| 1.00 | SITC of Addressable Fire Alarm Control panel - having fixed address capacity of 126 addresses that can be utilized in any combination of detectors/devices/modules across either One (1) Loop [CLASS A] or two (2) stubs [CLASS B] - having three (3) freely programmable relay outputs & four (4) freely programmable INPUT/OUTPUTS - supporting up to 2000 events & allowing individual customer text per device of up to 18 characters - having operating temperature of -5 to 40 degree centigrade with up to 95% relative humidity - having IP30 ingress protection rating - conforming to UL / FM / EN 54 / VDS / LPCB Approved
Including Battery
All Detectors and Devices with in-built isolation (isolators).
MAKE- Siemens Cerberus / Bosch/Honeywell esser | 1 | Nos | 3,15,500 ₹3.2 L | 1,11,000 ₹1.1 L |
| 2.00 | SITC Addressable Repeater panel
UL / FM / EN 54 / VDS / LPCB Approved
MAKE- Siemens Cerberus / Bosch/Honeywell esser | 1 | Nos | 86,000 ₹86,000 | 35,000 ₹35,000 |
| 3.00 | SITC of Addressable Heat Detector in-built isolation (isolators). with base - having both static & differential setting - & having inbuilt line isolation & having integral 360 degree visible LED for alarm indication, providing resistance to environmental & interfering influences like dust, fibers, insects, moisture etc.. Detector should have (2) two selectable parameter settings for detecting Rapid as well as Slow fires - detector should be capable of auto addressing - having operating temperature range of -10 to 55 degree centigrade with </=95% relative humidity & having Ingress Protection rating of IP40 - conforms to UL / FM / EN 54 / VDS / LPCB Approved
Including Back Box,cable glands with Accessories
Make -Siemens Cerberus / Bosch / Honeywell Esser | 12 | Nos | 3,380 ₹40,560 | 2,950 ₹35,400 |
| 4.00 | SITC of Addressable Manual call point in-built isolation (isolators). for direct activation of Fire - having inbuilt isolation & supporting 2 wire installation for both surface & recessed mounting options - having integral alarm indication LED & having operating temperature range of -10 to 55 degree centigrade with ingress protection rating of IP44 - conforming to UL / FM / EN 54 / LPCB Approved
Including Back Box,cable glands with Accessories
Make -Siemens Cerberus / Bosch / Honeywell Esser | 1 | Nos | 3,380 ₹3,380 | 3,100 ₹3,100 |
| 5.00 | SITC of Addressable LOOP POWERED Sounder with strobe - available in either Red or White colour - & with suitable Base for mounting - should have inbuilt line isolation - meeting the EN 54-3 standard & capable of providing max 16 tones & 2 alarm levels [Warning & Evacuation] & up to 99dbA sound output - having operating temperature range of -25 to 70 degree centigrade with </=95% relative humidity with optional IP65 Ingress protection level using deep base - conforms to UL / FM / EN 54 / VDS / LPCB Approved
Including Back Box,cable glands with Accessories
Make-Siemens Cerberus / Bosch / Honeywell Esser | 1 | Nos. | 11,930 ₹11,930 | 7,900 ₹7,900 |
| 6.00 | SITC of Input-Output module having monitorable contact in-built isolation (isolators). input for reporting technical status &/or activating of alarm & having Control output with potential free relay contact for activating alarm,having inbuilt isolation - & having integral LED indicator for indicating Input/Output statuses for alarm/Fault - capable of addressing automatically & supporting 2 wire installation - supporting operating temperature of -25 to 70 degree centigrade with up to 95% relative humidity - having IP65 with housing - conforming to UL / FM / EN 54 / VDS / LPCB Approved
Including Back Box,cable glands with Accessories
Make -Siemens Cerberus / Bosch / Honeywell Esser | 20 | Nos | 5,530 ₹1.1 L | 3,500 ₹70,000 |
| 7.00 | SITC of Addressable 4 Inputs / 4 Outputs Monitor Module, 4 inputs for potential-free contacts. Input lines are monitored for open line and short-circuit (termination resistors). Inputs can be independently configured via the fire control panel for status or alarm messages. 4 outputs with 4 potential-free relay contacts (AC 250 V / 4 A) for fire control installations.Status indication by LED. Power supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail.
UL / FM / EN 54 / VDS / LPCB Approved
Including Back Box,cable glands with Accessories
Make -Siemens Cerberus / Bosch / Honeywell Esser | 5 | Nos | 8,600 ₹43,000 | 16,000 ₹80,000 |
| 8.00 | SITC of PNG Gas Detector with Display, acknowledge key and double compression glands
3 wire gas transmitter flameproof/ Explosionproof CIMFR/PESO Certified Enclosure
-- Detection Method : Natural Diffusion
- Gas to be detected : PNG
- Range : 0-100% LEL
- Detection Principle : Catalytic bead
- Display : 4 Digit Seven segment LED Display,4 LEDs to Indicate Status of Instrument
- Setting : By Using Magnetic Pen Without Opening Cover
- Supply Voltage : 18 TO 36 VDC, Typically 24V DC
- Standard Output1.: 4-20mA Current Output
- Output 2.: TWO SPDT Relays of rating ‘5A/250VAC, 5A/30VDC’
- Enclosure: Cast Aluminium LM6
Along with Basic mounting accessories such as Rawl plug, Self-Thread Screw,
Plain Washer Spring washer, 2mm Allen key & 3mm Allen key etc.
Make - Evikon / Ambetronics / Dragger / Greystone | 12 | Nos | 17,600 ₹2.1 L | 15,100 ₹1.8 L |
| 9.00 | Supply, installation of 2core x 1.5sqmm Copper conductor FRLS Insulated armoured cable fixed to ceiling/wall by means of saddles/supports etc. [Outer sheath of the cable shall have RED color code]
Make -Polycab / RRK / Finolex / Caliplast | 400 | Mtr | 140 ₹56,000 | 130 ₹52,000 |
| 10.00 | Supply, installation of 2core x 1.5sqmm Copper conductor FRLS Insulated armoured cable fixed to ceiling/wall by means of saddles/supports etc. [Outer sheath of the cable shall have Black color code]
Make -Polycab / RRK / Finolex / Caliplast | 200 | Mtr | 130 ₹26,000 | 130 ₹26,000 |
Updated dates
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
18 Nov 2025, 6:55 pmClosed
Officer In-Charge, Engineering TMC
Engineering Department, 6th Floor, Service Block, TMH, Parel
Supply, Installation, Testing and Commissioning of Fire Suppression System for the Kitchen at Service Block, TMH
2025_TMC_883137_1
TMC/Mech/FireSuppre/Kitchen/36
Open Tender
Machineries/ Mechanical Engg Items
90 days
TMH, Parel
As per tender document
6 documents required · 6 mandatory
₹0
₹48,000
TMH, Parel
24 Mar 2026
28 Oct 2025
20 Nov 2025
28 Oct 2025
18 Nov 2025
6 Nov 2025
28 Oct 2025 - 30 Oct 2025
31 Oct 2025
Amount
SITC of Addressable Fire Alarm Control panel - having fixed address capacity of 126 addresses that can be utilized in any combination of detectors/devices/modules across either One (1) Loop [CLASS A] or two (2) stubs [CLASS B] - having three (3) freely programmable relay outputs & four (4) freely programmable INPUT/OUTPUTS - supporting up to 2000 events & allowing individual customer text per device of up to 18 characters - having operating temperature of -5 to 40 degree centigrade with up to 95% relative humidity - having IP30 ingress protection rating - conforming to UL / FM / EN 54 / VDS / LPCB Approved Including Battery All Detectors and Devices with in-built isolation (isolators). MAKE- Siemens Cerberus / Bosch/Honeywell esser
SITC Addressable Repeater panel UL / FM / EN 54 / VDS / LPCB Approved MAKE- Siemens Cerberus / Bosch/Honeywell esser
SITC of Addressable Manual call point in-built isolation (isolators). for direct activation of Fire - having inbuilt isolation & supporting 2 wire installation for both surface & recessed mounting options - having integral alarm indication LED & having operating temperature range of -10 to 55 degree centigrade with ingress protection rating of IP44 - conforming to UL / FM / EN 54 / LPCB Approved Including Back Box,cable glands with Accessories Make -Siemens Cerberus / Bosch / Honeywell Esser
SITC of Addressable LOOP POWERED Sounder with strobe - available in either Red or White colour - & with suitable Base for mounting - should have inbuilt line isolation - meeting the EN 54-3 standard & capable of providing max 16 tones & 2 alarm levels [Warning & Evacuation] & up to 99dbA sound output - having operating temperature range of -25 to 70 degree centigrade with </=95% relative humidity with optional IP65 Ingress protection level using deep base - conforms to UL / FM / EN 54 / VDS / LPCB Approved Including Back Box,cable glands with Accessories Make-Siemens Cerberus / Bosch / Honeywell Esser
SITC of Input-Output module having monitorable contact in-built isolation (isolators). input for reporting technical status &/or activating of alarm & having Control output with potential free relay contact for activating alarm,having inbuilt isolation - & having integral LED indicator for indicating Input/Output statuses for alarm/Fault - capable of addressing automatically & supporting 2 wire installation - supporting operating temperature of -25 to 70 degree centigrade with up to 95% relative humidity - having IP65 with housing - conforming to UL / FM / EN 54 / VDS / LPCB Approved Including Back Box,cable glands with Accessories Make -Siemens Cerberus / Bosch / Honeywell Esser
SITC of Addressable 4 Inputs / 4 Outputs Monitor Module, 4 inputs for potential-free contacts. Input lines are monitored for open line and short-circuit (termination resistors). Inputs can be independently configured via the fire control panel for status or alarm messages. 4 outputs with 4 potential-free relay contacts (AC 250 V / 4 A) for fire control installations.Status indication by LED. Power supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail. UL / FM / EN 54 / VDS / LPCB Approved Including Back Box,cable glands with Accessories Make -Siemens Cerberus / Bosch / Honeywell Esser
SITC of PNG Gas Detector with Display, acknowledge key and double compression glands 3 wire gas transmitter flameproof/ Explosionproof CIMFR/PESO Certified Enclosure -- Detection Method : Natural Diffusion - Gas to be detected : PNG - Range : 0-100% LEL - Detection Principle : Catalytic bead - Display : 4 Digit Seven segment LED Display,4 LEDs to Indicate Status of Instrument - Setting : By Using Magnetic Pen Without Opening Cover - Supply Voltage : 18 TO 36 VDC, Typically 24V DC - Standard Output1.: 4-20mA Current Output - Output 2.: TWO SPDT Relays of rating ‘5A/250VAC, 5A/30VDC’ - Enclosure: Cast Aluminium LM6 Along with Basic mounting accessories such as Rawl plug, Self-Thread Screw, Plain Washer Spring washer, 2mm Allen key & 3mm Allen key etc. Make - Evikon / Ambetronics / Dragger / Greystone
Supply, installation of 2core x 1.5sqmm Copper conductor FRLS Insulated armoured cable fixed to ceiling/wall by means of saddles/supports etc. [Outer sheath of the cable shall have RED color code] Make -Polycab / RRK / Finolex / Caliplast
Supply, installation of 2core x 1.5sqmm Copper conductor FRLS Insulated armoured cable fixed to ceiling/wall by means of saddles/supports etc. [Outer sheath of the cable shall have Black color code] Make -Polycab / RRK / Finolex / Caliplast
Supply, installation of 4core x 1.5sqmm Copper conductor FRLS Insulated shielded armoured cable fixed to ceiling/wall by means of saddles/supports etc. for Repeater panel [Outer sheath of the cable shall have RED / Black color code] Make -Polycab / RRK / Finolex / Caliplast
SITC UL Listed Premium Quality Linear Heat Sensing Cable. Fixed Temperature type detector for Fire Detection. Rated Temperature - 180 deg C Make - GILPRO/ Ansul/ Amerex
SITC Kitchen 6 L (SS) Fire Extinguisher - ISI Marked, mounting brackets , anchor fastner etc complete in all respect Make - Minimax/ Ceasefire / Amerex
Supply, installation of "FIRE EXIT " signege- SINGLE / DOUBLE SIDE - 150*400mm - FOR FIRE EXIT Prolite / Autolite
Supply, installation of Exit Signage Autoglow type. Green Letters with White Back ground . Prolite / Autolite
Supply, installation of EXTINGUISHER Signages Prolite / Autolite
Supply, installation of MCP Signages Prolite / Autolite
Design & SITC Kitchen suppression system - 01( Asper drawing) Hood No 1 Size -5700 X 750mm Hood No 2 Size -4,900 X 800mm Make - GILPRO/ Ansul/ Buckeye 18.01 Stored Pressure Type SS304L 9L X 3nos. (minimum) Cylinder filled with extinguishing agent (Special concentrated Wet Chemical - F Class). Propellent - Dry Nitrogen. Working Pressure 12bar, Diaphragm type Pressure Gauge, SS316 Isolation Ball Valve, Stainless Steel Syphon Tube. 18.02 CE approved Normally Closed type Solenoid Valve, MOC CF8 (SS304 Body, SS316 Internals), Operating Voltage - 24VDC. 18.03 Microprocessor based Agent Release Panel, for Fire Detection and Suppression. Construction - 18 Gauge CRCA sheet with powder coated finish. Capability to save upto 50 recent events / logs, for analyses and review purpose. Potential Free Contact Relays to integrate with other systems. 16 X 2 LCD Dot Matrix Display. Inbuilt Time Delay Feature (programmable). All type of necessary indication LEDs (AC On, System ON, Battery Low, Gas Released, Gas Inhibit, etc) 2 Nos - Battery Backup of 12V, 7 AH. Panel is with inbuilt battery charger.
18.04 UL Listed Premium Quality Linear Heat Sensing Cable. Fixed Temperature type detector for Fire Detection. Rated Temperature - 180 deg C 18.05 Spray Nozzles as per flow design with Blow of Cap. Swirl Internals to spray controlled wet chemical droplets on Fire Source. Duct and Plenum - 15deg Spray Angle. Appliances - 35deg Spray Angle. 18.06 SS316 Enclosure for Cylinders. Provided with Acrylic Inspection Window. Lock and Key Arrangement. Wall mounting arrangement and protects cylinder and valve from any damage or dust. 18.07 UL Listed Audio Visual Hooter, for Pre Alarm and Agent Released Alarm. Wall mounted type. 18.08 UL Listed Manual Pull Station for Releasing the system manually. Dual Action type (Open the Flap, Pull the lever). Resettable with allen key to prevent any un-authorized reset. 18.09 CE approved Normally Open Gas Shut off Valve. Operating Voltage 24VDC. Manual Reset type valve, to prevent auto reset, thus preventing leakage of Gas after system discharge18.10 SS316 Pipes with SS316 Ferrule fittings. SS316 Ferrule Fittings will include Tee, Elbow, Union, Male and Female Connectors. SS304 mounting accessories like Self Drill Screws, Hexagonal Nut and Bolts, Sensor and Tube Mounting 18.11 Commissioning and testing of the above system.
Design & SITC Kitchen suppression system - 02 (As per drawing) Hood No 3 Size -7,400 X 750mm Hood No 4 Size -1000 X 1000mm Make - GILPRO/ Ansul/ Buckeye 19.01 Stored Pressure Type SS304L 9L X 3nos. (minimum) Cylinder filled with extinguishing agent (Special concentrated Wet Chemical - F Class). Propellent - Dry Nitrogen. Working Pressure 12bar, Diaphragm type Pressure Gauge, SS316 Isolation Ball Valve, Stainless Steel Syphon Tube. 19.02 CE approved Normally Closed type Solenoid Valve, MOC CF8 (SS304 Body, SS316 Internals), Operating Voltage - 24VDC. 19.03 Microprocessor based Agent Release Panel, for Fire Detection and Suppression. Construction - 18 Gauge CRCA sheet with powder coated finish. Capability to save upto 50 recent events / logs, for analyses and review purpose. Potential Free Contact Relays to integrate with other systems. 16 X 2 LCD Dot Matrix Display. Inbuilt Time Delay Feature (programmable). All type of necessary indication LEDs (AC On, System ON, Battery Low, Gas Released, Gas Inhibit, etc) 2 Nos - Battery Backup of 12V, 7 AH. Panel is with inbuilt battery charger.
19.04 UL Listed Premium Quality Linear Heat Sensing Cable. Fixed Temperature type detector for Fire Detection. Rated Temperature - 180 deg C 19.05 Spray Nozzles as per flow design with Blow of Cap. Swirl Internals to spray controlled wet chemical droplets on Fire Source. Duct and Plenum - 15deg Spray Angle. Appliances - 35deg Spray Angle. 19.06 SS316 Enclosure for Cylinders. Provided with Acrylic Inspection Window. Lock and Key Arrangement. Wall mounting arrangement and protects cylinder and valve from any damage or dust. 19.07 UL Listed Audio Visual Hooter, for Pre Alarm and Agent Released Alarm. Wall mounted type. 19.08 UL Listed Manual Pull Station for Releasing the system manually. Dual Action type (Open the Flap, Pull the lever). Resettable with allen key to prevent any un-authorized reset. 19.09 CE approved Normally Open Gas Shut off Valve. Operating Voltage 24VDC. Manual Reset type valve, to prevent auto reset, thus preventing leakage of Gas after system discharge 19.10 SS316 Pipes with SS316 Ferrule fittings. SS316 Ferrule Fittings will include Tee, Elbow, Union, Male and Female Connectors. SS304 mounting accessories like Self Drill Screws, Hexagonal Nut and Bolts, Sensor and Tube Mounting 19.11 Commissioning and testing of the above system.
Fitech Engineers Pvt. Ltd. (BID ID -3319049)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.83 MB
techspecs.pdf
Tender Documents • 0.17 MB
techdocumentchecklist.xls
Tender Documents • 0.03 MB
drawing.pdf
Additional Documents • 0.36 MB
BOQ_928214.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid