Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAccepted-AOC 00 BALITIKURI BALITIKURI NASKARPARA HOWRAH WEST BENGAL 711113 | HOWRAH | WEST BENGAL | 711113 | ₹1.6 Cr | L1 | Accepted-AOC ACCEPTED |
| 2 | L2₹1.8 Cr+₹17.2 L (10.4%)Rejected-Finance | ₹1.8 Cr+₹17.2 L (10.4%) | L2 | Rejected-Finance Quoted Higher Rate |
| 3 | L3₹2.0 Cr+₹39.3 L (23.8%)Rejected-Finance | ₹2.0 Cr+₹39.3 L (23.8%) | L3 | Rejected-Finance Quoted Higher Rate |
Tender Value
Refer Docs
EMD Value
₹5 L
Closing Date
31 Dec 2018, 1:00 pmClosed
SUPERINTENDING ENGINEER , P.W.D., HEC
KIT Annex Building, 5th FLOOR, KOLKATA 700073
Shifting of LT panels from central corridor at different fl. of Main Bldg. to the proposed four storied Electrical panel room attached with a 20 passenger lift block in the Main Bldg. within the campus of SSKM Hospital, Kol. Scheme Code PG17 EI Work
2018_WBPWD_198872_1
WBPWD/SEHEC/SKHED/NIQ37/18-19
Open Tender
ELECTRICAL WORKS ORG
Item Rate
300 days
SSKM Hospital
Please refer Tender documents.
5 documents required · 5 mandatory
₹5 L
O/O the SE, P.W.D., Health Electrical Circle
29 Jan 2021
30 Nov 2018
2 Jan 2019
1 Dec 2018
31 Dec 2018
7 Dec 2018
6 Dec 2018
Amount
SUB HEAD-I : LT PANEL
DG BACK UP PANEL WITH DUAL SOURCE POWER : (Main Panel -1&2)
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
RAW POWER PANEL WITH DUAL SOURCE : (Main Panel -3)
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
SUB-PANEL WITH DUAL SOURCE DG BACK UP : [Sub Panel no. 1]
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
SUB-PANEL WITH DUAL SOURCE DG BACK UP : [Sub Panel no. 2, 3 & 4]
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
SUB-PANEL WITH DUAL SOURCE DG BACK UP : [Sub Panel no. 5]
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
RAW POWER SUB-PANEL : [Sub Panel no. 6]
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
SMART SUB-PANELs FOR CRITICAL AREA : [Emergency OT, ITU, CCU & PICU] :
SITC of floor mounted Indoor type extensible cubical MV switchboard,fabricated by CPRI approved panel maker having compartmentalized design, fabricated out of 14 SWG ( 2.0 mm ) nominal thickness CRCA sheet steel,front and back openable, hinged, single shuttered, with incoming ACBs/MCCB & Outgoing ACB/MCCB/Main Switchs and all accessories as per size, design & drawing to be approved by EIC and conforming to IS with latest modification and as per detail specification attached ( uploaded in the specification section)
Design, Manufacture, testing, supply, installation and commissioning of Double door outdoor type Distribution Feeder Pillar box conforming to Indian Standard IS : 5039-1969 with latest amendments,suitable for use on 3 phase 4 wire, 400/440 Volts 50 Cycles A.C. Supply and shall be suitable for short circuit fault of 31 MVA at 415 Volts, fabricated as per size, design & drawing to be approved by EIC. The Enclosure shall provide Degree of protection IP -54 in accordance with IS : 2147 -1962 with its latest ammendmentThe feeder pillar box will be fabricated by CPRI approved fabricator as per detail specification attached ( uploaded in the specification section).
S&F of 415V, 160 A TPN Main Switch in SS enclosure with 3 nos. 125 Amp. HRC Fuse (minimum 80kA) having blown fuse indication and both side cable end box on MS frame on wall (Make - L&T, Cat No. SK95005).
S&F of 415V, 160 A four pole on-load changeover switch in SS enclosure with both side cable end box on MS frame on wall (Make - L&T, Cat No.CO21600OSOO ).
SUB HEAD-II : CABLING WORK
Supply of Cable Supplying of one number 1.1 KV Grade XLPE insulated and PVC sheathed aluminium conductor cable ( Armoured ) conforming to IS: 7098 / 1988 with its latest amendment of following size. [ Make Nicco / Fort Gloster/Polycab/Havells]
4 Core 400 mm²
4 Core 300 mm²
4 Core 240 mm²
4 Core 185 mm²
4 Core 150 mm²
4 Core 70 mm²
4 Core 50 mm²
4 Core 25 mm²
Laying og Cable
(i) Laying of the following Cables in existing covered masonery trench incl. taking out RC covers, setting them in order as and mending good the damages to GS.
4 Core 400 mm²
4 Core 300 mm²
4 Core 240 mm²
4 Core 185 mm²
ii) Laying of the following Cables on prefixed tray/ Bracket including S&F MS clamps as required as to GS.
4 Core 400 mm²
4 Core 300 mm²
4 Core 240 mm²
4 Core 185 mm²
4 Core 150 mm²
4 Core 70 mm²
4 Core 50 mm²
4 Core 25 mm²
iii) Laying of the following Cables through prelaid UPVC / G.I. protection pipe as to GS.
4 Core 400 mm²
4 Core 300 mm²
4 Core 240 mm²
4 Core 185 mm²
4 Core 150 mm²
4 Core 70 mm²
4 Core 50 mm²
4 Core 25 mm²
S&F of Electro Zinc Galvanised (for indoor) / Hot Dip Galvanised (for outdoor) Wiremesh cable Tray in accordance with standard BSEN 12329-2000 with all mounting accessories. All trays should be 3005 mm long. Cable tray shall be manufactured from steel wires, welded together and bent into final shape prior to surface treatment. Steel Wire Cable Tray should be produced from lateral and longitudinal sidewall steel wires, with minimum diameters between 3.7 mm to 5.9 mm for trays depending on the widths of the trays as per the design parameters. Trays should be manufactured with a longitudinal ‘T-welded’ safety edge along the top wire of the sidewall. Trays should be constructed with a 50mm x 100mm mesh configuration. Trays should be coupled together using fast spring coupler. The coupling will have the same surface finish as the tray. Loading and deflection characteristics of the tray should be tested and the results published in accordance with the European Standard IEC 61537. Fire test certification should be published in accordance with the E30/E90 standard. Electrical continuity across a coupling should be demonstrated by means of a published test method and result. [MAKE: LEGRAND (CABLOFIL)/ OBO]
105 / 400 mm for outdoor application.
54 / 300 mm. for indoor application.
54 / 200 mm. for indoor application.
S&F of G.I. pipe protection (ISI-Medium gauge) for protection of cable.
100 mm dia
80 mm dia.
S&F of UPVC pipe protection (Schedule 80) for protection of cable.
250 mm dia
200 mm dia.
S&F of UPVC pipe coupler (Schedule 80) for following :-
250 mm dia
200 mm dia.
S&F of compression type gland complete with brass gland, rubber rings for dust & moisture proof entry of PVC armoured cables as below as per G.S.
4 core 400 sq mm
4 core 300 sq mm
4 core 240 sq mm
4 core 185 sq mm
4 core 150 sq mm
4 core 70 sq mm
4 core 50 sq mm
4 core 25 sq mm
4 core 16 sq mm
Finishing the ends of following cables by crimping method including S/F dowells solderless sockets, tapes and jointing materials etc. as per G.S.
4 core 400 sq mm
4 core 300 sq mm
4 core 240 sq mm
4 core 185 sq mm
4 core 150 sq mm
4 core 70 sq mm
4 core 50 sq mm
4 core 25 sq mm
4 core 16 sq mm
Straight through Jointing of cable of 3.5 / 4 core PVC / XLPE with heat shrink cable jointing kit Raychem including S&F ferrul, tapes and jointing materials (Brand approved by EIC)
4 core 400 sq mm
4 core 300 sq mm
4 core 240 sq mm
4 core 185 sq mm
4 core 150 sq mm
4 core 70 sq mm
4 core 50 sq mm
SUB HEAD-III : MCB BD etc.
S&F of 415V 8-Way double door Vertical TPN DB (make- Legrand) in S.S. enclosure on angle iron frame on wall consisting with 1 no. 160A, MCCB (35KA/25KA, 'C' curve) as incomer, 8 nos. 63A TP MCB as outgoing complete with all accessories & interconnection with 2 nos. Cable end box as per GS.
S&F of Double Door type horizontal TPN MCB PDB complete with DIN Channel, Neutral Bar, Earth Bar and other accessories on angle iron frame on wall, incl. necy. earthing attachment as per direction of EIC (for new requirement as well for replacement of existing derated DB in the surrounding area) :-
6-Way, TPN MCB PDB comprising with 1 No. 440V, 80/100A. 4-Pole Isolator as incoming and 18 nos. 250 V, 16-32 A. SP MCB as outgoing (For AC/power) (Make - Legrand).
4-Way,TPN MCB PDB comprising with 1 No. 440V, 63A. 4-Pole Isolator as incoming and 12 nos. 250 V, 16-32 A. SP MCB as outgoing (For Light & fan) (Make - Legrand).
S&F of Double Door type SPN MCB PDB complete with DIN Channel, Neutral Bar, Earth Bar and other accessories on angle iron frame on wall, incl. necy. earthing attachment as per direction of EIC as follows (for new requirement as well for replacement of existing derated DB in the surrounding area) :-
2+6 Way SPN MCB PDB comprising with 1 No. 250V., 40A. DP Isolator as incoming and 6 nos. 6/16 A. SP MCB as outgoing (Make - Legrand )
2+14 Way SPN MCB PDB comprising with 1 No. 250V., 63A. DP Isolator as incoming and 14 nos. 6/16 A. SP MCB as outgoing (Make - Legrand)
SUB HEAD-IV : Distribution Wiring
Distribution wiring in 1.1 KV grade 3x1.5 sqmm single core stranded 'FR' PVC insulated & unsheathed copper wire (Finolex/Havells/RR Kabel make) in 19mm bore, 3mm thick polythene pipe to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board concealed in wall complete with 2 nos. “Ph & N” copper bar incl. bakelite/ Perspex top cover 3 mm thick and incl. 175x100x65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish [concealed wiring for the panel bldg and new stairs all under construction] (Av. Run 10 Mtrs.)
S&F of 250V., 5A. 5-Pin Universal Key type Plug Base without Top and Piano Key type switch (both Anchor) on Board and Necy. Interconnections as per direction of E.I.C.
S&F of 16 SWG M.S. box with 3 mm. thick bkt top cover, following electrical accessories and earthing attachment incl. making connection as per GS as follows:-
240 x 200 x 65 mm comprising with 1 No. 250V 6 pin 20A plug socket with 1 No. 20A piano key type switch and 3 nos. 250V. 6A. 5 Pin plug socket with 3 nos. 6A Piano Key switch, 1 no. Indicator ( Anchor) and 20A switch type SP MCB (Siemens / Legrand)
150 x 100 x 65 mm comprising with 1 No. 250V 6 pin 20A plug socket with 1 No. 20A piano key type switch (Anchor)
175 x 100 x 65 mm comprising with 2 Nos. 250V. 5 pin 6A plug socket with 2 Nos. 6A piano key type switch (Anchor)
Distribution Wiring by S&F of following sizes PVC insulated Cu.wire in 19mm bore, 3mm thick polythene pipe concealed in wall complete with all accessories and mending good the damages incl.making connections as to G.S.:-
3x1.5 mm² for lift well wiring, separate 2x5A plug
2x2.5 mm² + 1x1.5 mm² for 15A power plug & Computer Boards
2 x 6 mm² & 1 x 4 mm² for Power DB to SPN DB
4 x 10 mm² & 2 x 6 mm² for sub-main wiring from VTPN to PDBs.
Finishing the ends of following sizes copper wire end / PVC cable/Al. with dowells solderless socket by crimping method as pre GS as follows :-
2 x 2.5 & 1 x 1.5 mm² cu. Wire
2 x 6 & 1 x 4 mm² cu. Wire
4 x 10 mm² & 2 x 6 mm² cu. Wire
SUB HEAD-V : Supply & Fixing of Fan
S&F of box type MS fan clamp for mounting ceiling fan as to GS.
S&F of 240 V, 100 Watt Step type Electronic Fan Regulator (Make - Anchor)
S&F of 230V, 48" (1200 mm) Sweep, A.C. Ceiling Fan ( Make: USHA Striker Plus / Crompton Greaves - HS+/HB+ / Orient Energy Star) 5-STAR Rating with minimum air delivery 210cu.m/min, speed 370 rpm, power input 52 watts without Regulator, incl. 1.6-2.5 micro-farad burst-proof P2 capacitor, Down Rod, Canopy, Fan Blades with all complete accessories and engraving & Painting the Departmental Number upto 15 digit on Fan Body and interconnection complete in all respect.
Supply of 230V, 18" (450mm) 4 (four) Blades Industrial type Air-Circulator Pedestal Fan complete with all accessories such as Regulator, Cord and 15 Amp. 3-pin Top (Make - E.P.C. Electrical Pvt. Ltd., Heavy Duty)
Supply & Fixing of 230V AC, 450 mm (18") sweep whole metal-body wall bracket fan (make- EPC Electricals Pvt. Ltd., Heavy duty) with P-2 type burst-proof capacitor and the fan to be grouted on wall incl making necesy. Connection as per direction of the EIC for lift m/c room & panel rooms.
S&F of 240V A.C. Exhaust Fan incl. Cutting hole on wall, with Louver Shutter (Aluminium) with Nuts, Bolts, washers etc. on wall and mending good the damages to original finish as per direction of the EIC.
1420 RPM, 300 mm. (12") sweep
SUB HEAD-VI : Supply & Fixing of Fittings & Fixture
S&F of 240V, LED tube light fittings suspended 25 cm. below the ceiling by 2 nos. 20mm. Dia. E.I. Conduit support with, MS 'L' clamp and necy. connection by 2 x1.5 mm² PVC insulated Cu. Wire & painting as follows:-
Single fittings incl. S/F 1 x 18 Watt LED Tube lamp (Make Philips, Cat No.TMC 501 P 1 x T LED, Master LED tube, model no. 18W 865 T8 I PC BODY/ equivalent product of Crompton/Wipro having similar specification in all respect)
Twin fittings incl. S/F 2 x 18 Watt LED Tube lamp (Make Philips, Cat No.TMC 501 P 2 x T LED, Master LED tube, model no. 18W 865 T8 I PC BODY/ equivalent product of Crompton/Wipro having similar specification in all respect)
S&F of Bulkhead LED Luminaire for wall mounting (Make-Philips) complete with 9Wt LED lamp and opal acrylic cover incl. necessary connection by 2 x 1.5 mm² PVC insulated Cu. Wire.
S & F Extra Conduit for suspension of FTL fittings exceeding 25 cm with additional 2 x 20 mm dia EI Conduit supports & necessary inter-connection by 3 x 1.5 mm² S/C PVC Cu. Wire, painting etc. as to GS.
SUB HEAD-VII : Earthing Installation
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By ISI Medium GI Pipe
Connecting the equipments to earth busbar incl. S & Drawing No. 6 SWG G.I. earth wire as to G.S.
S&F of Earth bus-bar of Galvanized MS flat 25 mm x 6 mm including nuts, bolts & washers etc. as to GS (for Lift well/ Panel rooms).
SUB HEAD-VIII : Miscellaneous
Preparation of planned & as-built G.A. drawings and Single Line Diagrams (SLD) of the proposed Electrical power distribution system of Main building from the sending end Sub-stations to the receiving end main panels of the building and from the main panel upto the TPN DB level mentioning their cable sizes at different levels and the drawings to be made in Autocad software in standard symbols and to be presented both in softcopies and hardcopies (6 copies of each set of drawing) in A1 sheets as per direction of the EIC.
Marking of identification number/nomenclature of ACB/Main switch/ VTPN/ HTPN/ SPN DB/ Starters etc after installation by suitable size identification plate or painted block letter matters as per direction of the EIC.
Hiring of 500 KVA Silent DG Set.
Hiring of Temporary Panel consisting of 630A SFU as incoming, 800A BBC and 2 x 400A SFU as outgoing.
Operation of 500/ 250 KVA Silent DG Set by skilled manpower for 8 hours.
Supply and pouring of Diesel including transportation upto worksite.
Withdrawing existing different sizes 1.1 K.V Grade 4/3.5 core PVC / XLPE cable from existing under ground trench very carefully one by one and shifting the above cable in proposed masonery cable trench incl. S & F MS clamps as required and mending by cavation of earth soil to original finish as per direction of EIC as follows.
One no cable upto 185 sq. mm. Cable
One no cable above 185 sq. mm. Cable
Two nos cable above 185 sq. mm. Cable
Dismantling & taking out existing old unnecessary LT panels very carefully after complete commissioning of the new panels from corridors of diffrent floors of Main Block after duly testing & disconnection of all sources of power one by one and shifting the panels to designated location in the campus of SSKM Hospital incl mending good the damages to original finish as per direction of EIC.
Terms and condition
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
M/S N. C. HORE
JAYBEECO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .