Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.7 LAccepted-AOC 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹39.4 L+₹2.7 L (7.37%)Rejected-Finance 64 250 2 COD ROAD HASTINAPURI MADHU NAGAR AGRA 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | L2 | Rejected-Finance Not become lowest bidder | |
| 3 | L3₹47.2 L+₹10.5 L (28.7%)Rejected-Finance 240 1 A RAI COLONY CIVIL LINES JHANSI 284001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L3 | Rejected-Finance Not become lowest bidder | |
| 4 | Rejected-Technical WARD NO 4 NEAR MASZID BHATTAGAON DISTT JHANSI 284001 UTTAR PRADESH | JHANSI | UTTAR PRADESH | 284001 | - | Rejected-Technical No enlisted in approriate category |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
16 Feb 2022, 6:00 pmClosed
Major Deepak Kumar
Garrison Engineer Jhansi
REPAIR, MAINTENANCE AND RENEWALS TO VARIOUS FEEDER PILLAR BOXES, LT PANEL, SWITCHGEARS AND CONNECTED WORKS IN OTM AREA AT VARIOUS UNIT LOCATIONS UNDER AGE E/M AT GE JHANSI
2021_MES_498083_2
GE/JHA/TOK/70 OF 2021-2022
Open Tender
Civil Works
Item Rate
180 days
GE Jhansi
Please refer tender document
7 documents required · 7 mandatory
₹500
Yes
GE Jhansi
₹80,000
Yes
19 May 2022
31 Jan 2022
18 Feb 2022
31 Jan 2022
16 Feb 2022
4 Feb 2022
Amount
Design, fabricate, supply, installation, testing and commissioning of indoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick with front and rear openable shutters with locking arrangement. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 300mm above FFL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on front doors of LT Panel. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of indoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick with front and rear openable shutters with locking arrangement. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 300mm above FFL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on front doors of LT Panel. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1500mm x 1300mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of indoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 2mm thick with front and rear openable shutters with locking arrangement. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-43 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 300mm above FFL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on front doors of LT Panel. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:- Location : 614 (I) AAD Bde CV
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1500mm x 1300mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with seperate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1250mm x 1250mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity complete all as specified and directed:-
Note: (i) The Contractor shall submit set of all drawings of the L.T. Panel and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
M&L in replacement of Power Cables, Aluminum Stranded Conductor 300 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH Line and testing on completion all as specified and directed by Engineer-in-Charge. Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ.
All as per item No. 14.00 here-in-before but of size 240 sqmm, 3.5 core.
All as per item No. 14.00 here-in-before but of size 185 sqmm, 3.5 core.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard / dense soil for laying of cables complete all as specified and directed by Engineer-in-Charge.
Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed by Engineer-in-Charge. (Note: Punned down thickness only shall be measured for the purpose of payment)
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
Supply and lay in trenches, un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm for cable protection in trenches complete all as specified and directed by Engineer-in-Charge.
Excavation in post holes (or similar holes) each not exc 0.5 Cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25cm, watering, and removing surplus soil to a distance not exc 50m and making good surface complete in any type of soil.
M&L for mild steel work as in replacement of posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire etc flat iron fillets(for securing wire mesh etc) including all necessary drilling, bolting or riveting etc and similar work confirming to Fe-290 Gde E-165 complete all as specified and directed.
M&L for preparation of new steel surfaces of any description not exc 10 cm in width or girth and painting with two coats of synthetic enamel paint of approved colour over a coat of red oxide primer complete all as specified and directed.
Supply and fix in replacement of Galvanized Steel Chain Link fencing of mesh size 50mm x 50mm and dia of wire 3.00mm with and including line wires fixed to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and directed by Engineer-in-Charge.
M&L for Framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed and hung as gates, including pestle hinges, stops, hand-made sliding bolts, etc. conforming to Fe.290.Gde-E-165 including taking down existing framed work of any description complete all as specified and directed by Engineer-in-Charge.
M&L for Mild steel bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips etc conforming to Fe.290.Gde-E-165 including taking down existing framed work of any description complete all as specified and directed by Engineer-in-Charge.
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in hard/dense soil in the transformer yard complete all as specified and directed by Engineer-in-Charge.
Supply and spread graded coarse aggregate of 63mm nominal size around outdoor transformer and HT 11 KV two/four pole structure complete all as specified and directed.
M&L for Brickwork with sub class ‘B’ bricks on plan built in CM 1:6 complete all as specified and directed.
M&L for rendering 10mm thick cement plaster 1:6 on fair faces of brick work or concrete surfaces finished even and smooth (with out using extra cement) complete all as directed.
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed by Engineer-in-Charge.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping of pole including necessary form work complete all as specified and directed by Engineer-in-Charge.
Supply and erection in replacement of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed by Engineer-in-Charge. (Note: Excavation and concrete shall be measured and paid separately under relevant items of this BOQ).
Supply, fabrication and fixing in replacement of 2.0mm thick Mild steel, plain, black sheets as in cable end boxes and covers for transformers, wall cladding, steel gates and similar work, cut to size, holes punched; including round headed screws, clout nails or rivets and fixed to steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. as required and applying two coats of synthetic enamel paint of approved colour over a coat of red oxide primer including cutting and removing corroded sheet complete all as specified and directed by Engineer-in-Charge.
Preparation of old steel surfaces of outdoor type LT panel boards of any size and painting with synthetic enamel paint of approved colour over a coat of red oxide primer (both internally & externally) and fixing 02 Nos steel danger plates on panel board complete all as specified and directed by Engineer-in-Charge.
Shutdown the power supply, disconnecting all incoming & outgoing cables carefully from outdoor type LT panel board, removing the burnt wiring, cleaning the bus bars, insulators and MCCBs with CTC, meggering the insulation value and replacing the bus bar supporting insulators wherever required to achieve required insulation resistance value, tightening all fasteners (renew if required), reconnecting back the incoming and outgoing cables with suitable cable Lugs, glands and wrapping the insulation tape on all bare conductors, supply and fixing EPDM rubber gasket for all doors for dust & vermin proof etc and testing on completion for proper functioning complete all as specified and directed by Engineer-in-Charge. Note: (i) Replacement of unserviceable MCCBs shall be measured and paid separately. (ii) Replacement of broken/corroded metal sheets/ angle iron parts of panel boards shall be measured and paid separately.
Supply, installation and testing, in replacement, of outdoor type, factory made cubicle panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 600mm x 600mm x 300mm (outer dimensions) for accommodating and including provision of following switchgears complete:- (i) TPN Aluminium bus bar of 50 x 5 mm provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision of suitable cable glands. (ii) MCCB, 250 Amps, 36 KA breaking capacity , 4 Pole, 415 V, 50 Hz, adjustable thermal and magnetic setting including spreader terminals - 01 No
Supply and fix in replacement of MCCB 630 A ,4 pole ,50 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 500 A ,4 pole ,50 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 400 A ,4 pole ,36 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glandsetc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 315 A ,4 pole ,36 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 250 A ,4 pole ,36 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 200 A ,4 pole ,36 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Supply and fix in replacement of MCCB 160 A ,4 pole ,36 KA (Ics =100% Icu) with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable size of cable glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II
M&L for pruning of tree branches up to 3.0 meter clearance all around HT/LT overhead lines and depositing where directed at a distance not less than 50m complete all as specified directed by Engineer-in-Charge. Note: The item will be measured in span length between poles. The approx span length is 50m.
Material and labour for cutting / pulling out of plants / bushes completely from roots including necessary excavation for removing (if required) in the area of outdoor substation yards / surroundings of substation buildings / pump houses, leveling of surface area, removing the grabage and deposited where directed up to 50m distance from the site of work complete all as specified and as directed by Engineer-in-Charge.
Allied Builders
M/s BRIJ KUMAR RAI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .