Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical 19 A DURGA BARI SADAR BAZAR MEERUT MEERUT MEERUT UTTAR PRADESH 250001 | MEERUT | UTTAR PRADESH | 250001 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹5 L
EMD Value
₹5,000
Closing Date
8 Nov 2023, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC MEERUT
130 D PAARESHAN BHAWAN VICTORIA PARK MEERUT
WORK TENDER
2023_UPTCL_855981_1
T-27/23-24/ETC/MT
Open Tender
Electrical Works
Item Rate
60 days
MEERUT
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC MEERUT
₹5,000
7 Dec 2023
26 Oct 2023
9 Nov 2023
26 Oct 2023
8 Nov 2023
26 Oct 2023
Amount
Partially drain out the transformer oil from tank, after due shifting of drums, pipes etc. with all cost of men, material T&P required for completion of work.
Opening of jumpers of 40 MVA transformer, Cutting of earthing strips and opening of electrical connections as follow:-
Opening of All HV, LV jumpers of 40 MVA Transformer
Opening of earthing strips by cutting & electrical connections
Complete, dismantling of 40 MVA T/F by opening of radiator, conservator tank, bushing, marshaling box, cooling fans, etc and Packing of bushings of 40 MVA T/F in crates and shifting the bushing from site to store.
Shifting/Dragging of 40 MVA T/F from plinth to near open space. Distance about 100 Mtr (each job of 05 Mtrx20=100 Mtr). Including turning of main tank if required with all T&P and work required to complete the job satisfactorily
Dismantling of HV side LAs and its structure and re-erection of these LAs with structure after installation of 63 MVA T/F including earthing etc.(01 Job includes all 03 phase)
Dragging of 63 MVA T/F Main tank from unloading site to T/F Plinth –Approx. distance -20 Mtr.(each job of 05 Mtr.x 04=20Mtr.)
Complete, erection of 63 MVA T/F by erection of radiator, conservator tank, bushing with its turrets (if available) connecting of all oil pipe line, erection of cooling fans, making control cables connection, buchholz relay etc. for completing the work, topping of T/F oil and. final oil filling in tank, radiator, conservator tank and all other associates. work for completion of work.
Earthing of main tank of 63 MVA T/F, at two points by using M.S. flat 50x6/75X10 mm size, its jointing with already laid earth mat (X&Y Electrodes) for its earthing work.
Replacement of existing old T/F RTCC Panel by new RTCC panel by opening of control cable, cutting of earthing termination and laying control cables, preparation of cable schedule etc. & shifting of dismantled panel to elsewhere as per directions of site incharge.
Centrifuging of complete T/F oil in T/F by connecting centrifuging pipes, circulating the T/F oil through Private centrifuging machine provided by contractor at his own cost with BDV machine and PPM kit and taking the BDV & PPM value of the oil periodically till the required value is achieved.
After centrifuging of T/F oil arrangement to be made (oil sampling and providing to lab) for oil testing result from any NABL Lab/CPRI Lab Noida. 1. DGA 2. BDV 3. PPM
Jumpering of T/F from HV with single Moose/Zebra/ Panther and L V side with double zebra/Moose/Panther complete up to 33KV main bus.
Earthing of T/F MB DM box OLTC, RTCC at two points using 75×10/50×6mm. And nutral of T/F as per draing using 40 mm M.S. rod after making delta formation with 3 M long electrodes.
Erection of following equipments as per instruction of various equipments manuals and technical specifications including shifting of structures/equipments from store to erection site including all other associated works including jumpering, making holes, fixing of suitable cable glands, ferrules and electrical connection/termination as per cable schedule, for completion of erection work satisfactorily:-
36 KV VCB
36 KV CTs (2000/1200/1A) with Junction box
Replacement of 36KV Isolator including opening/making of jumpers, earthing, N&B etc.
Dismantling of old 36KV CTs having ratio (800-400/1A) including opening of jumpers, earthing, N&B, secondary connections etc and shifting from site to store.
Dismantling of old 36KV VCB including opening of jumpers, earthing, N&B, secondary connections etc and shifting it to the store.
Replacement of old 145 KV CB (CGL Make comm. Year 1986) including work of dismantling of CB by opening of nut and bolts, opening of jumpers, cable connection, earthing and shifted upto store as per direction of site engineer. Erection of new 145 KV CB including shifting store to erection site including all other associated works satisfactorily and making of jumpers, earthing, N&B, secondary connections etc.
Dismantling of Old electro- mechanical type T/F C&R Panel including work of dismantling of existing 132/33 KV T/F control relay panel, opening of all the cables connected in the panel after noting down all the ferrules.
Erection of new 132/33 KV T/F panels connecting all the disconnected cables to the newly installed T/F Panel. Checking of all function of Panels w.r. to HV/LV CBs panel & from the PT, of view of protection for proper functioning of panel T/F.
Supply
Four Bolted type Zebra to Zebra PG Clamps made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
Four Bolted type Zebra to Panther PG Clamps made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
Four Bolted type Panther to Panther PG Clamps made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
36 KV CT Clamps suitable for ACSR Twin Zebra conductor made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
36 KV VCB Clamps suitable for ACSR Twin Zebra conductor made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
36 KV Isolator Clamps suitable for ACSR Twin Zebra conductor made of aluminum alloy LM-6 complete with galvanized N&B, spring and plain washers.
Zebra to Zebra spacer 100mm size
Meena Elect & Engg. Works
SATKAR TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .