Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC OLD NO 191 NEW NO 616 M T H ROAD PATTABIRAM CHENNAI 600 072 | CHENNAI | CHENNAI | TAMIL NADU | 600072 | L1 | Accepted-AOC ACCEPTED BEING THE LOWEST | |
| 2 | L2₹8.8 L+₹1.8 L (26.1%)Accepted-AOC 63 2ND MAIN ROAD NGO COLONY ADAMBAKKAM CHENNAI 600 088 | CHENNAI | CHENNAI | TAMIL NADU | 600088 | L2 | Accepted-AOC REJECTED BEING THE L1 ACCEPTED |
Tender Value
₹7.1 L
EMD Value
₹14,300
Closing Date
14 Nov 2022, 6:00 pmClosed
Garrison Engineer (I)(CG) Chennai
Garrison Engineer (I)(CG) Military Engineer services Second Floor CG DHQ No 5(TN) No 4 and 4 A Clive Battery complex Rajaji Salai Chennai 600001
Comprehensive maintenance and carrying out repair/replacement of DG sets and certain other electric work at various locations under GE (I) (CG) Chennai
2022_MES_559933_1
8971/E8
Open Tender
Entertainment/Musical Instruments
Item Rate
365 days
Garrison Engineer (I)(CG) Chennai
All as per tender documents
8 documents required · 8 mandatory
₹500
Garrison Engineer (I)(CG) Chennai
₹14,300
Yes
27 Dec 2022
27 Oct 2022
18 Nov 2022
27 Oct 2022
14 Nov 2022
2 Nov 2022
Amount
Comprehensive maintenance of Diesel engine driven Generating set of 125 KVA capacity installed at THALAKANCHERRY PH-I including attending the under mentioned works to ensure its satisfactory performance:-
(a) Checking the fan belt and adjusting tension (b) Checking the fuel and oil filter (c) Checking the air filter including cleaning and refixing (d) Checking of FIP oil level (e) Tightening the base bolts and nuts (f) Checking the coupling bolts and adjustment ,Checking the self starter and Dynamo
(g) Checking the battery distilled water levels and topping upto the required level. (h) Checking the panels (Manual as well as AMF) attached to the DG set for loose connections, defects if any in the panel Board and replacement of spares all as directed. (j) Checking the anti vibration mounting and adjusting the bolt. (k) Checking the radiator and radiator hose and arresting leak if any (l) Checking the engine oil level and topping upto the required level Note: Cost of spares shall be measured and paid separately under respective items here in after.
Comprehensive maintenance of DG set 100 KVA installed at ICGRA Meenabakkam including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 125 KVA installed at ICGAS ,Meenambakkam including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 160 KVA installed at ICGRA ,Meenambakkam including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 250 KVA installed at ICGRA ,Meenambakkam including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 15 KVA installed at RHQ (Trolley mounted ) including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 200 KVA installed at ICGAS ,Meenambakkam including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 40 KVA installed at RHQ (E) including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 62.5 KVA installed at 152 flats (Ragamalika) ,West moggapair including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 62.5 KVA installed at RHQ€ r including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 10 KVA installed at COMC CG House, Besant Nagar including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 100 KVA installed at CGSD ,Tondiarpet including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 200 KVA installed at CGSD , Royapuram including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 100 KVA installed at DHQ-5 including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Comprehensive maintenance of DG set 20 KVA installed at DHQ-5 including attending the works to ensure its satisfactory performance as mentioned under item No 1.10 and 1.20 here in before complete all as specified and as directed.
Checking the tappet clearance and adjustment of valve including replacement of tappet gasket and old item taken as credit for following DG Sets :-
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Checking the fuel pump timing and adjsuting if required including replacement of timing cover gasket and old item taken as credit for following DG sets:-
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply only fuel filter pre and secondary including rubber gasket and old item taken as credit for following DG sets (Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
DG Set of capacity 10 to 15 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply only lube oil filter including rubber gasket and old item taken as credit for following DG sets(Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply only air filter element including rubber gasket and old item taken as credit for following DG sets (Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply only fan belt of existing size and old item taken as credit for following DG sets(Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply only Radiator hose with clip of existing size and old item taken as credit for following DG sets(Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply and topping up the following items for the DG sets and old item taken as credit (Note: The Cost of replacement of item shall deemed to be included in the maintenance part of the DG set by the contractor)
Engine oil 20 W 40
Distilled water
Battery acid
Coolant
Benzo bolt with washer
Eye bolt for fuel pipe
Jubilee clamp for fuel pipe
Fuel Flexible pipe with brass or GM adaptor
Oil Flexible pipe with brass or GM adaptor
Flexible reinforced pressure pipe 3/8" dia.
Flexible reinforced pressure pipe 1/2" dia.
Flexible reinforced pressure pipe 1" dia.
Draining the engine oil from sump removing the sump cover cleaning the sludge and refixing the same including replacement sump gasket and filling oil and old item taken as credit for the following Gen sets as per manufactures instructions
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Dismantling the fuel pump from the Engine, transporting to the service center and complete servicing and overhauling of the pump including replacement of service kit ,element, delivery valve, plunger, copper washer etc all as required including re-calibration, refixing and testing and old item taken as creditcomplete for the following DG sets :.
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Dismantling the water pump from the Engine and supply and fix new water pump of existing size and testing and old item taken as creditcomplete for the following DG sets :.
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Dismantling the fuel AC pump from the Engine and supply and fix new fuel AC pump of existing size and testing and old item taken as credit complete.
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Draining out the diesel tank, cleaning / washing out the sludge and re-filling with diesel for following DG sets
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Taking down radiator, servicing, cleaning with suitable reagent, washing thoroughly,arresting leakage if any by welding / brazing and refixing the same complete all as specified and as directed. (Note :Necessary coolant and distilled water required will be measured and paid seperately under BOQ item Nos :21.04 and21.02 respectively herein before).
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Removing and replacement of Fuel injector pipe and old item taken as credit for following DG sets
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Material and labour for Heating and varnishing of alternator for following DG sets
DG Set of capacity 10 to 20 KVA
DG Set of capacity 40 KVA
DG Set of capacity 62.5 KVA
DG Set of capacity 100 to 125 KVA
DG Set of capacity 160 KVA to 250 KVA
Supply and replacement of following items for DG set of any capacity as per existing type and model old item taken as credit
Oil pressure gauge.
Battery terminal socket GM including soldering.
Battery terminal leads complete with brass connector
Radiator Cap
Fuel Tank Cap with Lock
Door lock of any type and size complete Set.
Door gasket of any type and size complete set.
Carbon brushes for charging alternator
PT Pump repair Kit
AVR Suitable for 62.5 to 125 KVA Alternators
AVR Suitable for 10 to 40 KVA Alternators
AVR Suitable for 160,200,250 KVA Alternators
Turbo chargers repair kit suitable for DG set 100 to 250 KVA
Supply and replacement of the following items for DG set control panel of any capacity and old item taken as credit
AC Ammeter digital type
AC Volt meter digital type 0 to 500 volt.
Frequency meter
DC Volt meter 0 to 24 V
lgnition switch with key for on, off and run.
DIN Rail for fixing MCB
MCB 6-32 Amps SP
MCCB 125 Amps, 3 Pole, 415 Volt, 25 KA capacity
MCCB 160 Amps, 3 Pole, 415 Volt, 25 KA capacity
Indicator lamp for panel board as per existing size.
No Volt Coil suitable for 3 phase power contactor 160-200 Amps ratings
Dash board pilot lamp.
PVC Control cable 2.5 sqmm copper Multistranded.
PVC Control cable 4 sqmm copper Multistranded.
Toggle Switch 15 Amps
AMF Relay 12 Volt DC
Battery charging alternator 12 Volt
Temperature Gauge with sensor
Electronic governor
RPM Meter
Door hinges
Oil indicator Sensor
AMF Panel relay
Battery charger AC to DC
Contactor 4 pole 200 Amps capacity
Single phase preventor
Speed control sensor
VMP 3P for AMF Panel
Removing dismantling and overhauling of 12 volt stater motor, replacement of armature coil, field coil, bush bearing etc to make the stater motor serviceable and old item taken as credit complete all as specified and as directed .
Removing dismantling and overhauling of 24 volt stater motor, replacement of armature coil, field coil, bush bearing etc to make the stater motor serviceable and old item taken as credit complete all as specified and as directed .
Material and labour for Spray painting of diesel generating set of capacity 10 to 40 KVA with acoustic enclosure with one coat of synthetic enamel paint including writing of SM/MES No on engine and alternator, body colour shall be apple green, black for foundation base frame, red for all guards,Complete all as specified and as directed
Material and labour for Spray painting of diesel generating set of capacity 62.5 to 125 KVA with with acoustic enclosure one coat of synthetic enamel paint including writing of SM/MES No on engine and alternator, body colour shall be apple green, black for foundation base frame, red for all guards Complete all as specified and as directed
Material and labour for Spray painting of diesel generating set of capacity 160 to 250 KVA open type with one coat of synthetic enamel paint including writing of SM/MES No on engine and alternator, body colour shall be apple green, black for foundation base frame, red for all guards Complete all as specified and as directed
Supply and fix lead acid battery of size 12 Volt ,100 AH including charging and removing old unserviceable battery of any description and taken as credit complete all as specified and as directed. Make : Exide/ Amaron/TATA
Supply and fix lead acid battery of size 12 Volt ,180 AH including charging and removing old unserviceable battery of any description and taken as credit complete all as specified and as directed. Make : Exide/ Amaron?TATA
Supply and fix lead acid battery of size 12 Volt ,130 AH including charging and removing old unserviceable battery of any description and taken as credit complete all as specified and as directed. Make : Exide/ Amaron/TATA
Cutting and removing old unserviceable steel sections and sheet metals and supply and fix new Mild steel sheet and steel sections of grade and existing size and shape by gas /arc welding /by nuts,bolts,rivets and old item taken as credit complete all as specified and as directed
Material and labour for PCC 1:3:6 type C2 using 40 mm graded stone aggregate as in foundation and mass concrete complete all as specified and as directed
EVEREST ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .