Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.6 LAccepted-AOC 18 KUSHAL LAYOUT 1ST CROSS KAGGADASAPURA CV RAMAN NAGAR POST BENGALURU 560093 | BENGALURU | BENGALURU URBAN | KARNATAKA | 560093 | L1 | Accepted-AOC AWARD OF CONTRACT | |
| 2 | L2₹37.7 L+₹3.8 L (11.1%)Rejected-Finance 121004 | L2 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 3 | L3₹41.1 L+₹7.2 L (21.2%)Rejected-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L3 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 4 | L4₹43.8 L+₹9.9 L (29.0%)Rejected-Finance 47A C3 OLD DAMU NAGAR PULIAKULAM COIMBATORE 641 045 | COIMBATORE | COIMBATORE | TAMIL NADU | 641045 | L4 | Rejected-Finance BEING NOT LOWEST TENDER | |
| 5 | L5₹48.6 L+₹14.7 L (43.2%)Rejected-Finance | L5 | Rejected-Finance BEING NOT LOWEST TENDER |
Tender Value
Refer Docs
EMD Value
₹98,000
Closing Date
16 Jul 2024, 6:00 pmClosed
GE (AF) SULUR
Garrison Engineer AF Sulur Military Engineer Services Kangayampalayam Post Sulur Coimbatore 641 401
COMPREHENSIVE MAINT OF AIR COMPRESSOR SERVO VOLTAGE STABILIZERS FOR BALANCED / UNBALANCE LOADS, LIFT, EOT CRANE, UPS AND OTHER MISC ITEMS AT AF STN SULUR
2024_MES_664054_1
8685/E8
Open Tender
Miscellaneous Works
Item Rate
334 days
GE (AF) SULUR
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹98,000
Yes
25 Sept 2024
4 Jul 2024
18 Jul 2024
4 Jul 2024
16 Jul 2024
11 Jul 2024
4 Jul 2024 - 8 Jul 2024
Amount
SCHEDULE A BOQ
Comprehensive maintenance of Air compressor 5 HP of Make Shakti 3 Phase including ,checking of airflow line ,oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location - 33 Sqn New Hangar-01 No
Comprehensive maintenance of Air compressor of any type , compressor drive motor-7.5 KW/10 HP, , 3 phase assembled with Air filter, compressor element, air receiver/ oil separator, air cooler, oil cooler, drive motor, gear casing, unloader, Elektronikon control system, air dryer with bypass valves etc including checking of airflow line, oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/ oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location – LCA Hanger 1 to 3-06 Nos, Rotable bldg- 01 No, avonics complex-02 nos armanet -02 nos IFCS-01 No, Role eqpt, -01 (Total -15 Nos).
Comprehensive maintenance of Air compressor of any type , compressor drive motor-12.5 KW/15 HP, , 3 phase assembled with Air filter, compressor element, air receiver/ oil separator, air cooler, oil cooler, drive motor, gear casing, unloader, Elektronikon control system, air dryer with bypass valves etc including checking of airflow line, oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/ oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location – Mechanical Bldg- 01, safety eqpt- 01, (Total -02 Nos).
Comprehensive maintenance of Air compressor of any type , compressor drive motor-15 KW/20 HP, , 3 phase assembled with Air filter, compressor element, air receiver/ oil separator, air cooler, oil cooler, drive motor, gear casing, unloader, Elektronikon control system, air dryer with bypass valves etc including checking of airflow line, oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/ oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location – LCA Hanger 1 to 03 (Total -03 Nos).
Comprehensive maintenance of Electric Powered Screw Air Compressor (EPSAC) Part No : E110-11AC, Free air delivery 16.9 cum/min, working pressure : 10.2 Kg/sqcm, Compressor drive motor -110 KW/ 147.5 HP, RPM-1485 of Make ELGI 3 phase including checking of airflow line, oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/ oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location - LCA ETB Bldg-02 No.
Comprehensive maintenance of Air compressor 5 HP of Make ELGI 3 Phase including checking of airflow line ,oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location - AVRO Hangar-2 Nos. Elect Bld-01, EW Bldg,- 01, LOX bay-01 (Total -05 nos)
Comprehensive maintenance of Screw Air compressor (ATLAS) Part No GA110-10, compressor drive motor-110 KW, 10 bar Make : Atlas Copco, 3 phase assembled with Air filter, compressor element, air receiver/ oil separator, air cooler, oil cooler, drive motor, gear casing, unloader, Elektronikon control system, air dryer with bypass valves etc including checking of airflow line, oil change, pressure switch setting, setting of safety valves, vibration and abnormal noise check, oil check/ oil consumption check, cleaning of air filters, checking functioning of valves, checking of gauge by the original manufacturer complete all as specified and directed. Location – LCA ETB Bldg-01 No.
Note for Item No 02 to 08 :- (a) The above comprehensive maintenance shall be done through authorised person of OEM on quarterly basis.
(b) The contractor shall make AMC contract with the original manufacturer of Air compressor and the repairs/maintenance shall be carried out through the original manufacturers only.
(c) The rate quoted shall be deemed to include to carried out all repairs to air compressor noticed during the period 11 months by providing materials and labour. Interim payments if required shall be made thrice for the period of 11months proportionately.
(d) Any other spare parts which have not covered in the relevant items but are required to make in functional condition are deemed to be included in the quoted unit rate.
(e) Cost of labour element towards removing of unserviceable spare parts and re-fixing of serviceable spare parts for supply only items here-in-after shall be deemed to be included in quoted rate. Supply only spare parts shall be measured and paid separately.
Comprehensive maintenance of goods lift to carry goods of 2000 kg capacity with a speed of 0.5 metre/sec, of Make : Johnson to serve ground floor and three upper floors with AC variable voltage & variable frequency drive(VVVF DRIVE) system, microprocessor based control system all as per IS 14665 with car position indicators on all floors, car position indicators in cabin, battery operated alarm bell and emergency lights ,cabin light & fan over load switch, auto revelling, intercom facility with centre opening, stainless steel power operated sliding doors, including checking the operation, adjusting, lubricating and repairs as required to machine motor, controller parts, safety devices, governors, repair/replacement as required to alarm bell, indicators, emergency light, emergency components, including low voltage protection relay, call bell , etc. complete all as specified and as directed. Machine No of Lift (L-H8229), Location : DWR Building - 01 No.
Comprehensive maintenance passengers lift to carry 10 passengers (680 Kg) capacity of Make: Johnson to serve ground floor plus four floors, including checking the operation, adjusting, lubricating and repairs as required to machine motor, controller parts, safety devices, governors, repair/replacement as required to alarm bell, indicators, emergency light, emergency components, including low voltage protection relay, call bell, etc complete all as specified and directed. Machine No of Lift - L/C 7489, Location : SRE Building - 01 No.
Comprehensive maintenance of passengers lift to carry 8 passengers (544 Kgs) capacity with a speed of 1 metre/ sec, of Make: OTIS to serve ground floor and 4 upper floors with AC variable voltage and variable frequency drive (VVVF DRIVE) system, micro processor based controol system all as per IS 14665 hall position indicators on all floors, car position indicators in cabin, battery operated alarm bell and emergency lights including cabin light and fan over load switch, auto revelling, intercom facility with centre opening, stainless steel power operated sliding doors, including examining the operation, adjusting, lubricating and repairs as required to machine motor, controller parts, safety devices, governors, repair/ replacement as required to alarm bell, indicators, emergency light, emergency components, including low voltage protection relay, call bell, etc. complete all as specified and directed. Machine No of Lift (MG055702), Location : New ATC Building - 02 Nos.
Comprehensive maintenance of goods lift to carry goods of 1000 kg capacity with a speed of 0.5 metre/sec, of Make : KONE to serve ground floor and three upper floors with AC variable voltage & variable frequency drive(VVVF DRIVE) system, microprocessor based control system all as per IS 14665 with car position indicators on all floors, car position indicators in cabin, battery operated alarm bell and emergency lights including cabin light & fan, over load switch, auto revelling, intercom facility with centre opening, stainless steel power operated sliding doors, including Examining the operation, adjusting, lubricating and repairs as required to machine motor, controller parts, safety devices, governors, repair/replacement as required to alarm bell, indicators, emergency light, emergency components, including low voltage protection relay, call bell , etc. complete all as specified and directed. Location : FMS - 01 No.
Note for item no 14 to 17 :- (a) The entire work mentioned in item No. 14 to 17 of BOQ, including comprehensive , Preventive and periodical maintenance of lifts/ elevators shall be got executed through OEM i.e.
(b) The tenderer shall have to replace the U/s materials within the OEM materials only. Necessary paid vouchers shall be submitted from OEM for the materials like ARD, drive, etc. Contractor is responsible for renewal of licence fee. The charges for annual Government inspection is deemed to be included in the quoted rate.
(c) The comprehensive maintenance include weekly, fortnightly, monthly, quarterly, half yearly inspection/testing/ preventive maintenance, replacement of unserviceable parts/ material including labour, transportation etc. complete.
(d) The complaints shall be attended forthwith as the complaint/failure from the time to time of receipt of the same. The contractor shall deploy sufficient lift mechanic and helper. Rate quoted is deemed to be inclusive of T&P required to carry out repairs, stationery for upkeep of records, uniform to mechanic and helper etc. The contractor shall maintain the attendence register of personnel deployed for the work and the same shall be put upto the Engineer-In-Charge as and when asked.
(e) The contractor shall obtain signature of Authorized representative of GE as token of satisfactory rectification of defects. Any minor complaints requiring no spare parts shall be rectified within 0ne hour and if requiring minor parts, shall be rectified within two hours. Any major complaints requiring major parts / repair shall be recctified within 24 hrs. In case delay in rectification of minor complaints , a panel recovery @ Rs. 200.00 per hour shall be imposed upon the contractor and in case of delay in major repair of the lkifts for more than 24 hours and upto 10 (ten) days, penalty on the contractor for a sum of Rs. 2000.00 per lift per day or part thereof and Rs. 4000.00 per lift per day or part thereof after 02 (two) days shall be imposed. The decision of the GE as to particular repair is minor/ major and a particular lift has been maintained or not onb a particular day, will be final and binding. The above penalty shall be in addition to the provision made in Clause No. 50 of IAFW-2249. In the event of burning of motor , a time of 7 days shall be allowed to the contractor for rectification of fault. After that period, penal recovery at the rate of Rs.2000.00 per day shall be imposed on the contractor.
(f) A complaint register will be maintained by the contractor and the contractor will obtain the complaint from JE/ AGE E/M office on every working day at 0800 hrs or will be informed telephonically by the Dept. at any time. Two mobile Nos and two email IDs to be maintained by the contractor to communicate the complaints. After attending the complaints the contractor will obtain the signature from the Authorised Representative of GE every day as token of complaints attended.
(g) Ser Item No. 14 to 17 of BOQ consists of comprehensive maintenance. The work will be carried out under Authorised dealer for comprehensive maintenance of lifts all as specified in DCS, Special condition, Particular specification, MES SSR and as directed by GE/Engineer-In-Charge.
(h) Lift mechanic shall be well experieced in lift/elevators repairs and maintenance and fully equipped with required T&P.
(i) Contractor shall submit police verification certificates of personeel employed before commencement of works.
(j) Contractor shall carry out daily, weekly, fortnightly, monthly, quarterly and half yearly inspection and report of the same shall be sbmitted to the Engineer-In-Charge.
(k) Contractor shall provide uniform to the personnel employed without any extra cost to the Deptt. And cost of the same is deemed to be included in the rate quoted of ser item Nos above and for non wearing of uniforms by the personnel employed by the contractor a penalty of Rs. 500.00 shall be levied per person per shift.
(l) The contractor shall ensure proper functioning of safety devices.
(m) The contractor shall stick/paste safety instructions at inside the cabins of all lifts with the contact number of opreater/machanic.
(n) The following repairs are deemed to be included in the rate quoted by the contractor under comprehensive maintenace :-
(i) CAR CABIN
(aa) Maintenance/repairs of cabin fan ( except rewinding)
(ab) Contractor is responsible for maintaining the car cabin neat and clean. Necessary cleaning to car cabin shall be done by the contractor on daily basis.
(ii) CONTROLLER
(aa) Checking fuses of controller and mains, replace if any found defective.
(ab) Checking the condition of breake oil and replacement if required.
(ac) Checking the flexible leads to relays to make them serviceable.
(iii) AC MOTOR
(aa) Lubricate bearing with suitable lubricants
(ab) Clean ventillation passages on weekly basis
(ac) Carry out the insulation test and continuity test of motor on quarterly basis and make them in serviceable condition.
(ad) Checking the alignment of motor shaft and relignment of shaft.
(iv) GOVERNOR
(aa) Lubricate bearing on weekly basis with suitable lubricants
(ab) Checking that levers working smoothly.
(ac) Checking that electrical contacts opens before rope get locked
(v) ROPES
(aa) Checking the condition of hoist and governor ropes
(ab) Lubricate ropes on weekly basis
(ac) Checking the dia of ropes and record in maintenance book on quarterly basis for its proper functioning.
(vi) HOIST WAY
(aa) Lubricate guides and guide shoes on weekly basis with suitable lubricants.
(ab) Checking that the buffers are in proper position and measure and record counter weight and buffer cleans with the car at the top.
(ac) Checking the rope fastening at the car and counter weight
(ad) Checking the guide clamps and adjusted
(ae) Checking the upper and lower limit switches for proper connection after physical inspection get the lift to travel by holding from the controller and see that the switches operate properly.
(af) Checking the condition of travelling cables and termination at junction boxes.
(vii) MACHINE ROOM
(aa) Checking and adjusting of over load relay and phase failure relay.
(ab) Checking power wiring termination in switch motor controller and power switching relays.
(ac) Checking lubrication of all equipments on weekly basis.
(ad) Cleaning the machine room on daily basis.
(ae) Cleaning the relay contacts, replacement of contacts
(viii) GEAR BOX
(aa) Inspect for stray noises
(ab) Checking axial play of work shaft
(ac) Lubricate bearing and top up oil in gear box as and when required
(ix) BREAKES
(aa) Cleaning of oil surfaces and trace source of oil leakage and arrest the leakages
(ab) Adjust clearence between shoes and drum on monthly basis.
(x) RETIRING CAR AND LOCKS
(aa) Checking operation car and lock from the top at each landing, checking that the retiring car solenoid is not getting over heated and that the movement of car is smooth.
(ab) Checking that all locks are functioning properly, mechanically and electrically after opening of covers, checking all set screws and springs and replace if necessary. The lever should lock the breake properly.
(ac) Checking that the retiring car does not touch the lock roller at the landing which is being passed.
(ad) Checking the door closes safely, clean and adjust if necessary.
(ae) Checking the car gear switch operates properly.
(af) Lubricate top track and door motor and linkage..
(ag) Checking the landing door and can be operated by emergency keys.
(ah) Repar/replacement of retiring car solenoid lock doors closer safety switch.
(xi) GENERAL
(aa) Checking the car frame for bends or cracks and correct if required.
(ab) Checking and carry out insulation resistance test half yearly basis for the following:-
(i) All power circuit cables and incoming cables
(ii) Switch and feed upto controller
(iii) Between different power relays
(iv) Power card in the travelling cables
(v) Motor
(vi) Checking opertaion of the car over speed safety gear by moving the levers mannually landing so that the safety locks up properly.
(ac) Checking that the sheaves are tight on the shaft , also checking with hammer sounding for cracks, chech sheave bearing clean and re-lubricate. Adjust for proper axial play.
(ad) Unload car(s) checking the worn gear lash and adjust by removal of sheaves as required
(ae) Checking of motor bearing, clean and lubricate.
(af) Checking that the gear coupling belts are tight.
(ag) Checking the oil seal of gear box and fill frush oil if required.
(ah) Contractor is responsible for maintenance of lift well/pit/ shaft/ machine room in dry and clean condition at all times. Any entry of water needs to be pumped immediately and rate quoted is inclusive of the cost of necessary pumping arrangement. A pump should be kept in store at all time to meet the emergency requirement. No extra payment will be done on this account.
(aj) Remove breake shoes clean and refit or replace breake linings inspect pins springs clean and reassemble. Checking that the breake drum is not scored or worn unevenly.
(ak) The cost of additional technicians required to do peridical maintenance checks is deemed to be included in the rates quoted. Nothing extra shall be paid on this account.
Supply and Fix Sealed Maintenance Free (SMF) battery of capacity 12 V, 7.5AH, suitable for passenger/ goods lift as required at location SRE/ DWR/ ATC bldg including initial charging complete with inbuilt charger ,electrolyte/ distilled water etc including taking down of old unserviceable battery and shifting to MES store yard for deposit all as directed by Engineer in Charge complete all as specified. Make of battery : Exide of model No. EP 65 or equivalent in Amar raja (Power Zone)/ Amaron
Note for Item No 98 :- The contractor shall submit full replacement warranty certificate for minimum 02 years from the date of installation.
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : Vinitec with input variation between 340V to 470V with output stabilized at 415 Volts of capacity 650KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : MAFI Sub Stn - No 1
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : Vinitec with input variation between 340V to 470V with output stabilized at 415 Volts of capacity 400KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : ATC bldg - No 1
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : Vinitec with input variation between 340V to 470V with output stabilized at 415 Volts of capacity 250KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : MAFI Sub Stn - No II
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of with input variation between 340V to 470V with output stabilized at 415 Volts of capacity 200KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : Sub Stn E - No 01
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 75KVA with all spares including isolating stabilizer from system, Opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system. periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location - ATC, TRCD(2 Nos), 152 Radar site, Transmitter, CRRW, 75 RMU,
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : Vinitec with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 100 KVA with all spares including isolating stabilizer from system, Opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system. periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location - Signal centre , radder section
Comprehensive maintenance of 3 phase oil cooled servostabilizer of Make - BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 250KVA with all spares including isolating stabilizer from system, Opening up, examining the accessories parts,cleaning,soldering as required and testing and connecting back with the system. periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location - Rubber store
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 15KVA Make-RDC with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : RT Cabin, rotable , opera
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 125KVA Make-Power one with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : SRE
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 150KVA Make-BEC with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : DWR
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make : BEC with input variation between 340V to 400V with output stabilized at 415 Volts of capacity 50KVA Make-BEC with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed. Location : T/51 Avionics Lab. OTF AC plant, SEW AC plant, AVRO ac Plant, trcl
Supply only Microprocessor board of servo stablizer of capacity 50KVA to 250KVA all as specified and as directed.
Supply only Servo motor suitable for 50KVA to 250KVA all as specified and directed.
Supply only Buck Boost transformer of servo stablizer of capacity 50KVA to 250KVA all as specified and directed..
Supply only Bypass switch of servo stabilizer of capacity 50 KVA to 250KVA all as specified and directed.
Note for item No 111 to 114 :- Cost of labour for fixing and taking down old defective parts with respect to above items has already included in unit rate quoted for comprehensive maintenance.
Supply and Fix Sealed Maintenance Free (SMF) battery of capacity 12 V, 100AH, suitable for existing 3 phase online UPS as required at location including initial charging complete with inbuilt charger including electrolyte/ distilled water etc including taking down of old battery and shifting to MES store yard for deposit all as directed by engineer in charge complete all as specified. Make of battery : Exide of model No. EP 65 or equivalent in Amar raja (Power Zone)/ Amaron
Note for Item No 116 :- The contractor shall submit full replacement warranty certificate for minimum 02 years from the date of installation.
Periodical Examination, normal and routine maintenance ,as per manufacturer’s instructions, Repair and periodical maintenance of indoor ,single Girder heavy duty electrically operated travelling (EOT) over head crane capable of handling 3.0 Tonnes capacity – 01 No, suitable for 415 volts, 50 Hz 3 phase, 4 wire, AC supply with clear hook height of 3.5 Mtrs from FFL including floor operated movable pendent control by means of push buttons independent of crab trolley position with protective panel with down shop lead (DSL) trailing cables and earthing etc, complete comprising of (a) class of Duty-CLII as per IS 807 & IS 3938 indoor, (b) Crane span-8.38Mts (c) Longitudinal travel shall be limited to 1.0 m away from the walls on both ends. (d) EOT crane shall be provided with the following electrically controlled. (i) Longitudinal Travel speed-20mpm (100%)-2mpm (10%), (ii) Cross travel speed -12 mpm (100%)-1.20mpm (10%), (iii) Hoisting speed – 6 mpm(100%) – 0.60 mpm (10%), (iv) Longitudinal Travel motor – 2X0.75 HP (SQC), (v) Cross travel motor – 0.5 HP (SQC), (vi) Hoisting motor – 5 HP (SQC) installed at Location – LCA ETB bldg. Make :- Stanmek Ingenieurs
Periodical Examination, normal and routine maintenance ,as per manufacturer’s instructions, Repair and periodical maintenance of indoor ,single Girder heavy duty electrically operated travelling (EOT) over head crane capable of handling 3.0 Tonnes capacity, suitable for 415 volts, 50 Hz 3 phase, 4 wire, AC supply with clear hook height of 5.1 Mtrs from FFL including floor operated movable pendent control by means of push buttons independent of crab trolley position with protective panel with down shop lead (DSL) trailing cables and earthing etc, complete comprise of (a) class of Duty-CLII as per IS 807 & IS 3938 indoor, (b) Crane span-8.38Mts (c) Longitudinal travel shall be limited to 1.0 m away from the walls on both ends. (d) EOT crane shall be provided with the following electrically controlled. (i) Longitudinal Travel speed-20mpm (100%)-2mpm (10%), (ii) Cross travel speed -12 mpm (100%)-1.20mpm (10%), (iii) Hoisting speed – 6 mpm(100%) – 0.60 mpm (10%), (iv) Longitudinal Travel motor – 2X0.75 HP (SQC), (v) Cross travel motor – 0.5 HP (SQC), (vi) Hoisting motor – 5 HP (SQC) Make : ROCKWELL installed at Location – FADEC bldg-2 Nos.
Periodical Examination, normal and routine maintenance ,as per manufacturer’s instructions, Repair and periodical maintenance of indoor, single Girder heavy duty electrically operated travelling (EOT) over head crane capable of handling 2.0 Tonnes capacity – 03 Nos, suitable for 415 volts, 50 Hz 3 phase, 4 wire, AC supply with clear hook height of 3.5 Mtrs from FFL including floor operated movable pendent control by means of push buttons independent of crab trolley position with protective panel with down shop lead (DSL) trailing cables and earthing etc, complete comprising of (a) class of Duty-CLII as per IS 807 & IS 3938 indoor, (b) Crane span-8.10Mts (c) Longitudinal travel shall be limited to 1.0 m away from the walls on both ends. (d) EOT crane shall be provided with the following electrically controlled. (i) Longitudinal Travel speed-20mpm (100%)-2mpm (10%), (ii) Cross travel speed -12 mpm (100%)-1.20mpm (10%), (iii) Hoisting speed – 6 mpm(100%) – 0.60 mpm (10%), (iv) Longitudinal Travel motor – 2X0.5 HP (SQC), (v) Cross travel motor – 0.33 HP (SQC), (vi) Hoisting motor – 4 HP (SQC) installed at Location – FADEC, LCA ETB & FMS Bldg. Make :- ROCKWELL/ Stanmek Ingenieurs/RANK
Supply and Fix Sealed Maintenance Free (SMF) battery of capacity 12 V, 65 AH, suitable for existing 3 phase online UPS as required at location including initial charging complete with inbuilt charger including electrolyte/ distilled water etc including taking down of old battery and shifting to MES store yard for deposit all as directed by engineer in charge complete all as specified. Make of battery : Exide of model No. EP 65-12 SMF Power Safe Plus or equivalent in Amar raja (Power Zone)/ Amaron
Supply and Fix Sealed Maintenance Free (SMF) battery of capacity 12 V, 26 AH, suitable for existing 3 phase online UPS as required at location including initial charging complete with inbuilt charger including electrolyte/ distilled water etc including taking down of old battery and shifting to MES store yard for deposit all as directed by engineer in charge complete all as specified. Make of battery : Exide of model No. EP 26-12 SMF Power Safe Plus or equivalent in Amar raja (Power Zone)/ Amaron
Note for Item No 121 & 122 :- The contractor shall submit full replacement warranty certificate for minimum 02 years from the date of installation.
Supply and fix in replacement of Compressor motor suitable for 20 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor motor suitable for 10 to 15 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Cylinder suitable for 20 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Cylinder suitable for 10 to 15 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Filters suitable for 20 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Filters suitable for 10 to 15 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Oil separator suitable for 20 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of Compressor Oil separator suitable for 10 to 15 HP air compressor including taking down unsv items alla s specified and directed by Engr-inCharge
Supply and fix in replacement of pressure switch suitable PSI for 10 to 20 HP air compressor all as specifed and directed by Engr-in-Charge
M & L for overhauling of Air compressor by opening cylinder and analysing deffects including replacement of all unsv spare parts I,e Air filtters, Oil filters, air oil separators, Lubricant kits, coolers, gears, Coupling kit, rubber gas kit, compressor oil, pumps, motor repair, all bring back to orginal working conditions all as specified and directed by Engr-in Charge
Taking out the defective/burnt cabin fan from the cabin, material and labour for rewinding of lift cabin fan with super enamelled copper winding wire of same gauge and class as of existing fan complete all as specified and directed by the Engineer-In-Charge.
Supply and fix Encoder suitable for 544/680/844 kgs carrying, 05 to 13 passenges Lift and connecting electrical cercuits without damage including testing all as directed at site by Engr-in-Charge
Supply and fix car door drive 1.5 KW suitable for 544/680/844 kgs carrying, 05 to 13 passenges Lift and connecting electrical cercuits without damage including testing all as directed at site by Engr-in-Charge
Supply and fix door sensor infrraied 270 beam suitable for 544/680/844 kgs carrying, 05 to 13 passenges Lift and connecting electrical cercuits without damage including testing all as directed at site by Engr-in-Charge
Supply, fixing and commisioning of Main V3F drive 12 to 15 KW capacity , 415 V fixing in contol panel properly electrically operated passenger lift of Make Tyssenkkrup, capacity 544/680/844 kgs carrying, 05 to 13 passenges Lift and connecting electrical cercuits without damage including testing all as directed at site by Engr-in-Charge
Supply and Fixing in replacement of FIR Sensor electrically operated passenger lift of Make Tyssenkkrup capacity 544/680/844 kgs carrying, 08 to 13 passenges Lift including taking down old unserviceable for sch of credit all as directed at site by Engr-in-Charge
Neptune Engineers and Builders
devan enterprises
KRISHNA ENTERPRISES
BHARATH TECH
LAKSHMI ELECTRICAL ENTERPRISES
UNIVERSAL ENGINEERING
KSR AND COMPANY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .