Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹4,000
Closing Date
24 May 2023, 10:00 amClosed
EE ETD Banda
220 KV Substation Tindwari Road Banda
Electrical Work
2023_UPTCL_802866_1
T-21/ETDB/2023-24
Open Tender
Electrical Works
Lump-sum
90 days
Banda
Having experience to do similar work in UPPTCL
2 documents required · 2 mandatory
₹590
EE ETD Banda
₹4,000
24 May 2023
18 May 2023
24 May 2023
18 May 2023
24 May 2023
18 May 2023
18 May 2023 - 24 May 2023
Amount
Details of Substation.
Repairing and Overhauling & Servicing of 145KV Circuit Breaker at 220 KV S/S Pahadi. Work consist of : (a) Complete dismantling of 01 No. pole mechanism assemby, main spring, ratchet gear and other connected part. Necessary repairing/rectification of defective part. (b) Replacement of all damaged and defective parts closing latch assembly, trip latch, close coil etc and its proper adjustment. Cleaning & greasing. (c) Check Gas pressure switch with proper adjustment and calibartion (d) Dismentling of all pole linkage, pins and rod assembly, cleaning, greasing and its proper adjustment. (e) Check statisfactory close/trip operation of the breaker both by local remote . (f) Check close/trip timing by digital timer
Repairing and Overhauling & Servicing of 33 KV VCB at various substation of ETD Banda. Work consist of : (a) Checking & Adjustment of Snatch gap travel of drive Insulators rod and tie rod of each Pole. (b) Replacement of all damaged and defective parts closing latch assembly, trip latch, close coil etc and its proper adjustment. Cleaning & greasing. (c) Oiling and Greasing of CRANK gear by openng of lock, circlip etc. (d) Dismentling of all pole linkage, pins and rod assembly, cleaning, greasing and its proper adjustment. (e) Check statisfactory close/trip operation of the breaker both by local remote . (f) Check close/trip timing by digital timer (g) Repairing of mechanism for solving the mechnical problem.. After Overhauling of VCB following test to be carried out. (i) Opening & Closing time of breaker of each Pole (ii) carring of contact resistance measurement of each Pole. (iii) Checking of Megger value of breaker Pole.
Measuring of CRM, Closing, Tripping time analysis & Operation Time measurement of 145 KV CB.
Synchronization of All relays (main-1 & main-2) with GPS Clock
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
M/S QUADRY CONTRACTOR AND SUPPLIAR
RAGHAVI ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .