Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | Ist₹27.1 LAccepted-Finance | Ist | Accepted-Finance L1 | |
| 2 | IInd₹29.4 LAccepted-Finance | IInd | Accepted-Finance L2 | |
| 3 | IIIrd₹33.8 LAccepted-Finance | IIIrd | Accepted-Finance L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹27.3 L
EMD Value
₹28,000
Closing Date
14 Jul 2022, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Electricity Transmission Circle-I, U.P. Power Transmission Corporation Ltd. 57- George Town, Prayagraj
64-ETC-I(A)/ 2022-2023
2022_UPTCL_712949_1
64-ETC-I(A)/ 2022-2023
Open Tender
Electrical Works
Item Rate
60 days
Sangipur
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE,ETC,PRAYAGRAJ
₹28,000
19 Jul 2022
6 Jul 2022
15 Jul 2022
6 Jul 2022
14 Jul 2022
6 Jul 2022
120 days
Amount
Erection, Testing and commissioning of 160 MVA 220/132 kV Transformer-I
Filling the T/F oil in oil tank and its centrifuging upto required BDV value and creating the vacuum inside the 160MVA T/F before filling the T/F oil inside the main tank.
Safe handelling and shifting of all acces. Of new 160MVA T/F-I such as radiators, conservator tank, bushing, coolings fans, motor drive mechanism of RTCC panel, oil pipe lie etc. from store place of subsatation sangipur to erections site including other associated work also if required for compltetion of job satisfactorly.
Complete erection of 220/132/11 KV 160 MVA T/F -I by erection of radiator, conservator tank, all bushing, their turrets connection of pipe lines cooling fan,PRV,OSR, motor drive mechanism of tap changer, RTCC Panel and all associated oil pipe lines etc to complete the job satisfactorily including 1st filling of oil and topping up of transformer oil(not circulation) in tank, radiator, oil pipe lines, conservators tank etc. and attending the oil leakage if any and all other associated work for satisfactory completion of work at 220KV S/S Sangipur. Crane, T&P shall be provided by contractor, all assistance in getting the transformer AND successfully commissioned by providing qualified manpower till commissioning.Complete evacuation of main tank of transformer and filling of nitrogen in vacuum up to required pressure and again evacuation the transformer tank after required time interval using centrifuging machine. Scope of work involves providing nitrogen gas or dry air generator having dew point 60 to 65 degree centigrade and filling it in main tank of transformer up to pressure of 5PSI or as per instruction of site engineer of BHEL and maintaining it in the tank as per direction of service engineer required for dry out of T/F. This process shall be repeated till the desired value of 5PPM or as direction of BHEL service engineer.
Centrifuging of complete T/Fs oil in T/Fs main tank by connecting centrifuging pipes circulating the T/F oil through centrifuging machineand taking the BDV, meggar value & IR values of the oil periodically till the required value in achieved as per direction of Supervising Engineer. The work includes all the work related to centrifuging the oil and filling the oil in T/F tank(centrifuging machine and operator shall be arranged by the contractor)
Laying, dressing and binding of cable including fixing of cable tray support structure and termination of cable making the top and its ferruling as per schedule and inter connection as per as per requirement of turrets , WTI, OTI, Bucholz relay, PRV, cooling fans, Pumps, OLTC, marshaling box etc. with proper ferruling as per drawing etc.
Earthing of T/F body, marshaling box, OLTC, RTCC Panel, at two point with 75x10 mm and 50x6mm M.S Flat from 40mm M.S Round(M.S Flat to be provided by departement)
Painting of earthing strips above the ground level by one coat of red oxide and two coat of bus green paint.
Delta earthing for 220/132/11 kv ,160 MVA T/F consisting of delta set with 3 nos.40 mm dia size 3 Mtrs. Long electrode its placing inside the ground and connecting all the three electrodes with 75x10mm M.S Flat 700 mm deep and connecting the same with eartmat at two places ( M.S round bar & flat provided by the department)
carriage of 40/20 KL oil tank including loading and unloading from UPPTCL s/s to 220 kv Sangipur s/s within approx 120 km distance
Testing of centrifuge T/F oil (DGA, ppm, BDV)of 160 MVA T/F at 220/132 KV S/S Sangipur, from government approve laboratory at the time of commissioning of transformer and after charging on load (preferbarly after 15 days)
Pre-erection and pre-commissioning testing as per site requirement for charging of 160MVA, 220/132KV T/F at 220KV S/S Sangipur under ETD-Pratapgarh. Testing kit and skilled operator shall be provided by contractor on their own cost and job includes to and fro charges per visit. the details of Pre-erection and pre-commissioning test are as followes :
insulation resistance measurement
Current ratio of LV& HV bushing
OTI and WTI calibration .
Transformer primary, secondary and tertiary winding capacitance, dissipation factor (Tan delta test), bushing capacitance test before erection and after erection on T/F.
Protection rely operation check.
Magnetizing current test
Vector group test.
Open circuit &Short circuit test
Magnetizing balance test
Voltage ratio test
winding resistance Measurement
Erection of following equipments as per instruction manual of various equipments and technical specification including shifting of material/equipment from store to erection site including all other associated work to complete the job satisfactorily.
Erection of 245kV SF6 Circuit Breaker pole with all access. and fittings as per manual
245kV CT Junction Boxes
245kV CVT Junction Boxes
245kV Tandem Isolators (Motorised) with post insulator all accs., Disconnector box & fitiings as per manufacture manual
36kV Drop Out Fuse Set with Post Insulators
245kV Post Insulators for support
198kV Surge Arrestors with all accss. And fittings etc
120kV Surge Arrestors with all accss. And fittings etc
Metering cubicle for ABT energy meters alongwith 4 nos. ABT meters
1.1kV Copper Control Cable laying ( Laying of following sizes of Copper Control Cables in the Cable trenches from various equipments / marshalling boxes / J.B.s in switch yard to control / relay panels in Control Room / BCU / Kiosk as per cable schedule, its saddling with saddle at every 750 mm distance including carriage of cable drums from store to site and shifting back to store and all other associated works to complete the job satisfactorily as per technical specification.)
2 Core x 2.5 Sq.mm
4 Core x 2.5 Sq.mm
6 Core x 2.5 Sq.mm
10Core x 2.5 Sq.mm
1.1kV Copper Control Cable dressing ( dressing of following sizes of Copper Control Cables in the Cable trenches from various equipments / marshalling boxes / J.B.s in switch yard to control / relay panels in Control Room / BCU / Kiosk as per cable schedule, shifting of material to site and back to and all other associated works to complete the job satisfactorily as per technical specification.)
2 Core x 2.5 Sq.mm
4 Core x 2.5 Sq.mm
6 Core x 2.5 Sq.mm
10Core x 2.5 Sq.mm
Control cable terminations (per core both ends)
Laying of power cable of following sizes 300mm below ground level including excavation of trench and laying of cable and putting 1st class bricks on its 75 edge along with cable on both side, filling the same with Ganga sand and then putting bricks on 115 mm side over the trench and then filling with earth including cost of brick, sand etc. and all other associated works to complete the job satisfactorily as per technical specification
3.5 Core x 95 Sq.mm
3.5 Core x 50 Sq.mm
Termination of following size of power cable by providing proper size of Aluminum Dowell/Jenison make lugs its crimping and connecting with equipments including cost of lugs and all other associated works to complete the work satisfactorily as per technical specification. The rates of termination of power cable includes the all cores of cable at one end with lug)
95 sq mm power cable terminations
50 sq mm power cable terminations
Erection of Auxiliary Structure, mast etc required for installation of CTs, LA,TI,PI,BSI etc at 220KV S/S Sangipur. The job consist shifting of all material i.e. structure parts, nuts, bolts, washers etc, from store to site of erection. Erection of structure as per relevant drawing and using flat/spring washer with each bolt matching holes, cutting notching of members if required shall also be done by the contractor without any extra cost of complete the work satisfactorily. All material to be erected shall be supplied by UPPTCL free of cost but all men, material and T&P required for satisfactorily completion of work shall be arranged by the contractor on his own cost.
Laying of 40mm dia MS round bar 800mm below ground level including cutting, straightening, welding painting of one coat of red oxide the two coat of black bitumen paint at joint excavation of trench, its back filling and all other associated work to complete the work satisfactorily as per drawing and technical specification, excluding the cost of MS round bar
Fabrication of 3M long electrodes with 40mm round bar having 150mm long conical shape and then its piercing vertically inside the ground with top 700mm below ground level and its welding with earthmat, excluding the cost of MS bar.
Earthing of auxilary structures & main structure and equipment such as isolator, panel and breaker by cutting, straightening, bending of MS falt and legging 800 mm below inside the ground up to earth mate and top of main & auxiliary structures including welding/jointing with main earth mate and structures/ equipments to be earthed including excavations of trenches its back filling and painting of earthing flat with green colour and all other associated work includig cost on men and T&P in scope of contrator.(MS Flat will be provided by department)
Earthing by75 x 10 mm MS flat
Earthing by 50 x 6 mm MS flat
Earthing by 25 x 6 mm MS flat
Interconnection & jumpering of various equipments with ACSR Zebra between Main and Transfer Bus Conductors, jack bus, Post Insulator equipments with the help of suitable clamps (to be provided by department) with all other associated cutting , bending and shifting of conductor works forsatisfactory completion of the job as per technical specifications. (1 Job includes Interconnection and jumpering of all the equipments in that Bay) :
Erection and commissioning of 63 kVA DG set with all access. And fittings as per manual
Erection and commissioning of Bay Marshalling Kiosk for 220KV Switchyard as per manual (Grouting of AC power supply cubical Box at 220KV S/S Sangipur under ETD-Pratapgarh for connection of circuit breaker and isolator etc. This Job also includes construction of tin shed for AC Power Supply cubical of size 1200x750x400 mm. All other associated work like two coat painting of tin shed and angle etc. required to complete the job satisfactorily including arrangement of all labour and T&P at his own cost.Tin shed and angle will be provided by contractor)
Erection and commissioning of Bay Marshalling Kiosk for 132KV Switchyard as per manual (Grouting of AC power supply cubical Box at 220KV S/S Sangipur under ETD-Pratapgarh for connection of circuit breaker and isolator etc. This Job also includes construction of tin shed for AC Power Supply cubical of size 1200x750x400 mm. All other associated work like two coat painting of tin shed and angle etc. required to complete the job satisfactorily including arrangement of all labour and T&P at his own cost.Tin shed and angle will be provided by contractor)
Installtion of GI perforated trays of various sizes for all cable trenches in switchyard 220/132/33KV , control room and bay kiosks.
SUPPLY
GI perforated trays of various size as required for all cable trenches in switchyard 220/132/33KV , control room and bay kiosks.
Bay marshalling Kiosk
for 220KV switchyard , AC Power Supply cubical of size 1200x750x400 mm made by 16SWG MS sheet with first quality Asian/ Nerolac/ Berger Paint one coat of red oxide primer and two coat of super enameled grey paint having 03 Nos installed Aluminum bus bar of size 25x12 mm and 750mmlength for R, Y & B phase & 01 No. Aluminum bus bar for neutral of size 25x6 and 750mm length mm cubical will have 200 Amp. Rotary Switch fuse unit 01 No, with 16 No. 16 Amp and 02 nos 32Amp. Triple pole neutral miniature circuit breaker of Schneider / Indotech made for arrangement of power supply. The cubical shall have the provision of visual indication of incoming supply & indoor light fitting of 12 watt LED lamp. The power cubical shall be weather proof, dust proof with proper locking arrangement.
for 132KV switchyard AC Power Supply cubical of size 1200x750x400 mm made by 16SWG MS sheet with first quality Asian/ Nerolac/ Berger Paint one coat of red oxide primer and two coat of super enameled grey paint having 03 Nos installed Aluminum bus bar of size 25x12 mm and 750mmlength for R, Y & B phase & 01 No. Aluminum bus bar for neutral of size 25x6 and 750mm length mm cubical will have 200 Amp. Rotary Switch fuse unit 01 No, with 16 No. 16 Amp and 02 nos 32Amp. Triple pole neutral miniature circuit breaker of Schneider / Indotech made for arrangement of power supply. The cubical shall have the provision of visual indication of incoming supply & indoor light fitting of 12 watt LED lamp. The power cubical shall be weather proof, dust proof with proper locking arrangement.
Omurmila Constructions
Preeti Enterprises
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .