Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹36.4 LRejected-Finance | ₹36.4 L | 1 | Rejected-Finance Lowest Bidder |
| 2 | 2₹37.1 LRejected-Finance | ₹37.1 L | 2 | Rejected-Finance 2nd Lowest Bidder |
Tender Value
₹36.4 L
EMD Value
₹73,000
Closing Date
21 Jan 2026, 2:00 pmClosed
EEE EWD Dumka
Dumka
S/R to E.I. in BED Building of Sahibganj College, Sahibganj.
2026_ENRGY_109013_4
Energy/EWD/Dumka/25/2025-26
Open Tender
Electrical Works
45 days
Dumka
Please refer Tender documents.
8 documents required · 8 mandatory
₹5,000
₹73,000
13 Apr 2026
15 Jan 2026
22 Jan 2026
15 Jan 2026
21 Jan 2026
16 Jan 2026
Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core in surface/recessed PVC conduit, with modular switch, modular plate suitable GI box etc as required a) Group - C
Wiring for circuit/ submain wiring along with earh wire with the following sizes of FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit as required
a) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire (For Circuit - 1074m + computer board - 250 from DB)
b) 2 x 1.5 sq.mm + 1 x 1.5 sq mm earth wire (9 Nos street light wiring on building)
c) 2 x 6.0 sq.mm + 1 x 6.0 sq.mm earth wire (6 Nos submain for power)
d) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (18 nos subamain for light, computer)
e) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (21 nos power wiring)
f) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (42 Nos A.C wiring direct from sub panel Busbar @ 25 mtr)
Supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit including dismantling as required a) 1 x 1.5 sq.mm (For inverter wiring)
Supplying and fixing suitable GI box with modular plac and cover in front on surface of in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch. connection, painting etc. as required
Supplying and fixing suitable GI box with modular plac and cover in front on surface of in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 5/6 amps modular switch. connection, painting etc. as required
S/F A following Compact unit made Modular Computer board. a) 9 Module - 1 Nos b) 5 amp switches - 2 Nos c) 5 amp socket - 2 Nos d) 15 amp socket - 1 Nos e) 15 amp switches - 1 Nos
S/F following way single pole neutral, sheet MCB distribution board, 240 volts on surface/ recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gtand plate, interconnections, Phosphatized and powder painted including earthing etc as reqd. (But without MCB/RCCB/Isolator)
a) 6 way double door
b) 4 way double door
c) 2 way double door
S/F following 240 volts, 'C' series/"B" series miniature circuit breaker suritable for lighting and other loads of following poles in the existing MCB DB complete with connection, testing and commissioning etc. as reqd.
a) 6/32 amps, MCB
b) 63 amps, DP MCB
c) 40 amps, DP MCB
S/F 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top'along with 20 Amps'C' series, SP MCCB, in sheet steel enclosure, on surface or in recess with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc as reqd..
S/F LED tube light fitting 20/22 watt including connection etc as reqd.
Supplying and fixing batten/ angle holder including connection etc as reqd.
S/F 2 pin 5 Amp ceiling rose on the existing junction box/woden block ineluding connection etc as reqd.
S/F 9/10 watt L.E.D lamp etc as reqd. (Bajaj/ Phillips/ or equi)
S/F steped type electronic fan regulator deluxe on the exisang switch Box/ cover including connection etc as reqd. (a) Electronic step fan regulator deluxe modular.
S/F PVC/ G.I box of follwing sizes on surface or in recess with sutiable sizes of Phenolic laminated sheet cover infront including painting etc as reqd. (a) 75 mmx75 mmx50mm deep/ (4"x4")
S/F 9" exhaust fan complete including connection etc as reqd.
Supplying and laying of XLPE insulated PVC sheathed aluminium armoured cable working voltage upto 1100 volts as per IS: 7098 (Part I) of following sizes (Make, Havelis,polycab, finolax, capital or equivelant) a) 3.5 core 150 sq mm (from Generator room to Main panel)
b) 3.5x 50 sq mm (Generator Panel to BED block)
c) 3.5 x 35 sq sq mm (Ground floor Main Panel to 1st & 2nd floor Light Main Panel)
d) 3.5 x 70 sq mm (Froin ground floor Main Panel to to 1st floor & 2nd floor Power Main Panel)
e) 3.5 x 25 sq mm ( For light and power subpanel)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 35 sq mm but not exceeding 95 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 95 sq mm but not exceeding 185 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
80mm dia Earthing Electrode 2mtr. Length / 80mm dia Earthing Electrode 3mtr. Length / 50mm dia Earthing Electrode 2mtr. Length/50mm dia Earthing Electrode 3mtr. Length & Backfill Compound chemical 4 Bag(per bag 25 KG)
Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required.
S/F 90W LED Street light Make - havells/bajaj/halonix/jaguar/benlo
S/F 65 mm dia , G.I. bend medium class (For LED street light strengthening)
S/F of 48" Ceiling Fan with all accessories. Make - Bajaj/Usha/Vguard/polar
Providing and fixing following DP/TP&N sheet metal switch disconnector fuse unit in the existing metal board with rewireable type fuses, including drilling holes in metal board . making connections. etc. as required.
32 amps, double pole (for street light on Buildings)
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. ( Main panel Ground Floor)
a) 250 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 100 amps, 10 KA fixed thermal setting MCCB (Solar Incomer & generator incomer) = 2 Nos
c) 100 amps, 10 KA fixed thermal setting MCCB (for 1st & 2nd floor outgoing) = 2 Nos
d) 200 amps, 35 KA adjustable thermal setting MCCB (for 1st & 2nd floor outgoing) = 2 Nos
e) 100 amps 4 pole Changeover = 2 nos
f) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing)= 7 Nos
g) 63 amps DP MCB = 4 Nos
h) Voltmeter = 1 Nos (digital)
i) Ammeter = 1 Nos (digital)
j) Indecator = 9 Nos
k) C.T. Coil = 3 Nos
l) 50mm x 5mm copper tape = 32 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Power Main panel 1st floor)
a) 200 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 4 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 13 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Power Main panel 2nd floor)
a) 200 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 4 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 13 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Solar/Light Main Panel 1st Floor)
a) 100 amps, 10 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 3 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 13 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Solar/Light Main Panel 2nd Floor)
a) 100 amps, 10 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 3 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 13 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Power/Light distribution Panel)
a) 63/100 amps 10 KA fixed thermal setting MCCB (Outgoing) = 1 Nos
b) Indecator = 3 Nos
c) 50mm x 5mm copper tape = 8 Kg
CGST@9%(mailto:CGST@9%塹ᴻ䡿ⲯ嶂藄挧ꮥ)
SGST@9%(mailto:SGST@9%塹ᴻ䡿ⲯ嶂藄挧ꮥ)
Labour Cess @ 1 %
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
technical_147274.pdf
techsummary_147274.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.14 MB
F2.pdf
Tender Documents • 0.27 MB
BOQ_147274.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid