Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 LAccepted-AOC 344 1 SB GORAI ROAD HILL VIEW PARK NORTH ASANSOL | ASANSOL | WEST BENGAL | L1 | Accepted-AOC Accepted | |
| 2 | L2₹1.4 L+₹763.73 (0.57%)Rejected-Finance 18 SANKAR BOSE ROAD KOLKATA | L2 | Rejected-Finance Rejected | |
| 3 | L3₹1.4 L+₹1,339.37 (0.99%)Rejected-Finance BHAGIRATHIPUR DOMKAL MSD | DOMKAL | MURSHIDABAD | WEST BENGAL | 742101 | L3 | Rejected-Finance Rejected | |
| 4 | L4₹1.4 L+₹2,029.42 (1.50%)Rejected-Finance 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L4 | Rejected-Finance Rejected |
Tender Value
Refer Docs
EMD Value
₹2,800
Closing Date
30 Jan 2025, 6:00 pmClosed
ASSISTANT ENGINEER
O/O ASSISTANT ENGINEER,BMSD,PHE DTE,BANKURA-722102
Dehydration and filtration and allied work for Transformer no. 1 , 2 at CWR site Sub-Station of Marar ws sch. Under Bankura Mechanical Division, P.H.E.Dte
2025_PHED_802372_8
WBPHED/AE/BMSD/NIeT- 10 OF 2024-2025
Open Tender
Electrical Work/ Equipment
Item Rate
10 days
Bankura
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,800
Yes
21 Mar 2025
21 Jan 2025
4 Feb 2025
21 Jan 2025
30 Jan 2025
21 Jan 2025
Amount
Disconnection of all incoming and out going power line from 400 KVA transformer with proper protection by engaging skilled HT related electrician.(2 nos. Transformer)
Drain out the transformer oil from conservour tank to the bottom level as required and storing in an empty cleaned drum as per direction.(including of hiring charges of empty cleaned drum)
Supply of transformer oil in sealed drum as per IS:335(1993). (Make - Powerol/Transol/Approved make)
Supply delivery of Elysian Blue Color Silica Gel dry and desiccant crystals type in the Breather of above transformer as per direction .
Supply of all type of cork gasket and oil seals (Conical) suitable for 400 KVA transformer
Taking out the top cover, inspection cover, H.V. & L.V. bushings with conservator tank and cleaning washing and removing of all damaged cork gaskets, oil seals from the transformers
Re-fitting, fixing the top cover, inspection covers, conservator tank with newly supplied gasket, oil etc as mentioned in sl. No. 6 and tightening of nuts and bolts after cleaning of the surface sludge of cover and coil assembly with the hot oil through filtering machine for 400 KVA transformer as per direction of E.I.C.
Filling the transformer oil through filter machine by old oil and newly supplied oil engaging skilled electrician for increasing IR value including hire charge of 5 KVA DG set. (for 2 nos. transformers)
Making necessary connection of Transformer at HT & LT side after rapping the end connections with new adhesive and insulation tapes and testing and commissioning all complete as per direction of E.I.C.
Charges for Di-Electric Strength Test (BDV Test) by the hiring of Testing Machine & Kit etc as per I.E Rules.
Painting of the above Transformer by the ready mixed primer of approved make, and brand incl. preparation of surface by sand paper, cleaning etc. for receiving two coat of superior quality synthetic anamal paint after applying one coat of red lead chromate primer as per direction of EIC N.B-Painting wil be done by the spray paiting machine
Add: 18% GST
Add: 1% Cess
M S ENTERPRISE (BID ID -6049413)
M/S.S.S.ENTERPRISE (BID ID -6057460)
WEST BENGAL ENGINEERING CO. (BID ID -6050660)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .