| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.8 LAccepted-AOC | L1 | Accepted-AOC L1 BID | |
| 2 | L2₹32.7 L+₹74,635.74 (2.33%)Rejected-Finance | L2 | Rejected-Finance BEING HIGHER THAN L1 BID | |
| 3 | L3₹41.0 L+₹9.0 L (28.1%)Rejected-Finance HALDIA BRAJALALCHAK DAKSHINCHAK BHABANIPUR EAST MEDINIPUR WEST BENGAL 721654 | MEDINIPUR EAST | WEST BENGAL | 721654 | L3 | Rejected-Finance BEING HIGHER THAN L1 BID | |
| 4 | Rejected-Technical 81 SAHAPUR MAIN ROAD PS BEHALA KOLKATA WB PIN 700038 | KOLKATA | WEST BENGAL | 700038 | - | Rejected-Technical NOT FULFILL THE TECH REQUIREMENT | |
| 5 | Rejected-Technical VILL RAJARCHAK PO HALDIA PORT DISTT PURBA MEDINIPUR WB PIN 721605 | MEDINIPUR EAST | WEST BENGAL | 721605 | - | Rejected-Technical NOT FULFILL THE TECH REQUIREMENT |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
26 Aug 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (CGN) kolkata
Military Engineer Services GE (I) (Coast Guard and Navy) Damodar Complex Naval Transit Accommodation Hastings, Kolkata 700 023
PROVN OF IMMEDIATE CRUCIAL REVAMPING REQUIRED AT CG VIKRAM ENCLAVE, ELECTRICAL HT ESTABLISHMENT AND UTILITIES (POWER RECEIVING END) UNDER GE (I) (CGN) KOLKATA
2022_MES_525756_4
8015/B/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (CGN) kolkata
as per tender document
11 documents required · 11 mandatory
₹500
GE (CGN) kolkata
₹78,000
Yes
18 Nov 2022
8 Aug 2022
27 Aug 2022
8 Aug 2022
26 Aug 2022
12 Aug 2022
Amount
Supply, install, testing & commissioning of indoor type VCB 630 A, 11 KV 3 phase, 50 HZ, 26.3 KA, HT totally enclosed free standing, sheet steel clad, cubical pattern, SCADA compatible,HT panel switch board with locking arrangement for panel doors, complete with short time with stand current sec with 3 Nos 630A PVC sleeved copper bus bars and comprising of the followings :- (A) Incoming TP vaccum circuir breaker 11 KV 630 A, horizontal draw out type, horizontal isolation, rated current 630 A -01 Nos each fitted with :- (a) Manually changing & closing mechanism, 1- Motorised spring charged closing mechanism. (i) Mechanical close/strip knob - 01 set. (ii) Mechanical ON/OFF indicator - 01 No. (iii) Mechanical spring charged / free indicator -01 No. (iv) 1- Set of 6 Nos + 6 NC Aux contact block -01 No. (b) 1- Set space heaters 1x100 watt -02 nos, 230V AC with switch humidity sensor and thermostat. (c) VCB ON & OFF switch, trip circuit heating, auto trip, service position, test position. (d) 1-Set of Red/green indicating lamps for circuit breaker on/off auto trip indication. (e) 3nos CTs 100-50/5A-5A, 1.0/5P10, 2.5VA/2.5VA, STC: 21KA/3s (f) 1-3 phasing cast draw out type potential transformer ratio 11 KV root 3/ 110 V class 0.5 accuracy, 50 VA/ph burden, complete HT & LT fuses and connected to incoming side ( one per incoming VCB) (g) Luminous push button for trip circuit check. (h) Microprocessor based relay with local display & communication port. (j) Multifunction electronic digital meter consisting of measurement of current, voltage frequuency, KW, KWH, KWARH etc type PM 500. (k) 1 No- Cut out plate for cable entry for HTcable upto 300 sq mm 3 core cable. (l) PVC FRLS copper cable single core multistranded of size 2.5 sq mm for all control wiring. (m) MCB DP 32A -01 No for control supply. Note: 1. OEM Drawings shall be submitted for approval prior to the assembling and necessary factory testing shall be carried out in presence of rep of accepting officer. 2. The switchgear specifications shall be complying with the requirements stated in the latatest IEC standard. 3. Cost of foundation and earth work deemed inclusive of the rate. 4. Quoted rate is inclusive of disconnection/re-connection of HT cables from existing VCB. 5. Degree of Ingress protection shall be as per OEM standard."
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm. Complete all as specified and as directed. (Note : CPT SS-5 (03 Nos.), Vikram Enclave ( 03 Nos.) & DHQ-8 (02 Nos.)
Disconnecting, taking out old unserviceable under ground cable of rated voltage 11 kV, nominal cross sectional area of main conductor 120 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 120 sqmm,3 Core. Complete all as specified and as directed.
Supply,fixing,installation & commissioning of 3 phase, 4 wire 11KV/110V, 100/5 A, class 0.5S, 50 HZ CT,PT operted HT Trivector meter suitable to fix with VCB, Complete all as specified and directed. Make- Secure Metres, product- Premier 300HTCT or as aprroved by GE.
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron strip of size 32 x 6mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI medium grade earth lead protection pipe and pre-cast earth pit cover made of RCC (1:1.5:3) type A1 duly reinforced with 8mm dia TMT bar @150 c/c both ways, one lifting handle made of 10mm dia TMT bar embedded in cover slab and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer of 15cm thick complete all as specified and directed. {NOTE:- Each protection pipe and earth lead upto and including 7.50m length is deemed to be included in unit rate of of this item.
Supply and install APFC PANEL WITH MPP-H CAPACITOR AND MCCB AS INCOMER 100 KVAR with 5 steps (50 + 25 + 15 + 5 + 5) with corossion proof powder coating and designed with fully copper conductor, inbuilt micro processor relay for intelligent power factor control, air core reactor for extra safety from inrush cureent (high current) with provision of cable entry from top and bottom , automatic temp control through fans and louvers in panel and double side earthing connection. Complete all as specified and directed.
M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32x6mm galvanised iron strip. Complete all as specified and as directed.
Supply only galvanized steel chain link fence fabric of mesh size 100 mm X 100 mm, made out of 3.15 mm nominal dia of mesh wire complete all as specified and as directed.
Fixing only galvanized steel chain link fence fencing including line wires any mesh, size and type to any type of standards, rails, straining bolts, etc. including provn of binding wire complete all as specified and as directed.
M & L for providing reinforced cement concrete type B-l, 1:2:4 (20 mm graded aggregate) in precast posts, fencing posts, straining or terminal posts, struts etc. for fencing, average sectional area n exc 100 sq. cm, with or without chamfered angles and flat, splayed, rounded or mitred tops as directed and fixed
S & F for framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165. complete all as specified and as directed.
M & L coarse aggregate of dia 40 mm below the surface and leveling upto depth 300 mm with proper ramming and leveling , complete all as directed.
M & L for disconnecting the existing VCB from MES substation at Vikram Enclave and shifting and installation the same at CPT Substation-5 incl all connected accessories Complete all as specified and directed.
M & L for disconnecting the existing VCB/OCB from MES substation at DHQ-8 and handover to MES store for further disposal. Complete all as specified and directed.
M/S MECHANICAL ENGINEERING and ELECTRICAL CONTRACTORS
JOTSHNA ELECTRICALS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .