| 1 | L1₹36.2 LAccepted-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹40.7 L+₹4.2 L (11.4%)Rejected-Finance | L2 | Rejected-Finance Not being Lowest | |
| 3 | L3₹40.7 L+₹4.2 L (11.5%)Rejected-Finance | L3 | Rejected-Finance Not being Lowest |
Tender Value
₹40.0 L
EMD Value
₹80,100
Closing Date
29 Jul 2022, 6:00 pmClosed
GE Chandimandir
Garrison Engineer Chandimandir panchkula Haryana 134107
GE/CHM-34/2022-2023 PROVN OF 200KVA TRANSFORMER, 10 TON ACS AND 20 KVA UPS FOR RNC AT CHANDIMANDIR
2022_MES_532790_1
GE/CHM-34/2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Chandimandir
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Garrison Engineer
₹80,100
Yes
21 Oct 2022
22 Jun 2022
5 Aug 2022
22 Jun 2022
29 Jul 2022
9 Jul 2022
Amount
Dismantling of boarding, any description, fixed in any position with nails complete all as specified and directed.
Anodised aluminium snap grid frame work for false ceiling ,all as specified
Hangers 4 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long complete, all as specified
4mm thick Non asbestos fibre cement building boards fixed or laid/ inserted to timber/GI/Aluminium framework with screws, all as specified.
Anodised aluminium (with powder coating of minimum 50 micron thickness) frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc, complete all as specified
Sheet glass 4.80mm thick, ordinary quality and glazing with aluminum beading in square exc 0.5 sq.m in each pane , all as specified.
Supplying, installing and commissioning of split type air conditioner with cooling function EER 3.2 of capacity 2.00 TR, five star rated with cordless remote control unit and in built air ioniser, plasma filter for better indoor air quality, five star rated suitable for wall mounted, single phase, 230/250 volt AC including breaking necessary hole in wall for fixing indoor and outdoor unit and making good to disturbed surfaces with cement mortar to match with existing finishes after commissioning, PVC pipe medium duty 25 mm dia for draining out condensed water, all as required including necessary electric connections, complete all as specified and directed. Note :- (i) Quoted rates shall deem to includ the cost of drain pipe, copper tubing of requisite length and 4 sqmm multi standard copper cable , brackets, etc. (ii) Installation and commissioning to be done through OEM / its authorised service centre / agency.
Automatic copper wound voltage stabilizer of capacity 5 KVA , digital display type for low and high voltage correction , equipped with electronic transistorised relay, time relay for two minute suitable for correction on single phase 50 cycles, AC supply ,input voltage supply between 170 V to 250 V and stabilized voltage between 220 ±5% , all as specified . Note : This item shall be fixed with AC catered in respective item of this schedule.
Supplying and fixing, commissoning and testing of air conditioner of output capacity 30000/33000 K. Cal Per hour (10/11 ton) , indoor outdoor package type suitable for operational on three phase AC electric supply including air cooling system, ducting/piping , plumbing and electric connection, complete all as specified and directed, comprising of following:- (a)Supply of Air Cooled Package split units with scroll Compressor working on R 407C refrigerant gas. The unit should be factory charged with Refrigerant.The outdoor unit shall be factory assembled and unit shall be housed in a sturdy weather proof casing constructed from rust-proof mild steel or GI with powder coated finish, suitable for operation on 380 - 415 Volts 50 Hz three Phase AC Supply of capacity 10/11.0 TR ,air Cooled Package units including gas and gas Charging . (b) Galvanised sheet steel ducting of rectangular shape of length as required and fabricated at site including 2 gauge for plenum box, 24 gauge for acoustic linning ,duct insulation with Nitrile rubber 19 mm, aluminium Powder coated supply Grills, MS Volume control damper, outdoor unit stand, refrigerant piping per circuit from indoor to outdoor , canvas connection,insulating pad,PVC Drain pipe of 25 mm dia of requisite length , requisite wiring from indoor to outdoor with 4 core, 2.50 Sqmm copper conductor cable, making good the disturbed surfaces of wall, complete all as required at site as per manufacturers reccomendations for efficient functioning of the unit. Note- i)The work is to be carried out in RNC of WC. ii)The contractor is requested to visit the site before quoting to ascertain the site requirement .
Single pole and neutral enclosure with a two pin and earth plug socket, complete with one single pole MCB 32 Amp,240V flush type, all as specified.
MCB SP 40 to 63 Amps 240 Volts having braking capacity 10 KA "C" characterstic, all as specified .
Sub main wiring with 2 runs of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 6 Sqmm FRLSH, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of size not less than 25mm dia including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 6 sqmm FRLSH 1100 volts grade cable continuous earth wire of green colour code complete, all as specified and as directed. Note:- (a) Two runs of 6.0 sqmm cable and one run of 6 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealing conduit and making good to disturbed surfaces and matching with existing finish. (c) Colour code shall be red for phase, black for neutral and green for earth.
Sub main wiring with 4 runs of single core PVC insulated and PVC Unsheathed, multistranded copper condutor of nominal area 16 Sqmm FRLSH, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of size not less than 32mm dia including all fittings and one run of PVC insulated and PVC unsheathed, multistranded copper conductor of nominal area 16 sqmm FRLSH 1100 volts grade cable continuous earth wire of green colour code complete, all as specified and as directed. Note:- (a) Four runs of 16 sqmm cable and one run of 16 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealing conduit and making good to disturbed surfaces and matching with existing finish. (c) Colour code shall be red for phase, black for neutral and green for earth.
Vertical TPN MCCB DB, double door, flush type, 4 way 200 Amps suitable for MCB 415 volts ,all as specified.
Vertical TPN MCCB DB, double door, flush type ,4 way 200 Amps suitable for MCCB upto 125 amps 415 volts ,all as specified.
MCCB four pole of 200 Amps, 3 phase 415 Volts having breaking capacity 25 KA 50 Hz , all as specified .
MCCB four pole of 63 Amps, 3 phase 415 Volts having breaking capacity 16 KA 50 Hz , all as specified .
MCB triple pole ,63 Amps 415 Volts having breaking capacity 25 KA 50 Hz , all as specified .
MCB triple pole and neutral ,63 Amps 415 Volts having breaking capacity 16 KA 50 Hz , all as specified .
Supply, installing, testing and commissioning of online UPS 20 KVA, three phase, 360 VDC , input 340-460 VAC , output 415 VAC with inbuilt isolation transformer and 12 Volt 100Ah SMF batteries for 60 minutes backup including battery rack and connectors, all as specified and directed.
Supply, installing, testing and commissioning of grid of minimum 3 Sealed maintenance free chemical earthing electrode, each individual earthing electrode having following specification :- (a) Diameter of the pipe-80 mm, thickness of the pipe-3.9 mm, Length of the pipe- 3000mm, Galvanised thickness- 80-100 micron, Type of galvanising- Hot dipped , Chemical used in the pipe- High conductive and crystalline conductive mixture ( CCM) , Chemical approx weight 12 Kg. (b) Ground back filled compound 50 kg as conforming to IS 3043 properly mixed the after all around the electrode. (c) Necessary boring in ground in any type of strata/soil and connecting to test point. (d) Construction of brick masonry earth pit of internal size 30cm x 30cm and 30cm deep including finishing work and fixing of CI cover as manufacturer specification complete all as specified and directed (e) Testing for proper working. NOTE- Earth resistance at each grid should be less than 1 ohm at test point .
Copper strip of size 32 x 6mm, fixed on wall or laid in floors/buried in ground, all as specified and directed.
Excavation in trenches in any type of soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth, for laying of cable, poles etc and getting out, complete all as specified.
All as per item No here in before but depth exe 1.5 mtr but not exe 3.0 mtr .
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each, complete all as specified.
Removing excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point ,complete all as specified.
Sub class B bricks for protection to UG cable, laid in trenches, complete all as directed.
Dry sand cushioning to UG cable 8 cm thick before laying and 15cm thick after laying complete all as specified and directed. Note:- Punned thickness shall be measured and paid.
80 mm bore, light grade galvanized iron pipe for cable protection, fixed along the poles/walls or laid under road/culvert etc, complete all as directed.
Supply , installing, commissioning and testing transformer step down, Copper wounded, Outdoor type complete with standard fittings HT 11 KV/433 volts (at no load) 3 phase 4 wire, 50 Hz, 200KVA capacity, core type double copper wound, oil immersed. naturally cooled,. Oil naturally Air neutral (ON AN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with victor group DYn-11 with natural brought out on secondry side (LV side) and having tapping at +- 7.5% in steps of 2.5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temp rise should not exceed 45 degree celsius in oil and 55 degree Celsius in HV/LV winding when measured by resistance method after continous full load run on an ambient temperature of 40 degree Celsies. The Transformer shall be IS- 1180 level III marked and shall comprises of the following :- (a) Three Nos porceian bushing suitable for 11 KV on HV side complete with copper rods, nuts and washers (b) One cable box on LT side (Secondary side) consisting of four Nos porcelain bushing with copper rods, complete with nuts and washers with cable glands (c ) Oil conservator with filter type drain valve and oil level gauge (d) De- hydrating breather with first type fill of dehydrating agent (Silica Gel) (e) Explosive vent, thermometer pocket on tank cover .Oil level gauge , Oil drain filter valve, Lifting lugs, Oil filling hole with cap , plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers. (f) One no 100 mm dia dial type thermometer vapour pressure type , having range 0-120 Degree Celsius with metal guard having maximum perimeter temperature reading indicator with re- setting devices (g) Two earthing terminal on tank cover to facilitate fixing of 25x4 mm GI iron earth strip for earthing of body (h) Rating plate and terminal marking plate (j) Extra bushing for neutral, out side the cable box for providing independent set of earthing for neutral. (k) First filling of new transformer oil, IS- 335, level III marked (Make savita/power link) filtered and tested. NOTE: (i) Transformer shall be painted two coats of epoxy paint. (ii) Transformer shall be 5 star rating & energyconvervant (Energy conservation Binary Corps) for which necessary test certificate to be produced by Contractor form OEM of the transformer. (iii) Pre dispatch inspection of transformer shall be carried out be rep of Accepting Officer at manufacturer premises with overall cost quoted by Contractor. Nothing extra shal be payable on this account. (iv) After installation of the transforme, the same shall be tested and commissioned by SEI and equipment/instruments required for testing shall be arranged by Contractor. Cost of the same shall also be deemed to be included in the item rates quoted by the Contractor
HT cable 11 KV grade, XLPE insulated (earthed) screened, PVC bedded, galvanized iron strip armoured with stranded aluminium conductor cable of cross sectional area 95 sqmm, 3 core, ISI marked with IS:7098 (part-II) as amended upto date in trenches/ ducts/ through pipes etc and making connection and testing, complete all as specified and directed.
XLPE insulated, LT armoured electric cable with aluminium stranded conductor 1100 volts grade ,cross-sectional area 240 sqmm, 3.5 core laid in trenches/pipes/ducts/walls with necessary cable lugs and glands, nuts, bolts and washers etc and testing, complete all as specified and directed.
Gang operated air break switches complete with drop out fuse unit assembly , triple pole, manually operated, mounted on insulators and steel frame,vertical isolation 12 insulators type with operating mechanism worked from ground level for rating 200 Amps, 11000 volts complete with GI operating pipe of heavy duty grade of suitable length ,complete all as directed.
Earthing complete with galvanized steel earth plate electrode size 600x600x6.0mm thick buried directly in ground vertically in a pit of depth not less than 2.25 mtr below ground levels with top edge of the earth plate not less than 1.5 mtr below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and including galvanized iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanized including GI protection pipe light grade 40mm bore connected to main earth wire on pole light grade 20 mm bore connected to main earth wire on pole or control board or main switch and GI pipe medium grade 20mm bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:2:4 type B-1 20 mm graded stone aggregate excavation and earth work all as shown in electrical plate No 3 of MES Schedule part I of 2009 connected to earthing test point indicaed including testing on completion, all specified & as directed.
Cross arms,supports, clamps etc fabricated from structural steel section including nuts, bolts , washers, welding, bending ( cold or hot ) drilling holes for bolts , bent to any shape or size as indicated or directed inclusive of one primer coat of red oxide zinc chromate one under coat and one finishing coat of aluminium paint, complete all as directed.
Jumpers in red/yellow/blue colour for HT lines/connections made from aluminium conductor single core PVC insulated cable of suitable size, complete including winding wires, aluminium tapes etc , all as specified and directed.
Steel tubular swaged poles with mild steel base plate, closed at top as specified, type 410 SP-55 (11 metre long) including painting with two coats of black bitumonous paint internally through out and externally up to the planted depth, remaining external portion to be painted with two coats of aluminium paint over a coat of red oxide primer, complete all as specified. NOTE: Excavation and earthwork, foundation concrete will be meaured and paid for separately, under the respective item(s).
Plain Cement Concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in pole foundations etc, complete all as specified.
Plain Cement Concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate as in pole / strut coping, complete all as specified.
Anti climbing devices, spikes type fabricated out of M.S. bars ( round,square and flat ) including nuts,bolts,washers and clamps in two halves, made to shape to suit the cross section of the pole, complete all as directed .
Danger notice plate of size 25cm x 20 cm , 1.6 mm thick of mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size for HT pole, complete all as directed.
Pin type insulator porcelain, vitreous white/brown including one galvanised MS spindle nut and two GI washers of size 150 mm height, 150 mm dia for 11000 volts , complete all as directed.
Single disc porcelain, vitreous white/brown insulator 255 mm dia and 145 mm height assembly for tension with tension clamps for conductor ,working pressure 11000 volts ,complete all as directed.
Cutting groove of width appx 300 mm and depth not less than 800mm in road/concrete surface for laying of 80 mm dia GI pipe and refilling the soil in layers incl watering and well ramming and making good the disturbed road/hard surface with Plain Cement Concrete 1:2:4 type B-1 using 20 mm graded crushed stone aggregate, complete all as directed.
Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint, complete with and including jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 95 Sqmm, complete all as specified and directed.
GI wire of 4 mm dia for connecting earth test point to lightening arrestor installed on top of 11 mtr long poles four pole structures, complete all as directed.
Lightening arrestors HT 11 KV expulsion type, transmission class, discharge capacity 65 kilo amp complete with all fitting, all as directed.
LT Panel board, indoor type suitable for floor mounting, size not less than 1200 x 1200 x 450 mm , with locking arrangement , fabricated out of 2 mm thick CRCA sheet and ISMC 75 for base frame, powder coated , dust/water and vermin proof , suitable for 415 volts 3 phase 50 Hz , complete with and including the following accessories :- (a) Four pole MCCB 315 amps capacity 35/36 KA 415 volts with adjustable thermal & magnetic release and Ics = 100 % of Icu - 01 No (Incoming) (b) Aluminium strip bus bars sleeve insulated and mounted on epoxy insulators, 600 amps capacity, TPN - 01 set (c) Four pole MCCB 100 amps 25 KA 415 Volts with adjustable thermal and magnetic release and Ics = 100 % of Icu -04 Nos (d) LED type indicators RYB - 01 set. (e) LT CTs 315/5 amps - 03 Nos (f) Multifunctional meter 96 mm x 96 mm, flush mounting, digital type - 01 No (g) Earthing terminals - 02 Nos. (h) Danger notice plate dully rivetted/fixed on front door - 01 No (j) Internal wiring of the panel board circuits with copper conductorPVC insulated single core cable of suitable dia including control MCB SP in each circuit.
LT Panel board, outdoor type double door , suitable for floor mounting of size not less than 600 x 900 x 450 mm with locking arrangement , fabricated out of 3.15 mm thick CRCA sheet, powder coated , dust/water & vermin proof , suitable for 415 volts 3 phase 50 Hz having ISMC 75 for base frame, 750 mm long legs of 50mm x6 mm angle iron (04 Nos) grouted in PCC 1:2:4, all as directed, complete with and including the following accessories :- (a) Four pole MCCB 315 amps capacity 35/36 KA 415 volts with adjustable thermal & magnetic release and Ics = 100 % of Icu - 01 No (b) LED type indicators RYB - 01 set. (c) Earthing terminals - 02 Nos. (d) Danger notice plate dully rivetted/fixed on front door - 01 No
KUNDRA CONSTRUCTIONS
Vasudeva Trading Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .