Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.6 LAccepted-AOC | L1 | Accepted-AOC Accepted due to lowest | |
| 2 | L2₹19.7 L+₹48,098.35 (2.51%)Rejected-Finance | L2 | Rejected-Finance Rejected due to not lowest | |
| 3 | L3₹21.0 L+₹1.8 L (9.58%)Rejected-Finance 11 GURU NANAK MARKET AMBALA ROAD SAHARANPUR 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | L3 | Rejected-Finance Rejected due to not lowest | |
| 4 | L4₹24.0 L+₹4.8 L (25.1%)Rejected-Finance | L4 | Rejected-Finance Rejected due to not lowest | |
| 5 | L5₹24.1 L+₹4.9 L (25.5%)Rejected-Finance | L5 | Rejected-Finance Rejected due to not lowest |
Tender Value
₹32.1 L
EMD Value
₹64,200
Closing Date
2 Sept 2020, 6:00 pmClosed
COL NK SAH
CWE (AF) LOHEGAON
SPECIAL REPAIR/REPLACEMENT OF EXISTING HT/LT CABLES AND MISCELLANEOUS WORKS OF 9 BRD AT AFS PUNE UNDER GE (AF) LOHEGAON
2020_MES_366120_1
81796/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
GE (AF) LOHEGAON
Please refer tender documents
5 documents required · 5 mandatory
₹500
GE (AF) LOHEGAON
₹64,200
Yes
8 Oct 2020
3 Aug 2020
4 Sept 2020
3 Aug 2020
2 Sept 2020
18 Aug 2020
Amount
Supply laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade earthed system, of size 3 core 185 sqmm.complete all as specified and directed by engr -in- charge.
Supply laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, earthed system of size 3 core 95 sq mm complete all as specified and directed by engr -in- charge.
Supply, laying, jointing, testing and commissioning of LT under ground cable 1100 volts grade XLPE (cross linked polythene ) armoured with galvanised round steel wire or steel strip , electric power cable heavy duty, with multi stranded aluminium conductor, laid in trenches, ducts fix on walls/poles with proper size saddles and clamp laid under roads/path/ drain /colverts or enclosed in GI pipe/ fix complete all as specified , for following size:- (a) 50 Sqm 3.5 core
(b) 35 Sqm 3.5 core
(c) 25 Sqm 4 core
(d) 16 Sqm 4 core
Material and labour for end joint kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed including excavation in any strata, taking out cable, and making disturbed surface after relaying the cable making joints suitable for aluminium conductor of size given complete all as specified , for following size:-. (a) 50 sqmm 3.5 core
(b) 35 sqmm 3.5 core
c) 25 sqmm 4 core
(d) 16 sqmm 4 core
Taking down the old and rusted GI bracket and supply fixing GI bracket (1.50 meter of length) of 40mm dia duly painted with two coat of supper enamelled paint over a coat of red oxide including suitable clamps nuts bolts and washers complete all as specified and directed by engr -in- charge.
Taking down the existing street light fitting and Supply & fix LED street light fitting 72 Watt with LED lamps and driver and made of pressure die-cast aluminium housing IP 65/IP66 road way luminaries (wider beam angle not less than 120 degree, optics with convex lens/pinet lens) with UV stablized polycarbonate cover or toughen glass cover and high power LEDs as light source with LED fittings system Lumen not less than 95 lumen per watt and electronic driver with efficiency 85% with inbuilt protection against lighting, over voltage, short circuit and surge/spike protection upto 5 KV ensuring longer life (THD<10%, PF shall be > 0.95, colour temperature 5700±300K), life expectancy of LEDs minimum 50,000 burning hrs, warranty of complete luminaries fitting shall not less than three years. The fitting shall be tested in NABL accredited LAB and LM 80 test certificate shall be submitted by the original manufacturer. The light fittings shall be fixed on pole with and including 25 mm dia ( or higher size as per manufacturer recommendation), bracket 1.5 m long complete with MS flat iron clamps (clamp shall be 40x5 mm MS flat), nuts and bolts and washers painting the clamps with coat of aluminium paint over a coat of red oxide primer including connection complete all as specified. Make: Jaguar Cat part No: LSRT01S072XC or equivalent in Bajaj/HPL/CG/Shakti/Havells.
Taking down the existing street light fitting and Supply & fix LED street light fitting 90 Watt with LED lamps and driver and made of pressure die-cast aluminium housing IP 65/IP66 road way luminaries (wider beam angle not less than 120 degree, optics with convex lens/pinet lens) with UV stablized polycarbonate cover or toughen glass cover and high power LEDs as light source with LED fittings system Lumen not less than 95 lumen per watt and electronic driver with efficiency 85% with inbuilt protection against lighting, over voltage, short circuit and surge/spike protection upto 5 KV ensuring longer life (THD<10%, PF shall be > 0.95, colour temperature 5700±300K), life expectancy of LEDs minimum 50,000 burning hrs, warranty of complete luminaries fitting shall not less than three years. The fitting shall be tested in NABL accredited LAB and LM 80 test certificate shall be submitted by the original manufacturer. The light fittings shall be fixed on pole with and including 25 mm dia ( or higher size as per manufacturer recommendation), bracket 1.5 m long complete with MS flat iron clamps (clamp shall be 40x5 mm MS flat), nuts and bolts and washers painting the clamps with coat of aluminium paint over a coat of red oxide primer including connection complete all as specified. Make: Jaquar Cat part No: LSRT01S090XC or equivalent in Bajaj/HPL/CG/Shakti/Havells
Taking down the existing street light fitting and Supply & fix LED street light fitting 120 Watt with LED lamps and driver and made of pressure die-cast aluminium housing IP 65/IP66 road way luminaries (wider beam angle not less than 120 degree, optics with convex lens/pinet lens) with UV stablized polycarbonate cover or toughen glass cover and high power LEDs as light source with LED fittings system Lumen not less than 95 lumen per watt and electronic driver with efficiency 85% with inbuilt protection against lighting, over voltage, short circuit and surge/spike protection upto 5 KV ensuring longer life (THD<10%, PF shall be > 0.95, colour temperature 5700±300K), life expectancy of LEDs minimum 50,000 burning hrs, warranty of complete luminaries fitting shall not less than three years. The fitting shall be tested in NABL accredited LAB and LM 80 test certificate shall be submitted by the original manufacturer. The light fittings shall be fixed on pole with and including 25 mm dia ( or higher size as per manufacturer recommendation), bracket 1.5 m long complete with MS flat iron clamps (clamp shall be 40x5 mm MS flat), nuts and bolts and washers painting the clamps with coat of aluminium paint over a coat of red oxide primer including connection complete all as specified. Make: Jaquar Cat part No: LSRT01S0120XC or equivalent in Bajaj/HPL/CG/Shakti/Havells
Taking down the existing flood light fitting and Supply & fix LED flood light fitting 150 Watt with LED lamps and driver and made of pressure die-cast aluminium housing IP 65/IP66 road way luminaries (wider beam angle not less than 120 degree, optics with convex lens/pinet lens) with UV stablized polycarbonate cover or toughen glass cover and high power LEDs as light source with LED fittings system Lumen not less than 95 lumen per watt and electronic driver with efficiency 85% with inbuilt protection against lighting, over voltage, short circuit and surge/spike protection upto 5 KV ensuring longer life (THD<10%, PF shall be > 0.95, colour temperature 5700±300K), life expectancy of LEDs minimum 50,000 burning hrs, warranty of complete luminaries fitting shall not less than three years. The fitting shall be tested in NABL accredited LAB and LM 80 test certificate shall be submitted by the original manufacturer. The light fittings shall be fixed on pole, wall or any building including connection complete all as specified and directed by engr -in- charge. Make: Jaquar Cat part No: LFLD02S150XC or equivalent in Bajaj/HPL/CG/Shakti/Havells
Taking down the existing flood light fitting and Supply & fix LED flood light fitting 300 Watt with LED lamps and driver and made of pressure die-cast aluminium housing IP 65/IP66 road way luminaries (wider beam angle not less than 120 degree, optics with convex lens/pinet lens) with UV stablized polycarbonate cover or toughen glass cover and high power LEDs as light source with LED fittings system Lumen not less than 95 lumen per watt and electronic driver with efficiency 85% with inbuilt protection against lighting, over voltage, short circuit and surge/spike protection upto 5 KV ensuring longer life (THD<10%, PF shall be > 0.95, colour temperature 5700±300K), life expectancy of LEDs minimum 50,000 burning hrs, warranty of complete luminaries fitting shall not less than three years. The fitting shall be tested in NABL accredited LAB and LM 80 test certificate shall be submitted by the original manufacturer. The light fittings shall be fixed on pole, wall or any building including connection complete all as specified. Make: Havells Cat part No JETAIRIS PLUSFLS300WLED757PSYMLT G or equivalent in Bajaj/HPL/CG/Shakti/Jaquar
Taking down old,rusted, unsv Junction box of any size, type and supply & fix new junction box of size not less than 30Cm x20 Cm x 10.5 Cm, made out of Fibre material, shockproof and rustproof, cable entry from bottom. 100% wheather proof, restricted to unauthorised tapping with class FV-0 as per IS : 11731 Part-II or V-0 as per UL-94 and fixing to pole etc using suitable clamps nuts, bolts etc for accommodating and including the following :- a) MCB SP 06 A-01 Nos
S&F in replacement of two run of PVC insulated 2.5 sqmm copper SC conductor cable between cable loops box to fitting drawn through the pole complete.(Two run of cable will be measured as one length)
Taking down Old unserviceable HT/LT UG cable of service connection or distribution system of any size and removing from complete all as specified and directed by engr -in- charge. ( Excavation and earth work will be measured seperately)
S&F in repair numerical type 3 over current earth fault relay , front USB Communication, 3 relay outputs, fault records-10, fixed design, non-draw out 1A/5A. MODEL-IRI-PRO-V2 + Resistor complete all as specified and directed by engr -in- charge. Make : ABB or equivalent
Taking down defective unserviceable GOD from pole and supply and fix gang operated air break switches 12 insulators mounted on MS Channel with operating mechanism worked from ground level suitable 11000 volts, 200 Amps including GI pipe handle clamps bolts, nuts, jumper wire connecting with stranded conductors complete with locking arrangements complete all as specified and directed by engr -in- charge.
Supply and fix in replacement of drop out fuse unit expulsion type for outdoor air break gang operated switch, single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts, washers etc, synthetic bounded fuse carrying tube complete with line taps and suitable for current carrying capacity upto 25-50Amps and connected with suitable size of ACSR conductor as jumper between GOD and DO fuse, with 11 KV HT PVC sleeve, with all fittings/accessories etc, including taking down of only 3 fuses complete all as specified and directed by engr -in- charge.
M&L for cross arms , bracings supports clamps and back plates fabricated from structural steel section including nuts bolts , washers welding , bending cold or hot ,drilling holes for bolts in any shape or size as indicated or directed as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide zinc chrome primer complete all as specified and directed by engr -in- charge.
M& L for replacement of defective current transformer resin coated two core double ratio ( one for protection and other core for metering equipment), class 1.0, ratio 100/50/05 Amp, for 11 KV of Crompton / MEI make complete all as specified and directed by engr -in- charge.
Taking out old unservicable battery back up from HT 11 KV VCB panel, S & Fix new batterry back up 24/30 Volt output voltage with maintenance free sealed lead Acid Battery suitable size complete as per exsisting or equivalent model and testing complete all as specified and directed by engr -in- charge.
Taking down old bus bar chamber, M&L for fabricating, supplying, installing, testing & commisioning of out door type CPRI approved factory made HT 11kV feeder pillar box of size not less than 165 x 80 x 117 cm with top cover 5 cm projected allround made with 3 mm thick CRCA sheet, weather proof, vermin proof with double door, handle with locking arrangement, powder coated with 7 tank process including PVC insulated copper bus bar 3 nos size of 130cm x 5 cm x 0.5cm & mounted on HT 11 kV insulators 9 nos (three nos per bus bar) insulators should be mounted on MS sheet with thickness 3mm made in shape including weather proof painting. The feeder pillar box should be mounted on ms frame made up with MS angle of size 60mm x60x 6 mm duly covered with MS sheet 3 mm thick on all sides about 35cm from the bottom of the FPB & all side removeable type including two coats of syntheic enamel paint over one coat of red oxide primer including necessry excavation earth work in any type of soil, pcc block (1:3:6) of size 120x25x60cm- 2nos embedded in ground etc complete including writing name of feeders on FPB with size of leetters not less than 10 cm complete all as specified and directed by engr -in- charge.
Taking down old poles, supply and fix steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to pole, B-118 final taper cap, bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-31 (09m long) including drilling of holes of required size for fixing of cross arms, panting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally & portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately and marking pole No. with black paint at suitable height complete all as specified and directed by engr in charge.
Taking down old poles, supply and fix steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to pole, B-118 final taper cap, bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-55 (11m long) including drilling of holes of required size for fixing of cross arms, panting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally & portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately and marking pole No. with black paint at suitable height complete all as specified and directed by engr in charge.
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole complete all as specified and directed by engr in charge. (a) soft/loose soil
(b) Hard/dense soil
Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by engr in charge.
Removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as specified and directed by engr in charge.
Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm( for HT cable) and 10 cm (for LT cable) after laying and stretching jointing and testing the cable complete all as specified and directed by engr in charge. [Note : Measuremenet will be done after punning]
Supplying and laying unreinforced precast concrete cable cover, class HV, type 1 flat of size 300mm x180mm x 40mm placed perpendicular of the cable complete all as specified and directed by engr in charge.
Supplying and laying un-reinforced precast concrete cable cover, class LV, type I, flat of size 250mm x 150mm x 40mm placed perpendicular of the cable complete all as specified and directed by engr in charge.
Supply and fix GI Pipe Light grade with all connected accessories of sizes 100 mm dia completed as directed for cable protection complete all as specified and directed by engr in charge.
Supply and fix GI Pipe Light grade with all connected accessories of sizes 40 mm complete all as specified and directed by engr in charge.
M&L for cement concrete (1:4:8) type D2 in foundation filling and mass concrete using 40mm graded stone aggregate for pole/stay foundation complete all as specified and directed by engr in charge.
M&L for cement concrete (1:3:6) type C2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation complete all as specified and directed by engr in charge.
M&L for cement concrete (1:2:4) type B1 in foundation filling and mass concrete and coping of poles incl necessary form work using 20 mm graded stone aggregate complete all as specified and directed by engr in charge.
KSP ENTERPRISES
Rajan Traders
Apurva constructions
SHRI SWAPNAYOG ENTERPRISES
MAYUR ELECTRIC SERVICES
M B Electric and Co
United Sales Corporation
MORESHWAR ELECTRICALS CORPORATION
R. T. Saluji
metro electrical services
Prasur Electricals & Engineering Co.
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .