Superintending Engineer (CIVIL), RRCAT
CSD OFFICE RRCAT INDORE
Management and upkeep of fire pump house and pressurized fire line in technical area of RRCAT Indore for a period of one year
2024_RRCAT_797678_1
RRCAT/CSD/3113/W-4271/24-25/23
Open Tender
Civil Works
Item Rate
365 days
Technical Area RRCAT
As per Tender Documents
3 documents required · 3 mandatory
₹0
₹96,000
30 Apr 2024
4 Mar 2024
29 Mar 2024
5 Mar 2024
25 Mar 2024
5 Mar 2024
Amount
Note 1) The contractor shall follow up with the officials of F&S, CISF,RRCAT security, Civil maintenance cell etc as frequently as required to run the system smoothly.
Note 2) The cost of deploying all labourers, all materials, wastages, tools, tackles, general safety gadgets, all applicable taxes including GST (Goods & Service tax), Corporation tax, Income tax, VAT, Labour cess , all other liabilities as per Contract Labour Act including those stipulated under clause 19 of section 4,section 8 & section 9 of the tender shall be entirely borne by the contractor and nothing on account of all these is admissible as the same is deemed to be included in the quoted rates. Note 3) In case of unsatisfactory quality of work, reduced rate shall be applied as per clause 16 of Section 5 of the tender. The decision of Engineer regarding reduced rate shall be final & binding. Note 4 )In case of non performance of work at any or all locations, recovery shall be made for non performance as per the quoted rate per number basis. In case of saving because of non existence of requirement question of recovery shall not arise.
Management of fire water pumping station in technical area including monitoring & operating 231 hp Diesel Engine Pump set (make-Kirloskar, model No 6SL9088TA 6819088TA),150 hp Main Electric Pump set (Make: Kirloskar, Model No – DSM150/46),two nos, 20 hp Jockey pump set, Zen Airtech make 5 hp Air Compressor set on round the clock basis without any interruption, all in close consultation with the engineer and F&S officials of RRCAT or their authorised representative including deployment of dedicated team (ITI in Mech/Plumbing/Electrical trade) round the clock basis to handle breakdown maintenance/ emergency maintenance, removal & repositioning of installations etc including cost of labourers, supply & use of all minor CONSUMABLE items like welding electrodes/ fluxes, fastener sets, gaskets, minor fittings, sundris, transport of deployed staff to inspect fire line etc
including maintaining the log book, giving daily feed back about the performance of pressurised fire line,valves,pumps etc in addition to all the activities /daily, weekly, monthly, quarterly, half yearly,yearly maintenance schedule enlisted in the detailed scope of work including carrying out repairs etc as & when required solely to ensure uninterrupted performance of the system etc all complete as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc complete job as directed by Engineer in Charge BUT EXCLUDING supply & use of all such major items/ spares /sub systems/major repairs/servicing /painting covered in the scope of other item of this schedule which are payable under relevant item.
Note: 1) The payment shall be based on calendar month whether it is of 31 days or less than 31 days.
2) Contractor shall take all necessary measures including training if any, at his cost to assure uninterrupted performance.
3) Engineer in Charge shall have right to disallow any workmen to work without assigning any reason whatsoever.
4) The Contractor has to deploy 02 (two) nos. skilled person with 01(One) no. supervisor in general shift for any type of fire line maintenance work and 01 (one).no. skilled pump operator in each shift. on regular basis at Fire pump house located in technical area.
Supply & positioning of Control panel Battery 12 Volts 40 Ampere hour for uninterrupted functioning of Kirloskar make 231 hp Diesel Engine Pump set installed at the fire pumping stations including removing the existing battery and staking at division's stores, testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Supply & positioning of Spare parts for the Kirloskar make 231 hp Diesel Engine Pump set installed at the fire pumping stations including removing the existing component and staking at division's stores, testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Diesel Engine filter & Lubricating oil filter
Engine oil
V belt
Breather Tube
Coolant
Engine Starter (shelf)
Battery 12 V 180 Ah
Dunlop pad
Radiator belt set
Pump coupling
Bearing
12 V Battery Charger
Supply & positioning of Spare parts for the Kirloskar make two 20 hp Jockey Pump sets installed at the fire pumping stations including removing the existing component and staking at division's stores, testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Bronze Impeller
Shaft
Copper Motor Rewinding
Gland Plate
Contactor MNS 45
Attending break down maintenance on emergency basis by replacing, repairing & servicing of Kirloskar make 231 hp Diesel Engine Pump set installed at the fire pumping stations including supplying, replacing & removing the existing component and staking at division's stores including oiling greasing, replacement of accessories like Cylinder Liner assembly, Piston Assembly, Connecting Rod Bearing ,Lube oil Pump: high discharge, Water pump sub Assembly Valve pair inlet & exhaust, Valve guide, Valve seal, Valve seat insert inlet , Valve seat insert exhaust, Set of Joints, set of rings, Cylinder head gasket, Fuel pipes, leak off pipe assembly, Valve collets pair, Starter ring, connecting rod assembly & testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions including cost of material , labours and tolls etc. complete all as directed by Engineer-in-charge
Labour charges for qauterly routine inspection & general servicing of Kirloskar make 231 hp Diesel Engine Pump set, Kirloskar make 28 hp Diesel Engine Pump set & SAME GREAVES make 60 hp Diesel Engine Pump set, installed at the RRCAT pumping stations by kirloskar company certified mechanic/ Engineer including cost of tooles & tacles and testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc including oiling greasing complete as directed by Engineer-in-charge.
Supply & positioning of Spare parts for Zen Airtech make 5 hp Air Compressor set installed at the fire pumping stations including removing the existing component and staking at division's stores, testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Safety valve
V belt
Compressor oil
Air filter
Oil Filter
Fan Pulley
Bearings
Supply & positioning of Spare parts for 8000 Ltr Hydro Pneumatic Tank and accessories installed near fire pumping stations including removing the existing component and staking at division's stores testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Pressure gauge
Level Indicator
Level switch
Pressure Safety Valve
Compatible Solenoid valves
Supply & positioning of Spare parts for the fire line headers (suction and discharge), Check/Sluice/Butterfly valves/wheel valve, Strainers etc installed at the fire pumping stations including removing the existing component and staking at division's stores, testing to show proper performance all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
Spindle or wheel of CI Gate/Sluice Valve- Φ250 mm
Spindle or wheel of CI Gate/Sluice Valve- Φ200 mm
Spindle or wheel of CI Gate/Sluice Valve- Φ150 mm
Spindle or wheel of CI Gate/Sluice Valve- Φ100 mm
Spindle or wheel of CI Gate/Sluice Valve- Φ80 mm
Bronze gate flap/Flap cover of size ranging from - Φ80 mm to Φ250 mm
S S Screens suitable for units of size ranging from - Φ80 mm to Φ250 mm
Fixing in position the departmentally supplied Sluice valve or wheel valve in the running or new pipe line including cutting of the existing or new pipe line, turning,machining,welding etc including providing & fixing EPDM gasket, distance piece with or without flanges or with pair of flanges complete with nut bolts including testing at working pressure of 10 kg per sq cm to show proper performance including removing the existing worn out valves and other components and staking at division's stores all as per detailed specifications, standard operating procedures with total adherence to labour laws, contract conditions etc and as directed by Engineer in Charge.
CI Gate/Sluice Valve- Φ250 mm with pair of flanges in distant piece
CI Gate/Sluice Valve- Φ200 mm with pair of flanges in distant piece
CI Gate/Sluice Valve- Φ150 mm with pair of flanges in distant piece
CI Gate/Sluice Valve- Φ 80 or Φ 100 mm with flanged distant piece
Repairing at scattered locations, flanged joint of specified diameter for DOUBLE FLANGED CAST IRON PRESSURE PIPES AND SPECIALS for fire water line by opening of defective joint together with one additional joint on either side of defective joint (if required), including re-aligning the disturbed pipes and providing all necessary jointing materials like Neoprene rubber gasket, mm threaded nuts, bolts, spring washers etc. complete and testing the joint for 16 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours as per drawings, specifications and as directed by Engineer-in-charge
Repair, servicing and maintenance of BUTTER FLY VALVE of specified size including replacement of neoprene rubber gasket, mm threaded nuts, bolts, spring washers and greasing using Castrol or Servo grease @ 50 grammes to 100 gramme per valve etc. complete including testing the valves and joints for 16 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours etc. complete as per drawing, specifications and as directed by the Engineer-in-charge.
Repair, servicing and maintenance of CAST IRON SLUICE VALVES of specified size including replacement of Neoprene rubber gasket, gland rope, nut bolts, washers and greasing to the spindle and sheet etc. using Castrol or Servo grease @ 100 gramme to 200 gramme per valve complete including testing the valves and joints for 16 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours etc. complete as per drawing, specifications and as directed by the Engineer-in-charge.
Servicing and overall maintenance of LANDING VALVES of 65 mm dia including replacement of rubber gasket, Silicon/Nylone diaphragm washer, nut bolts, gland rope, diaphragm disc etc including greasing to the spindle and sheet @ 100 gramme per valve etc. complete to keep in good running condition as directed by the Engineer-in-charge. Note: The scope of this item does not include replacement of 25 mm dia & 175 mm long brass spindle.
Servicing and overall maintenance of LANDING VALVES of 65 mm dia including replacement of rubber gasket, Silicon/Nylone diaphragm washer, nut bolts, gland rope, diaphragm disc etc including providing & fixing new 25 mm dia & 175 mm long brass spindle including greasing to the spindle and sheet @ 100 gramme per valve etc. complete to keep in good running condition as directed by the Engineer-in-charge.
Servicing and maintenance of NON RETURN VALVE of 200 mm dia including replacement of rubber gasket, nut bolts, washers and greasing using Castrol or Servo grease @ 50 gramme per valve etc. complete to keep in good running condition as directed by the Engineer- in-charge.
Supply, installation and testing of 80 mm dia BUTTERFLY VALVE gear type of one of the reputed make like Normex,Marsh,Afcon,Omkar,Virgo,Maxflow,Challenger etc conforming to I S 13095 including making necessary joints, providing all jointing materials, greasing using Castrol or Servo grease @ 50 gramme per valve, testing the valves and joints for 16 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours etc. complete as per drawing, specifications and as directed by the Engineer-in-charge.
Repair ,servicing and maintenance of AIR RELEASE VALVE of 25 mm dia including replacement of balls, rubber gasket, nuts, bolts, washers etc. complete to keep in good running condition as directed by the Engineer- in-charge.
Polishing of 65 mm landing valves at scattered locations, using Brasso, Cotton waste, oil and greases etc to produce a shining surface including taking up the job after a general survey to identify valves where polishing is permitted by the department all complete as per specifications and as directed by Engineer in Charge.
Demolishing Reinforced cement concrete works by chiselling at all levels including scaffolding, cutting of reinforcement bars by gas cutting, straightening & stacking of steel bars and disposal of unserviceable materials within 50 metres lead etc. complete.
Labour only for fixing of water monitors on existing fire water line including transporting the monitors safely up to worksite, cutting of pipes/opening of blind flanges and providing all necessary jointing materials like Neoprene rubber gasket, mm threaded nut bolts, washers etc. complete and testing the joints for 10 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours etc. complete as per drawing, specification and as directed by the Engineer-in-charge.
Providing, laying, jointing, fixing and testing of expansion joint suitable for fixing in specified size of MS/CI line manufactured by fabrication using Class ‘C’ heavy variety M.S. non galvanized pipes of Preferred make as per I.S. 1239-1979 of dimensions as shown in drawing no. 1410/1 including providing & welding front & rear flanges having uniformly spaced eight nos 22 nb holes for providing & fixing large nut bolts including cutting the pipes at site for proper fixing, turning of expansion joint, as required for proper fixing complete as per the code of practice of water supply in building of IS: 2065-1972, including testing the pipes and fittings for 16 kg/cm2 pressure with a minimum period of 2 hrs. duration, including laying at all levels including cost of all hoisting mechanism, tools & tacles,painting 2 coats with synthetic enamel paint over a coat of primer on all exposed portion of expansion joint etc complete generally as per drawing, specifications and as directed by the Engineer-in-Charge.
a)Expansion joint suitable for fixing in 200 mm nb MS/CI line manufactured by fabrication as described above including two nos flanges as specified with lengthy nut bolts etc.
b)Expansion joint suitable for fixing in 150 mm nb MS/CI line manufactured by fabrication as described above including two nos flanges as specified with lengthy nut bolts etc.
c)Expansion joint suitable for fixing in 100 mm nb MS/CI line manufactured by fabrication as described above including two nos flanges as specified with lengthy nut bolts etc.
Providing, laying, jointing, fixing and testing of double flanged distance pieces of total length ranging from 80 mm to 100 mm as per site conditions suitable for fixing in 150 mm nb MS/CI line manufactured by fabrication using Class ‘C’ heavy variety M.S. non galvanized pipes of Preferred make as per I.S. 1239-1979 including providing & welding front & rear flanges having uniformly spaced eight nos 22 nb holes for providing & fixing large nut bolts including turning of old/new pipes as required for proper fixing of butter fly valves or other fitments complete as per the code of practice of water supply in building of IS: 2065-1972, including testing the pipes and fittings for 16 kg/cm2 pressure with a minimum period of 2 hrs. duration, including laying at all levels including cost of all hoisting mechanism, tools & tacles,painting 2 coats with synthetic enamel paint over a coat of primer on all exposed portion of distance piece with double flanges etc complete as per drawing, specifications and as directed by the Engineer-in-Charge.
Providing, laying, jointing, fixing and testing of double flanged distance pieces of total length ranging from 80 mm to 100 mm as per site conditions suitable for fixing in 200 mm nb MS/CI line manufactured by fabrication using Class ‘C’ heavy variety M.S. non galvanized pipes of Preferred make as per I.S. 1239-1979 including providing & welding front & rear flanges having uniformly spaced eight nos 22 nb holes for providing & fixing large nut bolts including turning of old/new pipes as required for proper fixing of butter fly valves or other fitments complete as per the code of practice of water supply in building of IS: 2065-1972, including testing the pipes and fittings for 16 kg/cm2 pressure with a minimum period of 2 hrs. duration, including laying at all levels including cost of all hoisting mechanism, tools & tacles,painting 2 coats with synthetic enamel paint over a coat of primer on all exposed portion of distance piece with double flanges etc complete as per drawing, specifications and as directed by the Engineer-in-Charge.
Providing, laying, jointing, fixing and testing of blind flanges of following sizes suitable for fixing in MS/CI manufactured by fabrication using specified thickness of M S plate including making holes for providing & fixing large nut bolts, 3 mm thick neoprene gasket, all complete as per the code of practice of water supply in building of IS: 2065-1972, including testing the pipes and fittings for 16 kg/cm2 pressure with a minimum period of 2 hrs. duration, including laying at all levels including cost of all hoisting mechanism, tools & tacles,removal of old worn out flange or other fitment, painting 2 coats with synthetic enamel paint over a coat of primer on all exposed portion of flanges etc complete as per drawing, specifications and as directed by the Engineer-in-Charge.
16 mm thick, 200 mm dia blind flange for fixing in 80 mm n b pipe with gasket and 8 nos large nut bolts of 16 mm dia in machine made suitable holes.
16 mm thick, 220 mm dia blind flange for fixing in 100 mm n b pipe with gasket and 8 nos large nut bolts of 18 mm dia in machine made suitable holes.
20 mm thick, 280 mm dia blind flange for fixing in 150 mm n b pipe with gasket and 10 nos large nut bolts of 18 mm dia in machine made suitable holes.
22 mm thick, 350 mm dia blind flange for fixing in 200 mm n b pipe with gasket and 12 nos large nut bolts of 20 mm dia in machine made suitable holes.
32 mm thick, 550 mm dia blind flange for fixing in 350 mm n b pipe with gasket and 16 nos large nut bolts of 25 mm dia in machine made suitable holes.
Collecting fire water samples as directed, from fire hydrants or fire sumps at scattered locations in RRCAT, carefully in containers disinfected as per I S 1622-1987 for arranging testing on specified parameters as per IS 3025 part 1 to 60 to ascertain suitability of water for intended use, complete as per following notes and as directed by the Engineer-in- Charge.
Repainting of old painted surfaces with two coats of Enamel PU paint of Preferred make of approved post office red color/black flat oil paint on all fire pipe line headers /valve /h.p.tank /Diesel tank/pumps/Air compressor /supports etc within pumping station premises including preparing the surfaces, removal of old paint, if any, sand papering, filling with putty as required complete as per specifications and as directed by Engineer in Charge.
0.00 metre to 1.50 metre below average G.L
Lead charges by mechanical transport for lead exceeding 2 Kms but not exceeding 3 Kms including loading, unloading, stacking, levelling etc.
All soils
Demolishing brick work in cement mortar including scaffolding, stacking of serviceable material and disposal of unserviceable material within 50 mtr. lead as per drawings, specifications and as directed by the Engineer-in-Charge.
DEMOLISHING PLAIN CEMENT CONCRETE WORKS BY CHISELLING at all levels including scaffolding, disposal of materials within 50 m lead as per drawings, specifications and as directed by Engineer-in-charge.
Demolishing brick work in cement mortar at all levels including scaffolding, stacking of serviceable materials and disposal of unserviceable materials within 50 metres lead etc. complete.
Plain cement concrete 1:3:6 using graded stone aggregate 40 mm max. size including hand mixing,consolidating, finishing, curing ,etc complete but excluding formwork and as per drawings, specifications and as directed by the Engineer-in-charge.
REINFORCED cement concrete at all levels in M-20 grade using graded stone aggregate of 20 mm max. size including machine mixing, consolidation, finishing, curing, etc., complete at all height as per drawings, specifications and as directed by Engineer-in-charge but excluding shuttering, formwork and steel reinforcement.
In foundations, footings, plinth beams, base of columns, flooring.
Providing and placing in position REINFORCEMENT using TMT BARS of Preferred make having minimum yield strength of Fe 500 conforming to IS 1786, for reinforced cement concrete work at all levels, including cutting, bending, fixing, tying in position with 1.6 mm dia. soft drawn annealed binding wire, with chairs, legs, supports etc. complete including cost of transporting the bars from factory to required location at work site, cost of 1.6 mm dia. soft drawn annealed binding wire, watch & ward, insurance etc complete all as per drawing, specifications and as directed by Engineer-in-charge. (The contractor has to submit the test report & Challan of the reinforcement, procured by him.)
NOTE: Binding wire required for the work will have to be supplied by the contractor at their own cost and will not be measured for payment.
Providing centering and shuttering at all heights using timber planks/steel plates including strutting and propping etc. and removal of the same for in situ reinforced concrete and in plain concrete work as per drawings, specifications and as directed by Engineer-in-charge.
Foundations, footings, base of columns, plinth beams, flooring, machine foundations, bed blocks, windows cills, copings and mass concrete.
Providing, fabricating, cutting, erecting, and fixing in position structural steel works of any shape using ISMBs, Joists, channels, angles, flats, Tees etc. of minimum grade Fe 250, at all levels including welding, two coat painting with a primary coat of approved steel primer and transportation etc. complete as per specifications and as directed by Engineer-in-Charge. (The welding weights shall not be measured for payments but cost of same shall be included in the rate.)
Note: Only standard weight as per I S tables or actual weight of prefabricated sections whichever is less shall be considered for payment and welding weight shall not be considered for payment.
Providing & fixing in position Two piece/three piece full bore gear operated cast steel Ball Valves with flanged ends conforming to BS: 5351/ANSI B16.34, grade WCB, making necessary flanged joints, providing all jointing materials, testing the valves & joints and joints for 16 kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours including cost of removing of old existing valve etc. complete as per drawing, specifications and as directed by the Engineer-in-charge.
Making LEAD CAULKED JOINTS to cast iron socket and spigot or double socket pressure pipes and specials for water supply including cost of lead, spun(jute)yarn, fuel, labour, including making socket pits for lead pouring and caulking and testing the joints with clean and potable water for 10kg/cm2 pressure with a minimum testing duration of two hours as per specification and as directed by the Engineer-In-Charge.
150mm dia
100mm dia
80mm dia
Providing , laying and jointing cast iron specials/fittings for pressure pipes for water supply like tees, bends , collars, reducers, enlargers of all sockets, socket and spigot or double end flanged conforming to IS -1538 (Part I to XXIII)-1976 to correct alignment and levels including testing the specials to 10kg/cm2 pressure with minimum period of testing of two hours clean and potable water, complete as per drawing and specifications and as directed by Engineer-In-Charge.
Providing & fixing best Indian make C.I.GATE VALVE with flanged ends conforming to IS 780, along with a pair of C.I.tail pieces conforming to IS-1538, making necessary flanged joints, providing all jointing materials, testing the valves and joints for 10kg/cm2 pressure with clean and potable water with a minimum testing duration of two hours etc.,as per specification and as directed by the Engineer-In-Charge.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Providing , jointing and fixing HEAVY QUALITY G.I. FLANGES in pair for m.s. galvanized pipes conforming to I.S.: 778 including bolts, nuts, rubber insertion , including testing the joints for 16kg/cm2 pressure with clean and potable water with a minimum period of two hours duration & removing of old damaged flanges etc. ,as per specification and as directed by the Engineer-In-Charge.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
Providing, laying, jointing & fixing in position Mild Steel ERW pipes ’ conforming to IS: 1239 having minimum specified thickness manufactured by Preferred make , Electrodes including providing & fixing all required M.S. fittings & specials of grade ‘C’, cost of transportation to site, welding, testing at a pressure of 24 kg per sq cm for 30 minutes duration and a coat of approved epoxy primer etc. complete as per drawing, specifications and as directed by Engineer-in-charge.
150 mm (5.40 mm Minimum thickness)
100 mm (5.40 mm Minimum thickness)
80 mm (4.80 mm Minimum thickness)
Providing and laying in trenches socket and spigot centrifugally cast (SPUN) DUCTILE IRON PRESSURE PIPES FOR WATER SUPPLY CLASS K-9, PN 10, conforming to IS: 8329, externally bituminous painted over zinc coating and internally cement lined, including lowering and keeping them in position to correct alignment and levelling, including cutting to waste of pipes wherever necessary, testing the pipes after making necessary joints (joints measured and paid for separately) to 10kg/cm² pressure with minimum duration of testing for two hours with clean and potable water etc. complete.
Note: The measurement shall be taken along the centre line of pipes in between the fittings or specials.
Providing, fixing and laying Ductile Iron fittngs and specials of class K12 suitable for push on jointing externally and internally coated and testing the same as per IS 9523 etc complete as per specifications and as directed by engineer-in charge.
Providing and fixing in position rising spindle type preferred make gate valve for presure rating PN 1.6 confirming to IS: 14846/BS5163 with flanged ends confirming to IS 1538, fixing to existing flanged ends , providing all jointing materials ,neoprene gaskets, nuts, bolts, washers & removing of old existing valve etc. testing the valves and joints for 16Kg/cm2 pressure with clean and potable water with a minimum testing duration of 2 hrs etc. complete as per drawing, specifications and as directed by Engineer-in- charge.
Providing and fixing Gun metal Landing Valve consisting of stop valve and check nut valve, spindle,hand wheel, instantaneous female outlet fixed at 90 degree off to vertical axis of valve with blank cap fixed to outlet etc. confirming to IS 5290 including testing at 10 Kg/sqcm. for a period of 2 hours with clean water including making necessary flange joints with rubber insertion, bolts and nuts, painted with two coats of paint of approved shade over a coat of primer & remving of old damaged existing Landing Valve etc. complete all as per specification, drawings and as directed by Engineer in charge.
Supply and erection of 20/25 mm GM air release cock, with necessary GI coupling to be fitted on top of Air vessel or on wet riser including removing of old existing air release cock all as per drawings, specifications and as directed by Engineer in Charge.
Welding of M.S. Pipe line or any other member of any size any-where in RRCAT premises at all heights including scraping of existing worn out joint welding of joints using approved electrodes to achieve 3mm weld thickness of required weld length including removing flux, debris etc., painting one coat of steel primer touch up, grinding of joint before painting including safe removing & refixing of glass if necessary etc. complete as per drawing, specifications and as directed by Engineer-in-charge.
Supplying & Installation of best Indian make Pressure gauge for fire line including making joints, supplying all jointing materials including providing & fixing 3/8 " S S ball valve, 3/8 " brass,elblow nipple,bush & remving of old / damaged existing Pressure gauge etc complete including testing the pressure gauge & joints to 16 kg per Sq cm pressure with clean & potable water with minimum testing period of two hours duration, all as complete as per drawing and specifications and as directed by Engineer-In-Charge.
Repainting of old painted surfaces of C I /M S water line of specified diameter with two coats of compatible synthetic enamel/flat oil paint of approved shade & preferred make including preparing the surfaces, including removal of old paint, if any, sand papering, filling hair cracks with putty and other cracks with 'Roffe' repair mortar, primer as required, scaffolding & cleaning, cost of all materials, labour, all complete as per drawing, specifications and as directed by Engineer-in-charge.
100 mm dia
150 mm dia
200 mm dia
P M ENTERPRISES
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .