Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-Tender Fee not submitted |
Tender Value
Refer Docs
EMD Value
₹18,760
Closing Date
3 Sept 2022, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
Creation of 100 KVA Substation along with HT and LT Line
2022_PDD_183956_1
ED/UDH/72 of 2022-23 dt. 13-08-2022
Open Tender
Electrical Works
Turn-key
90 days
Tajoor Ward no 6 Mohalla Khudshana block Majalta
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Executive Engineer Electric Division JPDCL
₹18,760
29 Sept 2022
13 Aug 2022
5 Sept 2022
13 Aug 2022
3 Sept 2022
13 Aug 2022
13 Aug 2022 - 20 Aug 2022
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV Line 0n 8 mtr PCC poles 30mm Sq ACSR conductor for creation of 100 KVA Transformer at village Tajoor W.No. 6 Mohalla Khudshana Block Majalta Pyt. Channi District Udhampur
8 mtr. Long PCC Pole (PCC WL 200Kg)
GI V cross-arm with top bracket including clamps
GI channel X-arm including clamps and braces
30mm² ACSR Conductor
11 KV polymeric composite pin insulator 12 KV, 5KN, lighting impulse 75KV positive and 80KV Negative, Creepage distance 320mm
11 KV polymeric composite Disc insulator 12 KV, min failing load 45KN, lighting impulse 75KV positive and 80KV Negative, Creepage distance 320mm with fitting
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti- Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
11 KV GO, AB Switch 3-phase,3-Pole, 200 Amp, vertical type at tapping point
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT Line 0n 8 mtr PCC poles 30mm Sq ACSR conductor for creation of 100 KVA Transformer at village Tajoor W.No. 6 Mohalla Khudshana Block Majalta Pyt. Channi District Udhampur
8 mtr. Long Pole (PCC-WL-200Kg)
GI U-Clamp for shackle insulator
30mm² ACSR Conductor Weasel.
Shackle Insulators
Galvanized Nuts and Bolts.
LT line Spacer
Danger Plates with Clamps
Anti Climbing Device with Clamps
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey,Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation of 100 KVA Transformer at village Tajoor W.No. 6 Mohalla Khudshana Block Majalta Pyt. Channi District Udhampur
11/0.433kV, 3-phase Distribution Transformers 100 KVA with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 KV ,10 KA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( PCC-WL 300 Kg)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT distribution box for 100 kVA DTR with MCCB for incomer and SFU's for outgoing circuits
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Danger plate with clamps
Wedge connector/PG clmaps
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
SUMIT SHARMA
udhay partap singh
AJAY KAPOOR
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .