Loading…
Loading…
Tender Value
₹45.2 L
EMD Value
₹90,500
Closing Date
9 Sept 2026, 6:00 pm
GE 861 EWS
GE 861 EWS
SPECIAL REPAIR OF DAMAGED LT UG CABLE FROM POWER HOUSE No 03 (ALONGWITH GD POST NO 14 TO GD POST NO 18) AT DEPOT AREA UNDER GE 861 EWS
2026_MES_784514_1
GE 861 EWS-38(T)/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 861 EWS
As per NIT
8 documents required · 8 mandatory
₹500
GE 861 EWS
₹90,500
GE 861 EWS
9 Sept 2026
14 Aug 2026
12 Sept 2026
14 Aug 2026
9 Sept 2026
2 Sept 2026
20 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and Laying cable XLPE insulated screened PVC bedded armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area of size 500 sqmm 3.5 core laid in trench/ duct/ along pole/ wall/ road crossing etc and making connection including taking down old unserviceable cable of size 95 sqmm 3.5 core complete all specified and directed by Engineer-in-Charge.
Note:-
(a) The cost of thimbles/ lugs and cable gland and LT insulation tape for insulation etc is incl in quoted rate and no extra payment will be made for it.
(b) The ratye includes passing of cable through road/ wall etc. The quoted rate also includes making the existing surface good by the contractor. | 255 | RM | - | - |
| 2 | Supply and Laying cable XLPE insulated screened PVC bedded armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area of size 400 sqmm 3.5 core laid in trench/ duct/ along pole/ wall/ road crossing etc and making connection including taking down old unserviceable cable of sizes complete all specified and directed by Engineer-in-Charge.
Note:-
(a) The cost of thimbles/ lugs and cable gland and LT insulation tape for insulation etc is incl in quoted rate and no extra payment will be made for it.
(b) The ratye includes passing of cable through road/ wall etc. The quoted rate also includes making the existing surface good by the contractor. | 1,310 | RM | - | - |
| 3 | Material and Labour for instaling out door type sub panel of size 1M X 0.9M X 0.45M with canopy at top 3 phase 4 wire made out of CRCA sheet mounted on PCC platform including suitable bushbar of capacity 150 Amps with minimum 60cm ground clearance with following:-
(a) MCCB 4 pole 415 volts 200 Amps 36kA - 01 No (incoming)
(b) MCCB 4 pole 415 volts 200 Amps 36kA - 02 No (01 x outgoing & 01 x spare)
(c) MCCB 160Amps 4 pole - 01 No (Outgoing)
(d) Voltmeter digital type - 01 No
(e) Ammeter 0-100 Amp - 01 No
(f) Indicator (RYB) - 03 Nos | 1 | Each | - | - |
| 4 | Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including earth continuity GI strip 32mm x 6mm (upto test point from earth plate i.e. 7.5m min) by means of GI bolts/nuts/washersand including protected by 15mm dia GI light grade protection pipe from earth plate to test point, including making of test point. Earth plate shall be surrounded by packed layer of char coal/coke & salt all around bottom and top with alternative layer. 20mm GI mediumt grade pipe for watering (should be 10cm above GL) and including socket, plug, funnel, wire mesh, RCC cover and (including steel for cover) PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil , returning filling and disposal of surplus soil to a distance not exceeding 50m, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and and as directed by Engineer-in-charge.
Note:- (i) Earth continuity of GI strip 32mm x 6mm including protection pipe up to 7.5 mtrs from earth electrode will be included in unit rate, complete all as specified and directed.
(ii) The rate of earth work in soft/loose soil i.e. excavation, returing filling and removal, form work is included in this item and nothing shall be paid extra on this account.
(iii) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner.
(iv) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge. | 2 | Each | - | - |
| 5 | Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, Hard/ dense soil of poles/ stay/ cable etc including getting out in any type of soil complete all as specified and as directed by Engineer-in- charge. | 530 | Cum | - | - |
| 6 | Returning filling in, approved soft/loose soil, including spreading , levelling, watering and well ramming in layers, each layer not exceeding 25cm in any type of soil complete all as specified and as directed by Engineer-in- charge. | 338 | Cum | - | - |
| 7 | Removing excavated material of any type of soil not exceeding 50m and depositing where directedc at a level n exc 1.5 mtr above the starting point . complete all as specified and directed by Engr- in- charge. | 192 | Cum | - | - |
| 8 | Material and Labour sand cushioning, with dry and clean fine river sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and directed by Engr- in- charge.
(Note:- Punned thickness shall be considered for payment purpose) | 137 | Cum | - | - |
| 9 | Supplying and laying in replacement unreinforced precast concrete cable
cover, class LV, type 2, flat size 300mm x 180mm x 40mm complete all as specified and directed by Engr- in- charge. | 8,450 | Each | - | - |
| 10 | Supply and Laying GI tubing 100mm bore Light grade with all fittings such as clamps laid in trenchs or fixed on wall along pole including fixing arrangement , nut bolts, clamps etc.complete for protection of electic cable / strip complete all as specified and as directed by Engineer - in charge. | 36 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
BOQ_879058.xls
BOQ • 4.37 MB
Credit38T.pdf
Additional Documents • 0.20 MB
Tender38T.pdf
Tender Documents • 1.07 MB
Dateamdtcorrigendum.pdf
PDF • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].