| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.3 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹50.1 L+₹1.2 L (2.45%)Rejected-Finance E 84 OF HQ CWE NW MUMBAI AGE 87 1 3 GEETA NAGAR NAVY NAGAR COLABA MUMBAI 400 005 | MUMBAI | MAHARASHTRA | 400005 | L2 | Rejected-Finance Being other than lowest | |
| 3 | L3₹50.4 L+₹1.5 L (2.97%)Rejected-Finance | L3 | Rejected-Finance Being other than lowest | |
| 4 | L4₹65.3 L+₹16.4 L (33.5%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L4 | Rejected-Finance Being other than lowest |
Tender Value
Refer Docs
EMD Value
₹99,600
Closing Date
24 Aug 2022, 3:00 pmClosed
GE (NW) Navy Nagar, Colaba, Mumbai
GE NW NAVY NAGAR COLABA MUMBAI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI
REPAIR MAINT OF SUBMAIN WIRING ENERGY METERS AND METER CABIN AT VARIOUS BUILDINGS AND LIFT MACHINE ROOM AT NAVY NAGAR AND REPAIR MAINTENANCE AND REPLACEMENT OF LT PANELS UG CABLES STREET SECURITY LIGHTS AND OTHER EXTERNAL ELECTRIC WORKS AT RASHI AREA
2022_MES_534267_2
8225/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (NW) Navy Nagar, Colaba
Class D and Category b(i)
8 documents required · 8 mandatory
₹500
GE NW NAVY NAGAR COLABA MUMBAI
₹99,600
Yes
17 Oct 2022
5 Aug 2022
25 Aug 2022
5 Aug 2022
24 Aug 2022
11 Aug 2022
5 Aug 2022 - 17 Aug 2022
Amount
Supply, install, testing and commissioning of meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor,cubical indoor type for 415V, 3 phase, 4 wire made out of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 200 Amps rated copper bus bar(All in equal size), top and bottom cable entry with proper size glands including disconnecting cable connections and electronic meters from old meter cabin panel and fixing & connecting in new installed panel with provisions of thimble/lugs and making provisions of vision glasses for meter readings, one spare MCCB compartment, and including PCC on 1:2:4 type B-1 for fixing meter cabin at old meter cabin place complete all as specified and as directed comprising of the following :- Make :- Legrand/Standard/ACCURATE/Electrocontrol
(a) MCCB 100A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA - 01 Nos, Cat No-4200 55 of Make-Legrand/Siemens/L&T/Schneider. (b) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider. (c) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB. (d) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (e) Phase indicator lamp R,Y & B - (01 Set of three). (f) Copper Bus bar, 200 Amps Rated - R,Y,B & N - (01Set of four). (g) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (h) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel. Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing.
All as per Item No 1.00 above but comprising of the following :- (a) MCCB 63A, 4 pole, 415 volt, thermal magnatic release type, Ics=100% Icu, 25 kA-02 Nos, Cat No-4200 53 of Make-Legrand/Siemens/L&T/Schneider (b) MCB SPN 32 Amps- 10 Nos Make-Legrand Cat No-4086 17 or eqivalent to L&T/Schnider/ABB (c) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V, A, F, PF, KW, kVAR, kWH etc of make :- L&T, Cat Ref -WL441010OOOO-01 set or equivalent in Legrand/Schnieder/ABB. (d) Phase indicator lamp R,Y & B - (01 Set of three). (e) Copper Bus bar, 100 Amps Rated - R,Y,B & N - (01Set of four). (f) Reconnecting of submain cable 2 core 4/ 6 Sqmm copper conductor with outgoing of energy meter. (g) Making good the disturbed surface of meter cabin room if any damages occures during shifting of panel. Note :- Before fabrication of panel the contractor has to take approval from accepting officer on drawing.
Taking out old u/sand Supply, installing, testing and commissioning of LT feeder pillar box factory made cubical outdoor type, fabricated out of 2.00 5mm thick CRCA sheet with angle iron base frame made of 40x40x6mm, 45cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-66 protection, with separate hinge door for each compartment for incoming and out going MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with copper busbar (TPN), suitable double compression copper cable glands complete in all respect for bay work station and including provn of the following:- Note:- The panel shall be as per IEC/IS standards - IEC61439 1& 2 and CPRI certified. Make :- Legrand/Standard/ACCURATE/Electrocontrol
(a) S&F MCCB 100 Amps, 4 Pole, 25 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (b) S&F MCCB 63 Amps, 4 Pole, 16 kA, thermal magnetic release, Ics=100% Icu - 01 Nos, (c) S&F RCBO's 63 Amps, 4 Pole 300mA - 01 Nos, (d) S&F MCB SPN 40 Amps, 10 kA, - 01 Nos, (e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc of (f) Phase indicator lamp R,Y & B (Set of 3)- 01 Set (g) S&F Copper Bus bar 250 Amps of suitable size, all are in equal size - Set 1(R, Y, B, N) Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. Make of MCCB/MCB/RCBO's-Legrand/L&T/Havells
Supply and installation of Smart Single Phase Meter with the following specifications: (i) AC Single phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self-healing Mesh network with defalult and on demand display, biling date generation facility, anti-tamper features. Microprocessor and LED/LCD based circuitry. (ii) Meter should support the following data : 30 min instaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey date for energy, mopntly billing survey for cumulative energy and Max Demand. (iii) Meter should have connect/disconnect functionality operable from prepaid billing software. (iv) The meter should support open communication protocol DLMS with the software. MAKE: Secure, L&T, Schneider and HPL,Elmeasure. Note: (a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid mode. (c) The meters would carry 5 year warranty.
S & F cable PVC insulated, PVC sheathed, armoured, FRLS, 1100V grade, 2 core 6 sqmm stranded copper conductor electric cable laid on wall/ roof/ duct complete with proper saddling and connecting to DBs with glands including taking out existing unserviceable cable complete all as specified.
M & L for earthing complete with galvanized steel earth plate electrode 600 X 600 X 6 mm thick buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth strip 32 X 6mm by means of bolts, nuts and washers of galvanized iron or steel upto the test point all as shown in electrical plate No.3 of SSR Part-I connected toExisting earth strip including PCC earth pit with CI cover, GI funnel with wire mesh, GI protection pipe of 40 mm dia for earth lead and 20mm GI pipe for watering, excavation and earth work in any type of soil, filling the pit with charcoal and common salt surrounding the earth plate complete all as specified and directed by Engr-in-Charge including testing on completion.
M&L of aluminium strip 25x3.15mm with saddles and fixing screws etc. for roof conductors above ground.
M&L of test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 Nos 8mm dia 25mm long hex head screw
M&L scrapping old worn out paint from complete indoor type meter cabin panels and painting with one coat of synthetic enamel paint (incl front door in side and indl compartment outer side etc also) over a coat of primer and spray painting complete including fixing sticker danger sign board suitable for LT panel board all as specified and as directed by engr-in-charge.
Taking down defective street light fitting of any size/ type/ capacity from height of pole/walls/high mast of any location exceeding 3.0 m height for repair work and re-fixing back after repair work including checking, inspecting, testing and commmissioning complete all as directed by Engr-in-Charge. Note:a) The M/L for Items like electronic drivers,surge protection devices etc shall be measured and paid separately under relevant items here in under this Schedule. b) Necessary tools like ladders & other T&P required etc shall be arranged by the Contractor. c) The rate quoted deemed to be inclusive for minor parts nut bolts, circle clips, clamps etc if any required at site.d) The M/L for repairs to LED panel is not included in the scope and shall be measured and paid separately.
Supply only the following spares suitable for LED street/Flood light fittings of make: Bajaj/Crompton/Phillips/Havells/Wipro/Orient/C&S/Polycab/Shakti
Electronic driver suitable for outdoor LED fitting of capacity 70 to 110 Watt.
Electronic driver suitable for outdoor LED fitting of capacity 30 to 60 Watt.
Surge protection device compatible with industrial & outdoor LED fitting of capacity 10 KV complete all as specified and as directed.
Surge protection device compatible with industrial & outdoor LED fitting of capacity 5 KV complete all as specified and as directed.
Dismantling LED light fitting of Make:Bajaj /Crompton/ Phillips/ Havells/ Wipro/Orient/C&S/Polycab/Shakti of capacity 70 to 110 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Dismantling LED light fitting of Bajaj/ Crompton/ Phillips/ Havells /Wipro/ Orient/C&S/Polycab/Shakti of capacity 30 to 60 W ,strip opening the elctronic driver, LED panel complete, identifying defective LEDs , replacement of defective LEDs complete including soldering, replacement of pitted control wiring from LED panel to driver etc complete, including testing and commissioning complete. Note : The rate quoted is not inclusive of taking down and refixing of street light fittings and shall be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 4500 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 45 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items. Make:Bajaj/Havells/Crompton/Wipro
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items. Make:Bajaj/Havells/Crompton/Wipro
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 72 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items. Make:Bajaj/Havells/Crompton/Wipro
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 9000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 90 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items. Make:Bajaj/Havells/Crompton/Wipro
Taking out old RCC Poles of any size
Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) all as directed incl dismantling old one. NOTE :- Earth work, Cement concrete in foundation, coping etc will be measured and paid separately under relevant item. Make : M/S India Electric Pole Mfg Co MH /M/S Bombay Tubes/ M/S Singh Profile Pune/ Kalinga Tubes
Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) all as directed incl dismantling old one. NOTE :- Earth work, Cement concrete in foundation, coping etc will be measured and paid separately under relevant item. Make : M/S India Electric Pole Mfg Co MH /M/S Bombay Tubes/ M/S Singh Profile Pune/Kalinga Tubes
Supply, laying and commissioning, testing armoured heavy duty electric cable with copper conductor, 1100 volts grade of size 4 sqmm 4 core laid in trenches, passing through pipes, fixed on walls complete including connecting properly by means of thimbles/bottle lugs and taking out old u/s damaged cables. Make: Polycab/Gloster/Finolex/Asian/Universal
All as per item No-21.00 here in before but of size 2.5 sqmm 3 core including taking out old u/s damaged cables.
All as per item No- 21.00 here in before but of size 1.5 sqmm 2 core including taking out old u/s damaged cables.
M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete.
M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work.
S & F astronomical Timelite distribution board IP-54 with contactor, relay and prewired, 32A, 3 pole, 230 Volt , and Astronomical programmable time switch with backup of 6 years, 28 memory locations, current capacity 16 A with one CO time switches for street light complete. Make: Legrand/L&T/Indoasian
S & F in repairs digital time switch 3 phase of current capacity 16 Amps incl any type of accessories with suitable capacity of contactor after taking out unserviceable one. Make: Legrand/L&T/Indoasian
S & F in repair 3 pole power contactor with coil voltage 230 volt AC of current carrying capacity 32 to 40 Amps complete including control wiring thimbles etc complete all as directed. Make: L&T/Legrand/ABB/Seimens
Earthing complete with Galvanised Steel earthplate of size 60x60cmx6.3mm thick electrode and GI wire 4 sqmm dia as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to earth wire 4 sqmm by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. all as required at site for complete earthing).
S&F loop-in/loop-out box of outer size size 225mmx295mmx122mm made out of FRP(Hot moulded type) with weather proof canopy and locking screws along with with 5/6 Amps MCB - 01 No, 50 Amps rated 3 pole connector- 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector etc complete in the box, duly fixed to to steel tubular/rail/PCC/RCC pole using 25 x 3mm aluminium clamp not less than, including suitable gland and lugs for connecting cable complete all as directed including dismantling old one. Make: Hager/Sintex/Legrand
S&F street light bracket bend to shape made as required of 32/40mm dia 1 mtr long GI pipe light grade fixed to pole/wall with flat iron clamp of size 40x6mm two number with the help of nuts and bolts for fixing of street light fitting including making all electric connection including taking out old one complete all as specified and as directed.
M&L for preparation of old painted steel surfaces of 9 m long steel poles incl removing oily/greasy spots and applying one coat of aluminium paint complete including applying a coat of white wash on pole coping and lettering the pole details with white letters/ blackground etc complete all as directed
Excavation in trenches not exc 1.5 mtr wide and not exc1.5 mtr in depth for laying of cables etc. in any type of soil and getting out all as specified and directed by Engineer-in-Charge. Note : Rate includes removing of paver blocks carefully and stack properly for refixing after laying of cables .
All as per above item No.34 above but exceeding depth 1.5 mtr and n exceeding 3 mtrs.
Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils.
Removing excavated material from the site of work and transporting out of Station/site of work suitable to the contractor all as specified.
Supply, filling, spreading levelling and well ramming the river sand around cable in trenches for cable cushioning all as specified and directed.
Material and labour for 60 mm thick coloured interlocking paver tiles/ blocks, lacquer finish of size 250x250 mm having compressive strength of 35N/Sqmm, zig-zag (uni-paver) shape in flooring tested as per IS : 15658-2006, with and including layer of 50 mm thick natural river sand bed compacted complete as specified and directed.
Supply, laying un-reinforced precast concrete cable cover class LV type 1 flat size 250mm x 150 mmx 40 mm.
Cutting existing road surfaces or hard standing 0.45 mtr depth (22 thick comprising bituminuous topping) for laying of pipes/cables and making good disturbed surfaces to match with existing surfaces.
Material and labour for cement concrete type C-2, 1:3:6 (40mm graded stone aggregate), for coping and finished surface without using extra cement.
Supplying and laying with commissioning and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade of size 150 sqmm 3.5 core laid in trenches, passing through pipes, fixed on walls complete including connecting properly by means of thimbles and taking out old u/s damaged cables. Make: Polycab/Gloster/Finolex/Asian/Universal
All as per Item No-42.00 here in before but of sizes, 120 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 95 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 70 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 50 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 35 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 25 sqmm, 3.5 core.
All as per Item No-42.00 here in before but of sizes, 16 sqmm, 4 core.
All as per Item No-42.00 here in before but of sizes, 10 sqmm, 4 core.
All as per Item No-42.00 here in before but of sizes, 10 sqmm, 2 core.
M&L for 50mm dia High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe, for road crossing of cable or for cable protection laid in trenches or above ground surface fixed in repairs all as specified and directed.
All as per Item No-52.00 here in before but of sizes, 75mm dia
M&L for GI pipe ,light grade 50mm dia for road crossing or in hard standing for protection of cable above or under ground surface including taking out old one all as specified and directed.
Taking out old u/s and Supply, installing, testing and commissioning of LT feeder pillar box factory made cubical indoor type, fabricated out of 2.0mm thick CRCA sheet with angle iron base frame made of 40x40x6mm, 45cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-66 protection, with separate hinge door for each compartment for incoming and out going MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with copper busbar (TPN), suitable double compression copper cable glands complete in all respect for bay work station and including provn of the following:- Note:- The panel shall be as per IEC/IS standards - IEC61439 1& 2 and CPRI certified. Make :- Legrand/Standard/ACCURATE/Electrocontrol
(a) S&F MCCB 160 Amps, 4 Pole, 25 kA, thermal magnetic release, Ics=100% Icu - 01 Nos,
(b) S&F MCCB 100 Amps, 4 Pole, 16 kA, thermal magnetic release, Ics=100% Icu - 02 Nos,
(c) S&F MCB SPN 32 Amps, 10 kA, - 60 Nos,
(d) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc of
(e) Phase indicator lamp R,Y & B (Set of 3)- 01 Set
(f) S&F Copper Bus bar 400 Amps of suitable size, all are in equal size - Set 1(R, Y, B, N)
Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. Make of MCCB/MCB/RCBO's-Legrand/L&T/Havells
Taking out old u/sand Supply, installing, testing and commissioning of LT feeder pillar box factory made cubical outdoor type, fabricated out of 2.00 5mm thick CRCA sheet with angle iron base frame made of 40x40x6mm, 45cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-66 protection, with separate hinge door for each compartment for incoming and out going MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with copper busbar (TPN), suitable double compression copper cable glands complete in all respect for bay work station and including provn of the following:- Note:- The panel shall be as per IEC/IS standards - IEC61439 1& 2 and CPRI certified. Make :- Legrand/Standard/ACCURATE/Electrocontrol
(a) S&F MCCB 100 Amps, 4 Pole, 25 kA, thermal magnetic release, Ics=100% Icu - 01 Nos,
(b) S&F MCCB 63 Amps, 4 Pole, 16 kA, thermal magnetic release, Ics=100% Icu - 01 Nos,
(c) S&F RCBO's 63 Amps, 4 Pole 300mA - 01 Nos,
(d) S&F MCB SPN 40 Amps, 10 kA, - 01 Nos,
(e) Digital panel meter with LCD multifunction meter with CT/PT and all parameters as V,A,F,PF,KW,kVAR,kWH etc of
(f) Phase indicator lamp R,Y & B (Set of 3)- 01 Set
(g) S&F Copper Bus bar 250 Amps of suitable size, all are in equal size - Set 1(R, Y, B, N)
Note: All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. Make of MCCB/MCB/RCBO's-Legrand/L&T/Havells
Supply and fixing in repairs MCCB 100 Amps 25 KA , 50 Hz , Thermal magnetic release , ics=100%icu complete all as specfied and as directed.Make: Legrand/Havells/ABB
Supply and fixing in repairs MCCB 63 Amps 16 KA , 50 Hz , Thermal magnetic release , ics=100%icu complete all as specfied and as directed.Make: Legrand/Havells/ABB
Supply and fixing in repairs RCBO's 63 Amps 16 KA , 50 Hz , Thermal magnetic release , ics=100%icu complete all as specfied and as directed.Make: Legrand/Havells/ABB
Supply and fix in repair aluminium strip 25 x 3 mm with saddless and fixing screws etc. for roof/wall conductors and down conductors above ground complete with sadlless and insulators made out of porcelain and fixing screws for wall/roof conductor/down conductor including nut bolts & washers drilling and riveting for joints of suitable size as required at site all as specified and directed by Engr-in-Charge . Note porcelain insulators are to be fixed at an interval of not more that 75 cm
shree arihant constrution
NOEL ENGINEERS
Shree Ayyappa Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .