Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹29,000
Closing Date
22 Jul 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
(1) Pyt. Tikri-B (2) Pyt. Malhar Block Udhampur (3) Pyt. Malhar lower (4) Pyt. Seen Thakran (5) 25 KVA PHC Hartaryan and Mathan Pyt. Sunari under PRI Grants
2023_PDD_221135_1
ED/Udh/39 of 2023-24 dt. 12-07-2023
Open Tender
Electrical Works
Turn-key
60 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹29,000
7 Aug 2023
12 Jul 2023
24 Jul 2023
12 Jul 2023
22 Jul 2023
12 Jul 2023
12 Jul 2023 - 17 Jul 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr. Long PCC poles on 30mmsq. ACSR Weasel conductor at Pyt. Tikri-B (Installation of LT Electric Poles in Pyt. Tikri-B)
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles on 30 mm sq. ACSR Weasel Conductor at Pyt. Malhar (Shifting and installation of electric poles in pyt. Malhar Block udhampur pyt. Malhar)
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Survey, Supply, Transportation, Carriage, Ereciton, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles on 30 mm sq. ACSR Weasel Conductor at Pyt. Lower Malhar (Installation of cemented poles for Pyt. Malhar Lower, Block Udhampur )
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles on 30 mm sq. ACSR Weasel Conductor at Pyt. Seen Thakran ( Installation of electric poles in Pyt. Seen Thakran)
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR condcutor at Pyt. Telta PHC (Sunari) for creation of 25 KVA Sub Station (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
9 mtr. Long PCC Pole (PCC WL-300kg)
GI V-Cross arm with Top Bracket including clamp.
GI Channel X-arm including clamps and Braces.
100 mm sq. ACSR Weasel Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Installation of 25 KVA substation at Telta PHC Hartyan. (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
11/0.433kV, 3-phase Distribution Transformers 25 KVA with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² (2ckt.) 1.1 kv Grade, PVC insulated Al. stranded conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Cement bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, 30 mm sq. ACSR condcutor at Pyt. Telta PHC Hartyan for creation of 25 KVA substation (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr long PCC poles, 30 mm sq. ACSR condcutor at Mathan Block Udhampur pyt. Sunari for creation of 63 KVA Sub Station (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
9 mtr. Long PCC Pole (PCC WL-300kg)
GI V-Cross arm with Top Bracket including clamp.
GI Channel X-arm including clamps and Braces.
30 mm sq. ACSR Weasel Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Installation of 63 KVA substation at Mathan (Sunari) (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
11/0.433kV, 3-phase Distribution Transformers 63 KVA with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² (2ckt.) 1.1 kv Grade, PVC insulated stranded conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Aluminium Strip.
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
GI Barbed wire for Anti Climbing
Painting of 9 mtr long ST poles with two coat of Aluminium Paint and one coat of Red Oxide Paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, 30 mm sq. ACSR condcutor at Mathan (Sunari) for creation of 63 KVA substation (Installation of 25 KVA Transformer at PHC Hartaryan and Mathan Block Udhampur pyt. Sunari)
8 mtr. Long PCC Pole (PCC WL-200kg)
GI U clamps for Shackle Insulator
30mm sq. ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Galvanized stay set with 50*8 mm stay clamp, guy insulator(2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 16 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
VEENA CONSTRUCTION CO.
RAJINDER KUMAR
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .