing including electronic driver, heat shrink reflector toughened glass cover with all accessories having High lumen output, driver PF >0.98, having over voltage protection upto 400volts, surge protection level 7-10 KV, thermal short circuit protection THD <10%, made up of long life LED chips(SMD) in modular with Ra >70 and LED lumen efficiency> 120 lumen per watt, pre-wired complete with all accessories and connecting with 3core flexible copper cable PVC insulated of size 1.5 Sqmm all as specified and as directed. Note : The firm shall give warranty for flood light fitting including driver minimum for 3 years for any defects developed during the period.
Fabricate, supply and fixing hot dip galvanized mild steel conforming to Fe-290, Gde-E-165 framed brackets made out of angle/Tee/Channel sections, including cutting to shape, bending, electric arc welding, drilling holes etc., GI bolts, nuts, washers etc., all as necessary for laying and fixing LT cables complete all as specified and as directed.
Material and labour for horizontal core cutting of required size, length/ width in the RCC trench and wall for passing of cables and pipe lines including dismantling of RCC and cutting of reinforcement bars if needed, without damaging the structure and its strength and making good the disturbed surface to match the existing surface complete all as specified and as directed.
Material and Labour for design ,supply ,fabrication, Installation testing & commissioning factory made , Panel outdoor type ,totally enclosed, dust and vermin proof ,suitably ventilated, floor mounted suitable for 110 Volts DC Supply, fully compartmentalized, both side openable , fabricated out of 2.00 mm thick Stainless steel of grade316L , protection of enclosure IP-54 as per IS:2147 including suitable frame work/support made of 75mm stainless steel flat channel 3.00 mm thick ’front opening with provision for cable entry ,with proper ferrule and cable glands, internal wiring with PVC insulated multistranded copper conductor FRLSH cable of adequate size (minimum 1.5 sqmm ), panel compatible for SCADA system for monitoring of I/C and O/G feeders from the remote location ,including the required civil works /anchoring bolts for fixing ,PCC foundation etc with and including following all as specified and directed :-
BUSBAR CHAMBER : Electrically grade copper shrouded bus bar tinned of capacity equal to 1.5 times of the rated incoming control switch gear including interconnection of all switch gears ,fixed on DMC insulator . INCOMER (a) MCCB 250 Amps ,250 Volts ,2 Pole braking capacity not less than 25 KA microprocessor base release ,adjustable current setting , inbuilt instantaneous protection, Ics =100% Icu (1 sec) complete all as specified directed.-01 No (b) Ammeter 0-500 Amps digital type alongwith all accessories suitable for DC system) – 01No (c) Voltmeter 0-250 Volts digital type suitable for DC system – 01No
(d) Indication lamps LED type suitable for DC system- 01 set (e) MCB SP 2 Amp suitable for 110V DC for control/protection of equipment’s -01 set. OUTGOING OUTGOING (i) MCCB 63 Amps ,250 Volts ,2 Pole braking capacity not less than 16 KA microprocessor base release ,adjustable current setting , inbuilt instantaneous protection, Ics =100% Icu (1 sec) complete all as specified directed.-03 Nos
Notes: (a) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected & fresh panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer’s premises & all routine text like IR & Continuity Tests shall be performed/recorded in presence of authorized representative of Accepting officer. b) The panel manufactures should have following certification. i. CPRI certification & Degree of protection IP-54 should be in accordance to IEC: 60439 /IEC: 61439 as applicable. ii. CPRI certification short circuit withstand strength should be 50KA RMS for 1sec with initial peak of 105KA iii. CPRI certification rated current for short circuit not less than 5000A c) MCCB’s (Microprocessor based) provided should be capable for on line setting of the current. d) All the electrical switch gear like MCCB’s,MCB’s shall be same make. e) All MCCB’S should be compatible with SCADA through communication port for monitoring purpose only f) Drawing of panel board should be got approved from GE before fabrication. (g) Panel board should be fully compartmentalized in accordance to form 4 b of IEC
(i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests) (ii) CPRI certification short circuit withstand strength should be 50KA RMS for 1 sec with initial peak of 105KA. (iii) CPRI certification rated current for short circuit not less than 5000A (e) ACBs provided should be capable for on line setting to the time delay. (f) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make. (g) All incomer ACBs and MCCBs should be compatable with SCADA through communication port. (h) Drawing of panel board should be got approved from GE before fabrication. (j) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2.
Supply, installation, testing and commissioning Advance encapsulated compound based CPRI tested maintenance free, pipe-in-pipe technology upgraded (Zinc & Alloy Coated), ZINC COATED (80-100) microns with pure Zinc (99.9%) & ALLOY COATING (200-250) microns earthing system confirming to IS 3034, outer and inner pipe of 41.9mm, 26.4mm dia respectively, 2 metres length, Zinc coated with additional special Alloy coating 300mm on the topside for additional protection of the Terminal, annular space between the pipes filled up with COMPACT FILL(CF) (Crystalline Conductive Compound) (COMPACT FILL (CF) mixture which is machine pressed in the pipes shall not disintegrate or collapse when outer pipe corrodes), inner pipe extended with terminals for connectivity complete all as specified and as directed. Make "ASHWK"Model-ASEEL-1 9, 2m length (ZC & AC)
NOTES :- (i) The job includes digging the pits and refilling the same by Electrodite/Conductolite Back Fill compound (Ground Enhancer). (ii) The BFC should be eco friendly and it should not contain environmentally hazardous material/metal having ROHS Certification from NABL accredited lab. (iii) The earth pit shall be provided with a FRP earth pit cover for protection and safe guard of the terminals. (iv) In areas where soil condition is bad, good earth is to be arranged to fill the excavated pits by mixing the same with BFC 2 bags (as per soil condition) extra per pit/unit. (v) The material shall have good electrical conductivity & anti corrosion property in wide range of soil conditions.
(vi) Complete work shall be executed all as per manufacturer's instruction. (vii) All the above given dimensions may vary ± 1 mm (viii) The quantity of BFC Electrodite shall be increased according to soil condition and to achive the earth value less than 1 Ω.
Material and labour for GI perforated cable tray of size 450mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed.
Material and labour for GI perforated cable tray of size 400mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed.
Material and labour for GI perforated cable tray of size 350mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed.
Total amount of Schedule 'A' Part VI-B C/o to General Summary on Ser Page No.
SCHEDULE 'A' PART VII-B (L P AIR PIPELINE)
Material and labour for providing air tapping point complete with 100 x 50 x 50 mm dia flanged Tee -01 No, 50 x 25 x 25 mm dia flanged Tee - 02 Nos, 25 mm dia gate valves-04 Nos including rubber gasket and complete with necessary nuts, bolts, washers etc. as required complete all as specified and as directed.
Supply and fixing CI air moisture extractor for outlet of 100mm complete all as specified and as directed.
Supply and fixing sluice valve Cast steel Class PN 1.6 complete with both ends flanged and drilled with ISI marked (IS- 14846) of size 150 mm dia including Stainless steel non rising spindle and hand wheel complete all as specified and as directed.
Supply and fixing sluice valve Cast steel Class PN 1.6 complete with both ends flanged and drilled with ISI marked (IS- 14846) of size 100 mm dia including Stainless steel non rising spindle and hand wheel complete all as specified and as directed.
Supply and fix pressure gauge bourdon with glycerin filled of range 0 to 21 kg/Sqcm, 4" dia and stainless steel body including accessories complete all as specified and as directed.
Total amount of Schedule 'A' Part VII-B C/o to General Summary on Ser Page No.
SCHEDULE 'A' PART VIII-B (FIRE ALARM SYSTEM)
Supply and laying/fixing to wall/ceilingall as per standard norms, 2 core 1.5 Sqmm FRLSH PVC insulated armoured multistranded copper conductor cable ISI marked all as specified and as directed.
Supply & fixing Carbon-di-Oxide fire extinguisher ISI marked of capacity 4.5 Kilogram consisting of welded mild steel cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 300mm long high pressure discharge hose, discharge nozzle, suspension bracket, ISI marked with IS:15683, finishing externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners with internal charge, complete all as specified and as directed.
Supply & fixing Carbon-di-Oxide fire extinguisher ISI marked of capacity 6.5 Kilogram consisting of welded mild steel cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 300mm long high pressure discharge hose, discharge nozzle, suspension bracket, ISI marked with IS:15683, finishing externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners with internal charge, complete all as specified and as directed.
Supply & fixing 6 Kg DCP fire extinguisher ISI marked with stored pressure, handheld, floor mounted type suitable for class ABC fire ISI marked with IS:15683 complete with refill, full length back bracket, hose and clip complete all as specified and as directed.
Supply & fixing 9 Kg DCP fire extinguisher ISI marked with stored pressure, handheld, floor mounted type suitable for class ABC fire ISI marked with IS:15683 marked complete with refill, full length back bracket, hose and clip complete all as specified and as directed. Note: All the work under this Schedule(i.e schedule for fire alaram system VIII ‘B’) shall be got excecuted through approved consultant/ Agency after getting approval from Accepting officer.
Total amount of Schedule 'A' Part VIII-B C/o to General Summary on Ser Page No.
GENERAL SUMMARY
Total Amount of Schedule ‘A’ Part I for “BUILDING AND STRUCTURE” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II-A
Total Amount of Schedule ‘A’ Part II-B for “EXCAVATION AND EARTH WORK” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part III
Lump sum price worked out by the contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part IV-A
Total Amount of Schedule ‘A’ Part IV-B for “INTERNAL ELECTRIFICATION” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part V-A
Total Amount of Schedule ‘A’ Part V-B for “EXTERNAL WATER SUPPLY” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “EXTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part VI-A
Total Amount of Schedule ‘A’ Part VI-B for “EXTERNAL ELECTRIFICATION” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “LP AIR PIPELINE” as listed in Schedule ‘A’ Part VII-A
Total Amount of Schedule ‘A’ Part VII-B for “LP AIR PIPELINE” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “FIRE ALARM SYSTEM” as listed in Schedule ‘A’ Part VIII-A
Total Amount of Schedule ‘A’ Part VIII-B for “FIRE ALARM SYSTEM” brought forwarded from Serial Page No
Lump sum price worked out by the contractor for “REPAIRS TO RCC DUCT AND PROVISION OF NEW DUCT” as listed in Schedule ‘A’ Part IX
Lump sum price worked out by the contractor for "DEMOLITION/DISMANTLING" as listed in Schedule ‘A’ Part X
M/S. KASHI KANCHAN PVT. LTD.
Som Projects Pvt. Ltd.
vijay infraprojects pvt ltd
surendra infrastructure pvt ltd
SOOD ASSOCIATES PVT LTD
Rabina Enterprises Pvt Ltd
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf