Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-AOC | L1 | Accepted-AOC The lowest bidder | |
| 2 | L2₹12.2 L+₹25,760 (2.16%)Rejected-AOC 546 14 JUTOGH CANTT SHIMLA HP 171008 | SHIMLA | HIMACHAL PRADESH | 171008 | L2 | Rejected-AOC Other than the lowest bidder | |
| 3 | L3₹13.1 L+₹1.2 L (9.75%)Rejected-AOC 58 3 JUTOGH CANTT SHIMLA 08 HP | SHIMLA | HIMACHAL PRADESH | 171001 | L3 | Rejected-AOC Other than the lowest bidder | |
| 4 | L4₹13.9 L+₹2.0 L (16.9%)Rejected-AOC BOOTH NO 119 SECTOR 9 PANCHKULA 134109 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134109 | L4 | Rejected-AOC Other than the lowest bidder | |
| 5 | L5₹14.4 L+₹2.5 L (20.6%)Rejected-AOC CB 288 RING ROAD NARAINA NEW DELHI 110028 | NEW DELHI | DELHI | 110028 | L5 | Rejected-AOC Other than the lowest bidder |
Tender Value
₹17.9 L
EMD Value
₹35,760
Closing Date
26 Apr 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE JUTOGH
GE JUTOGH, JUTOGH CANTT, SHIMLA (HP)-171008
PROVN OF 630 KVA AUTO VOLTAGE SERVO STABILIZER FOR POWER SUPPLY WITH ALLIED WORK AT MH SANJAULI UNDER GE JUTOGH
2022_MES_515712_1
GE/JUT-05 OF 2021-22
Open Tender
Civil Works
Item Rate
120 days
SANJAULI
CLASS E CAT b (i)
7 documents required · 7 mandatory
₹500
GE JUTOGH
₹35,760
Yes
29 Apr 2022
29 Mar 2022
28 Apr 2022
29 Mar 2022
26 Apr 2022
12 Apr 2022
60 days
Amount
Supply, Installation, Testing and Commissioning of Servo Controlled voltage Stabilizer factory assembled floor mounted of capacity 630 kVA, complete (As per BIS 9815: Part 1) 3Phase , 50 Hz, naturally oil cooled, Outdoor type, Unbalanced Type, Copper Wound, Digital Display type, smooth and silent operation with 1st filling of Transformer oil having following specification:
Servo Controlled Technology
Type - Three Phase, Indoor, unbalanced supply, unbalanced load
Oil cooled type
Testing - as per IS- 9815 and IS: 2026
Input Voltage - 340 V - 480 V Ph to Ph
Output voltage - 415+/- 1% (Adjustable)
Frequency - 50 Hz +/- 5%
Metering - Digital Microprocessor Based
Efficiency - Not less than 95%
Responsible time - less than 10 mili second
Insulation Resistance (IR) - More than 10 Mega ohms at 500 VDC
No distortion in wave form
Rate of correction 8 volts/second for single phase and 20 Volt/second for Phase to Phase
Duty Cycle - Continuous 24 x 7
Protection Provided - Over load & Short Circuit Protection, High/Low Voltage cut off, Single phase preventer, phase sequence change protection, Stablizer Bypass arrangement etc.
1st filling of transformer oil to be included by manufacturer
Note: (i) Drawing and Specification of Servo Stablizer will be submitted by the vender and approved by GE before placing order. (ii) Rate of all type of T&P and labour for installation and testing are incl in quoted rates. (iii) Rate of any type of Civil work reqd as per site condition for installation of Stablizer are incl in quoted rates. (iv) Original factory test certificates with purchase voucher will be submitted by the vender before payment.
Supply, laying and testing XLPE insulated, armoured heavy duty LT electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 400 sqmm 3.5 Core with cable lugs etc incl complete connection between Transformer, Change over and Servo complete all as per OEM instruction complete all as specified and directed.
S&F of on- load changeover switches 4 pole, 630 Amps, 415 volts in sheet metal enclosure incl fixing on wall with nut & bolts or fastener complete all as per specified and directed.
M&L for earthing complete with copper plate earth electrode 60cmx60cmx3.15mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to copper earth lead strip of size 20X3.0 mm at two points by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 40 mm dia GI pipe for protection pipe and arrangement of watering pipe incl PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing and dismantling ,taking down old unser earthing complete all as specified and directed. Note: Rates of earth work, earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead upto 7.5 mtr, charcoal dust, common salt, PCC earth pit, CI frame, RCC cover, funnel with wire mesh, protection pipe, pipe for water, test point deemed to be included in quoted rate for this item.
M/S kuldeep kumar khullar
M/S JOHN VASSELLY
SHARMA ELECTRICAL ENGINEERS
Electro Tech Systems
Ayushmat Contractors
M/S MECHANICAL ENGINEERING and ELECTRICAL CONTRACTORS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .