| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.5 LAccepted-AOC AMLA TOLA DISTT KATIHAR BIHAR 854105 | KATIHAR | BIHAR | 854105 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹29.9 L+₹2.6 L (9.52%)Rejected-Finance 01 PATHWALIYA GONDA GONDA GONDA UTTAR PRADESH 271001 | GONDA | UTTAR PRADESH | 271001 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹35.3 L+₹7.9 L (29.0%)Rejected-Finance 16 INDIA EXCHANGE PLACE SUIT NO 32 3RD FLOOR KOLKATA 700 001 | KOLKATA | WEST BENGAL | 700001 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹37.7 L+₹10.3 L (37.9%)Rejected-Finance VILL JETHIA NATUN PARA PO JETHIA HALISAHAR PIN 743135 | 24 PARAGANAS NORTH | WEST BENGAL | 743135 | L4 | Rejected-Finance Other than lowest |
Tender Value
₹34 L
EMD Value
₹68,000
Closing Date
11 Mar 2023, 6:00 pmClosed
GE(FW) Kolkata
D9 Commissariat Road Hastings Kolkata 700022
SPL REPAIR TO LT PANELS AT OD-2, P-1, SS NO-02, SS NO-04 AND SS NO-06 WITH ALLIED WORKS UNDER GE (FW) KOLKATA
2023_MES_580355_1
8986/FW/E8
Open Tender
Civil Works - Others
Item Rate
120 days
GE(FW) Kolkata
Ref tender documents
7 documents required · 7 mandatory
₹500
GE(FW) Kolkata
₹68,000
29 Mar 2023
11 Feb 2023
13 Mar 2023
11 Feb 2023
11 Mar 2023
25 Feb 2023
Amount
Taking out unserviceable LT panel board (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000 mm x 2000 mm x 900 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 2000 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS Channel of size 75x40mm complete with legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including supply and fixing of the following accessories :-
ACB, 4 pole, 50 KA, 1000 Amps, Manual Draw out (MDO) Icu= Ics=Icw (1sec), 415 Volts AC - 01 No (Make: L&T, Cat No: UW110NFD01800 / SCHNEIDER, Cat No: MVS10N4MW6L/ LEGRAND, Cat No:0287 32/ C&S Cat No: WX10N4P*A(S) or equivalent model in ABB/HAGER)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discharge current 100 kA -01 No (MAKE: L&T, Cat No:AUSP123PN100 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 36 KA, thermal magnetic release, 320 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM98403OOQOOG / HAGER, Cat No: HNJ321DR / SCHNEIDER, Cat No: LV540308/ LEGRAND, Cat No: 6676 54/ ABB, Cat No: 1SDA116377R1 / C&S Cat No: CSE3N400ATM4P-*)
MCCB, 4 pole, 36/40 KA, thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT201DR / SCHNEIDER, Cat No: LV525342 / LEGRAND, Cat No: 4202 48/ ABB, Cat No: 1SDA116345R1 / C&S Cat No. CSE2NN250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC - 04 Nos (Make: L&T, Cat No: CM90642OOMO / HAGER, Cat No: HHS161DR / SCHNEIDER, Cat No: LV516313 / LEGRAND, Cat No: 6690 30 / ABB, Cat No: 1SDA116250R1 / C&S Cat No. CSE2M250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 100 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM91712OOKOOG / HAGER, Cat No: HHS101DR / SCHNEIDER, Cat No: LV510317 / LEGRAND, Cat No: 4200 55 / ABB, Cat No: 1SDA116246R1 / C&S Cat No. CSE1M125ATM4P-* )
MCCB, 4 pole, 25 KA, thermal magnetic release, 63 Amps, Ics=100% of Icu, 415 Volts AC - 01 No (Make: L&T, Cat No: CM91712OOHOOG / HAGER, Cat No: HHS064DR / SCHNEIDER, Cat No: LV510315 / LEGRAND, Cat No: 6697 16 / ABB, Cat No: 1SDA116244R1 / C&S Cat No. CSE1M125ATM4P-* )
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 300/5A - 01 Set (Set of 03)
LED indicating lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
Taking out unserviceable LT panel board (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000 mm x 1800 mm x 900 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 1200 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS Channel of size 75x40mm complete with legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including supply and fixing of the following accessories :-
ACB, 4 pole, 50 KA, 800 Amps, Manual Draw out (MDO) Icu= Ics=Icw (1sec), 415 Volts AC - 01 No (Make: L&T, Cat No: UW108NFD01800 / SCHNEIDER, Cat No: MVS08N4MW6L / LEGRAND, Cat No:0287 31/ C&S Cat No: WX08N4P*A(S) or equivalent model in ABB/HAGER)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discharge current 100 kA -01 No (MAKE: L&T, Cat No:AUSP123PN100 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 36 KA, thermal magnetic release, 400 Amps, Ics=100% of Icu, 415 Volts AC - 01 No (Make: L&T, Cat No: CM98403OOROOG / HAGER, Cat No: HNJ401DR / SCHNEIDER, Cat No: LV540309/ LEGRAND, Cat No: 6676 55 /ABB, Cat No: 1SDA116378R1 / C&S Cat No.CSE3N400ATM4P-*)
MCCB, 4 pole, 36 KA, thermal magnetic release, 320 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM98403OOQOOG / HAGER, Cat No: HNJ321DR / SCHNEIDER, Cat No: LV540308/ LEGRAND, Cat No: 6676 54/ ABB, Cat No: 1SDA116377R1 / C&S Cat No: CSE3N400ATM4P-*)
MCCB, 4 pole, 36/40 KA, thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT201DR / SCHNEIDER, Cat No: LV525342 / LEGRAND, Cat No: 4202 48/ ABB, Cat No: 1SDA116345R1 / C&S Cat No. CSE2NN250ATM4P-*)
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 300/5A - 01 Set (Set of 03)
LED indicating lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
Taking out unserviceable LT panel board (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000 mm x 2000 mm x 900 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 1200 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS Channel of size 75x40mm complete with legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including supply and fixing of the following accessories :-
ACB, 4 pole, 50 KA, 800 Amps, Manual Draw out (MDO) Icu= Ics=Icw (1sec), 415 Volts AC - 01 No (Make: L&T, Cat No: UW108NFD01800 / SCHNEIDER, Cat No: MVS08N4MW6L / LEGRAND, Cat No:0287 31/ C&S Cat No: WX08N4P*A(S) or equivalent model in ABB/HAGER)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discharge current 100 kA -01 No (MAKE: L&T, Cat No:AUSP123PN100 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 36/40 KA, thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC - 03 Nos (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT201DR / SCHNEIDER, Cat No: LV525342 / LEGRAND, Cat No: 4202 48/ ABB, Cat No: 1SDA116345R1 / C&S Cat No. CSE2NN250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC - 06 Nos (Make: L&T, Cat No: CM90642OOMO / HAGER, Cat No: HHS161DR / SCHNEIDER, Cat No: LV516313 / LEGRAND, Cat No: 6690 30 / ABB, Cat No: 1SDA116250R1 / C&S Cat No. CSE2M250ATM4P-*)
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 300/5A - 01 Set (Set of 03)
LED indicating lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
Taking out unserviceable LT panel board (of any size) and Supply, install, commissioning and testing of outdoor type LT panel board, cubical type, sloping canopy top roof, dust and vermin proof, made out of 3.15 mm thick CRCA sheet of size 2000 mm x 2000 mm x 900 mm, fabricated in CPRI approved factory with front and back openable door (with locking arrangement) and making compartment for each ACB/MCCB/change over switch separately, duly powder coated over a coat of red oxide zinc chrome primer inclusive of four numbers aluminium bus bar of 1200 Amps capacity (of adequate length), for three phase and neutral system, fixed over and including 4 nos insulators, pre-wired with PVC insulated stranded copper conductor (of adequate size), all incoming / outgoing connection to be made with copper lugs and copper strips, with provision of cable entry and exit at mid portion of the panel board (with cable gland),and two numbers Danger Notice Plate (of size 20 cm x 15 cm, suitable for LT line, made out of 0.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS Channel of size 75x40mm complete with legs not more than 450mm long including grouting with PCC 1:2:4 type B1 complete all as directed by the Engr-in-Charge including supply and fixing of the following accessories :-
ATS, 4 pole, 50 KA, 630 Amps + AST controller(MDO) Icu= Ics=Icw (1sec), 415 Volts AC - 01 No (Make: L&T, Cat No:CK90167BSOO+ CK90192OOOO/ SCHNEIDER, Cat No:J07ATSC30600K500 / HAGER Cat No.HIB463I+HZI815I / ABB Cat No.1SYN108726R1001+1SCA122946R1001/
MCCB, 4 pole, 36 KA, thermal magnetic release, 630 Amps, Ics=100% of Icu, 415 Volts AC - 02 Nos (Make: L&T, Cat No: CM94106OOT1OG / HAGER, Cat No: HNJ631DE / SCHNEIDER, Cat No: LV563309/ LEGRAND, Cat No: 6676 57 / ABB, Cat No: 1SDA116379R1 / C&S Cat No.CS630NFMU*4P)
Surge protection device, 3 phase, 4 module, 3P+N, type 1+2, for protection against direct and indirect lightning surge, maximum discharge current 100 kA -02 Nos (MAKE: L&T, Cat No:AUSP123PN100 OR equivalent model in ABB / HAGER / SCHNEIDER / LEGRAND/SIEMENS)
MCCB, 4 pole, 36/40 KA, thermal magnetic release, 200 Amps, Ics=100% of Icu, 415 Volts AC - 03 Nos (Make: L&T, Cat No: CM92109OOP1OG / HAGER, Cat No: HNT201DR / SCHNEIDER, Cat No: LV525342 / LEGRAND, Cat No: 4202 48/ ABB, Cat No: 1SDA116345R1 / C&S Cat No. CSE2NN250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 160 Amps, Ics=100% of Icu, 415 Volts AC - 04 Nos (Make: L&T, Cat No: CM90642OOMO / HAGER, Cat No: HHS161DR / SCHNEIDER, Cat No: LV516313 / LEGRAND, Cat No: 6690 30 / ABB, Cat No: 1SDA116250R1 / C&S Cat No. CSE2M250ATM4P-*)
MCCB, 4 pole, 25 KA, thermal magnetic release, 100 Amps, Ics=100% of Icu, 415 Volts AC - 01 No (Make: L&T, Cat No: CM91712OOKOOG / HAGER, Cat No: HHS101DR / SCHNEIDER, Cat No: LV510317 / LEGRAND, Cat No: 4200 55 / ABB, Cat No: 1SDA116246R1 / C&S Cat No. CSE1M125ATM4P-*)
MCB, 10 kA, 'C' Curve, SP, 06-32 Amps - 03 Nos
CT's ratio 300/5A - 01 Set (Set of 03)
LED indicating lamp with holder for main supply & standby supply indicating RYB (Set of three) - 01 Set
Note:-(i) All incoming and out going cables, duly thimble along with suitable size of brass cable glands, to be connected to accessories. (ii) All ACB, MCCB & Changeover to be connected internally with suitable size of aluminium strip. (iii) All requisite accessories including spreader terminals shall be provided alongwith MCCBs and cost of the same shall be deemed to be inclusive in the quoted rates.
Excavation in trenches not exc 1.5 metre width and not exceeding 1.5 metre in depth in soft/loose soil and getting complete all as specified and as directed.
Excavation of trench in road/hardstanding etc, not exc 1.50 m wide and not exc 1.50 m deep and getting out complete all as specified and directed.
Returning, filling in including spreading levelling watering and well ramming in layers n.exc 25 thick for soft/loose soil complete all as specified and as directed.
Removal of excavated material to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed.
M&L for dry sand cushioning / sand covering for underground cable protection and consolidated and compacted with clean dry sand complete all as specified and as directed. (NOTE: Punned thickness shall be measured for payment)
M&L bricks with sub class 'B' locally available laid in trenches above sand cushioning for cable protection complete all as specified and as directed.
Supply and fixing 100 mm bore galvanized iron pipe (light grade) with all fittings, laid in trenches or under roads/floors/culverts etc complete all as specified and as directed by the Engineer-in-charge.
Supply, Laying and testing XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cable 1100 Volts grade with stranded aluminium conductor cable, laid in trench or fixed to wall/passing through pipe/pole incl necessary aluminium thimbles, jointing and testing complete of the following sizes and cross sectional area :- (Note :- Necessary earth work to be measured and paid separately.
300 Sqmm, 3.5 core
240 Sqmm, 3.5 core
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 X 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
Supply and fixing galvanised Iron earth strip 25 x 4mm for connection of earthing with LT panel board burried in ground etc., complete all as specified and as directed by the Engineer-in-charge.
S.K. TRADERS
R.K.TRADING CO. INDIA
BASU AND CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .