| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.8 LAccepted-AOC 0 PRAGATIPUR DHARMA SARMA PATH BIRUBARI KAMRUP ASSAM 781016 | KAMRUP METRO | ASSAM | 781016 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹37.3 L+₹31,490 (0.85%)Rejected-Finance PRAGARI NAGAR BYE LANE 3 HOUSE NO 05 SATGAON UDAYAN VIHAR GUWAHATI 781171 | KAMRUP METRO | ASSAM | 781171 | L2 | Rejected-Finance Not Validated (other than lowest bidder) | |
| 3 | L3₹46.0 L+₹9.0 L (24.4%)Rejected-Finance HOUSE NO 29 A SIJUBARI NIZARA PATH PO PS HATTIGAON GUWAHATI 38 | KAMRUP METRO | ASSAM | 781038 | L3 | Rejected-Finance Not Validated (other than lowest bidder) | |
| 4 | L4₹50.3 L+₹13.3 L (36.1%)Rejected-Finance | L4 | Rejected-Finance Not Validated (other than lowest bidder) | |
| 5 | Rejected-Technical F NO A1 APURBA ENCLAVE BRINDABAN PATH RUPNAGAR KAMRUP GUWAHATI ASSAM 781005 | KAMRUP METRO | ASSAM | 781005 | - | Rejected-Technical Suspension imposed by GE Jorhat |
Tender Value
Refer Docs
EMD Value
₹87,380
Closing Date
25 Dec 2023, 6:00 pmClosed
GE GUWAHATI
GE GUWAHATI, PO SATGAON, DISTT KAMRUP - 781027
SPECIAL REPAIR/REPLACEMENT OF LIGHTENING PROTECTION SYSTEM, EARTHING NETWORK AND CONNECTED ITEMS OF OTM/MD ACCN UNDER GE GUWAHATI
2023_MES_630186_1
GE/GUW/61/8381 OF 2023-24
Open Tender
Civil Works
Item Rate
180 days
GUWAHATI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE GUWAHATI
₹87,380
Yes
23 Feb 2024
28 Nov 2023
27 Dec 2023
28 Nov 2023
25 Dec 2023
12 Dec 2023
28 Nov 2023 - 5 Dec 2023
Amount
Disconnecting/Taking down old unserviceable Earthing pit of any type with accessories including removing demolished materail out side MD land complete all as specified and as directed.
Material and labour for earthing complete with GI earth plate 600mm x 600mm x 6.3 mm thick electrode buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level connected to GI earth strip 25 x 4 mm by means of bolts, nuts checks nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES schedule Part-I and including 40 mm bore light grade GI protection pipe (upto 7.5 metres beyond outer edge of earth pit) PCC M-10 grade (Nominal Mix) using 40 mm graded stone aggregate in pit with 40mm thick RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced with 8mm dia bar both way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, common salt ad chaarcoal filling, necessary excavation and warth work complete all as specified and as directed. Note: Rate of item is deemed to be incuded for excavation in hard rock, by compressor machine to achieve required depth.
Material and labour for earthing complete with GI earth plate 600mm x 600mm x 6.3 mm thick electrode buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level connected to GI earth strip 32 x 6 mm by means of bolts, nuts checks nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of MES schedule Part-I and including 40 mm bore light grade GI protection pipe (upto 7.5 metres beyond outer edge of earth pit) PCC M-1+B500 grade (Nominal Mix) using 40 mm graded stone aggregate in pit with 40mm thick RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced with 8mm dia bar both way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe,, common salt ad chaarcoal filling, necessary excavation and warth work complete all as specified and as directed. Note: Rate of item is deemed to be incuded for excavation in hard rock, by compressor machine to achieve required depth. Note for Sl No 2 & 3 (i) It the desired earth resistance is not acheived during testing as per IS the complete earthing shall be carried out by the contractor at his wan cost and no extra clain shall be admissable. (ii) Length of earth strip/electrode beyond 7.5m shall be seasured and paid separately under respective items of this BOQ (iii) Resistance value should be less than 5 Ohm
Material and labour for earthing complete with copper earth plate 900mm x 900mm x 5mm thick electrode buried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less then 1.5 metres below normal ground level connected to GI earth strip 50 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shoen in electrical plate No 3 of MED schedulr Part-I and including 80 mm bore light grade GI protection pipe (upto 7.5 metres beynd outer edge of earth pit) PCC M-1+B500 grade (Nominal Mix) using 40 mm graded stone aggregate in pit with 40mm thick RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced woth 8mm dia bar noth way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, coon salt and chaarcoal filling, necessay excavation and earth work complete all as specified and as directed. Note: Rate of item is deemed to be included for excavation in hard rock, by compressor machine to achieve required depth.
Material and labour for earthing complete with copper earth plate electrod 600mm x 600mm x 3 mm thick electrode buried directly in ground (earth pit not less then 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level connected to copper earth strip 20 x 30 mm by means of briazzing made out og copper steel all as shown in electrical pate No 3 of MES schedule Part-I and including 40 mm bore light grade GI protection pipe (upto 7.5 metres beyond oter edge of earth pit) PCC M-10 grade (Nominal Mix) using 40mm graded stone aggregate in pit with 40 mm thick RCC graded stone aggregate, reinfroced with 8mm dia bar both way @ 150mm c/c, watering arrangement with funnel and wire mesh and 20 mm bore light grade GI watering pipe, common salt and chaarcoal filling, necessary excavation and earth work complete all as specified and as directed. Note:-Rate of item is deemed to be included for excavation in hard rock, by compressor machine to achieve required depth. Note: (i) If the desired earth resistance is not achive during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissable. (ii) Length of earth strip/electrode bwyond 7.5mtr shall be measured and paid under relevent item of this BOQ. (iii) Resistance value shall be less than 5 Ohm. (iv) Copper plate shall be of 99.99% Copper.
Taking down of unserviceable copper earthing strip any size complete all as specified and directed.
Supply and Fixing of copper strip of size 20mmx3mm thick for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, complete all as specified and as directed. Note : Copper strip shall be 99.99% of copper.
All ae per item No 7.00 here in above but fixing only complete all as specified and as directed. Note: Old serviceable copper earthing strip retrieved from serial item No 7.00 here-in-before shall be used under this item .
Taking down of unserviceable aluminium earthing strip any size complete all as specified and as directed.
Supply & fixing of copper strip of size 32mmx6mm thick for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicted situation for loop earthing etc as in repair complete all as specified and as directed.
Material & Labour for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of size 25x3mm aluminium strip complete all as specified and as directed.
All as per item No 11.00 here in above but fixing only complete all as specified and as directed. Note: Old serviceable Aluminium earthing strip retrieved shall be used under this item.
Taking down of unserviceable GI earthing wire any size complete all as specified and as directed
Material and Labour for galvanised steel wire of size 4mm dia for earth continuity conductor of main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit pipe or fixed to poles or any other inicated situation for loop earthing etc complete all as specified and as directed.
All as per item No 14.00 here in above but fixing only complete all as specified and directed. Note: Old serviceable Aluminium earthing wire retrieved from serial item No 14.00 here-in-before shall be used under this item.
Material and labour for 32mm bore galbanised iron pipe, light grade including all firings and fixed laid in trenches or fixed to wall/ along the pole for protection of cable including taking down old GI pipe, complete all as specified and as directed. Note Excavation & earthwork shall be measured & paid for separtely.
Supply and Fixing of earthing test point terminal block made of gun metal or phosphorus bronze of size 75mmx75mmx25mm thick drilled and screws including MS box 2 mm thick if suitable size for protection of test point terminal, including dismantling of old unserviceable test point complete all as specified and as directed.
Material and Labour for cutting of existing steel tubing for alteration or additions (each cut measured) of size 50/40mm bore complete all as specified and as directed.
Material and Labour for screwing existing steel tubing for lateration or additions of size 50/40 mm bore complete all as specified and as directed.
Supply and Fixing of Air termination, single pointed copper rod 12mm dia and 300m long (99.9% molecularly copper) with complete acessories fixed on copper strip for earth conductivity to ground as in repair complete all as specified and as directed.
Supply and Fixing of Air termination, single pointed Al rod 12mm dia and 300mm long with complete acessories fixed on AI strip for earth conductivity to ground as in repair all as specified and directed.
Supply and laying in trenches 20mm nominal bore light grade galvavised coated steel tube conforming to IS 1239(Part-1) including all fittings conforming to IS 1239 (Part-2) complete all as specified and as directed. Note: Excavation & earthwork shall be measured & paid for separately under relevant item of this BOQ
Supply and fixing funnel with mesh for earth pit all complete as specified and as directed
Surface excavation not exceeding 30 cm deep in soft loose soil and averaging 15 cm deep and getting out including removing the materials to a distance not-exc 60 mtr including cutting vegetation complete all as specified and as directed.
Supply and Fixing of PCC M-10 grade (nominal mix) usign 40mm graded stone aggregate for earthing pit of outer size 450x450x300mm, wall thickness 10mm and RCC cover in reinforced cement concrete M-15 grade (Nominal Mix) using 20mm graded stone aggregate, reinforced with 8mm dia bar both way @ 150mm c/c of size 450x450x80mm including GI funnel and necessary earth work including taking down old earth pit cover of conventional earthing complete all as specified and directed.
Material and labour for Earth Pit Indicator for existing earthing pit made out of 16 mm dia, 60 cm long M S square bar embedded in PCC M-10 grade (nominal mix) using 20mm graded stone agreegate in PCC block of size 30cm x 30cm x 3mm including C I plate size 30cm x 30cm x 3mm tthick fixed on side wall of PCC block complete all as specified and as diredted. Note: (i) The cost for writing of following lettering shall be deemed to be included in the unit rate of this item. (a) Type of earthing like as Chemical or Copper plate of GI plate or GI wire or Copper strips. (b) Location (c) Pit No (d) Results (e) Date of Testing (e) Date of Testing (ii) The earth pit indicator shall be provided near to eathing.
Supply and Fixing of factory made Poly propylene earthing earth pit cover made out of Hi Grade heavy duty propylene , HD PVC Chamber of outer size 300x300mm, with safe working load 2000 kg including taking down old earth pit cover complete all as specified and as directed
Material and Labour for copper brazing of two copper strip of size 20mm X 3mm thick to 32mm X 6mm thick/copper rod of 17mm dia fixing on wall with the help of post insulator/ fixing on pole with the help of clamp and post insulator complete all as specified and as directed
Suppy and fixing of post insulator for earthing strip including taking down old post insulator complete all as specified and as directed
Supply and laying in trenches 15 mm dia galvanised iron tubing medium grade with and including all fittings such as bends, elbows, tees, short pieces, union etc in trenches including taking down & dismantling of existing 15mm dia GI pipe complete all as specified and as directed
Supply and Fixing for 15mm dia Gate valve iron wheel head screwed both ends ISI marked fixed to GI pipe including taking down & dismantling of existing 15mm dia gate valve complete all as specified and as directed
Supply and Fixing of 500 liters capacity white colour triple layer, rotational moulded, polythene water storage tank (Cylindrical vertical with closed top) hoisted and fixed on roof in position, including all fitting such as connection pieces with GI tank nipple for inlet, outlet, washout and overflow etc complete all as specified and as directed.
MAC ENGINEERS
M/S SEWAK SINGH
Ankur Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .