Repair/maintenance to street lights. LT panels and summer/ Cooling appliances at Varanasi Cantt.
2021_MES_460202_1
8486/E8
Open Tender
Civil Works
Item Rate
270 days
Banaras
AS Per NIT
8 documents required · 8 mandatory
₹500
Yes
GE (East) Allahabad
₹70,000
Yes
25 Sept 2021
15 Jul 2021
11 Aug 2021
15 Jul 2021
9 Aug 2021
30 Jul 2021
15 Jul 2021 - 22 Jul 2021
Amount
Checking of Air conditioner at site, transporting to workshop in E/M yard, dismantling of Air conditioner and taking down of compressor of air conditioner of window / Split type, 1.5 / 2.0 ton capacity, including cutting & brazing of suction / discharge tubing, complete all as specified and directed.
Sealed compressor unit of capacity of 1.5 Ton for window type air conditioner / split type AC, complete all as specified and directed. MAKE:- ACCEL/ CARRIER / KIRLOSKAR COPLAND / VOLTAS as approved by GE.
Sealed compressor unit of capacity of 2 Ton for window type air conditioner / split type AC, complete all as specified and directed. MAKE:- ACCEL/ CARRIER / KIRLOSKAR COPLAND / VOLTAS as approved by GE.
Gas charging in Air conditioner window / Split AC 1.5 / 2 Ton Capacity with appropriate quantity of refrigerant Gas after fixing new compressor including replacement of filter strainer and testing on completion, complete all as specified and directed.
Detecting the cause of leakage and rectifying the same and ensuring the complete system leak proof and charging of refrigerant gas with appropriate quantity suitable for window type AC / split type AC including testing for smooth functioning, complete all as specified and directed.
Repair / Servicing to window type / split type AC 1.5 ton / 2 ton capacity any make by dismantling the blower motor, condenser fan motor, fan blade, blower drum any type etc., cleaning and servicing of serviceable parts, replacement of wiring kit, knob and unserviceable spare parts etc., replacement of insulation foam 3 mm thick, air filter and re- assembling the serviceable parts etc., and testing for smooth functioning and re-installation at site including depositing unserviceable parts thus retrieved in MES store yard, complete all as specified and directed. NOTE:- Spare parts required shall be measured and paid seperatly as 'Supply and fix' under respective items of this Schedule.
Supply and fix following spare parts of window type AC / split type AC, complete all as specified and directed :-
Running capacitor 36 / 45 / 50 + 6mF ± 5%, 440 Volt AC. MAKE:- Usha / Asian / Crompton greaves / Sriram / Havells / Epicos / Totaline as approved by GE.
Relay for window AC of capacity 1.5 Ton / 2 Ton
Thermostate for AC
Blower motor, single phase, 230Volt AC for window type air condtioner. MAKE:- KIRLOSKAR / JYOTI / BEACON as approved by GE.
Blower fan blade made of plastic for window or split air conditioner.
Condensor fan blade made of plastic for window or split air conditioner.
Indoor unit complete for 1.5 ton split type air conditioner.
Condensor motor 0.1(1/10) hp, single phase, 230 V, AC electric supply for outdoor unit of split type air conditioner any capacity
Condensor motor 0.05(1/20) hp, single phase, 230 V, AC electric supply for outdoor unit of split type air conditioner any capacity
Outdoor unit complete including enegy efficient rotary compressor, compete, copper white for 1.5 Ton split type AC.
Programmable Logic Controller (PLC) unit for split type air conditioner, same make and capacity as existing MAKE:- CARRIER / VOLTAS / ACCEL / LG / SAMSUNG / BLUE STAR as approved by GE.
Contactor, single phase, 230V of suitable capacity for Split type AC of 1.5 Ton / 2 Ton capacity including coil. MAKE:- CARRIER / VOLTAS / ACCEL as approved by GE.
Sub main wiring complete with 2 runs of 6 sq.mm PVC insulated and unsheathed 1100V grade multistranded FRLS grade copper conductor cable drawn through and including provision of rigid PVC conduit 25mm dia including conduit accessories and connecting terminal ends to DB's including providing 1 run of 6 sq.mm PVC insulated unsheathed multistranded FRLS grade copper cable as earth continuity conductor and connecting to common earth dolly, complete all as specified and directed. NOTE:- (i) Two runs of 6 sq.mm copper conductor, one run of 6 sq.mm copper earth continuity conductor and one run of PVC conduit and conduit accessories shall be measured as one unit length. (ii) Extra length of cable / wire required for connection to MCBs shall not be measured and the rate quoted per unit shall deemed to be inclusive of the same accordingly.
Sheet metal enclosure with three pin earth plug and socket complete with MCB 20 Amp, Single Pole 240 Volt 'C' curve and 10kA breaking capacity including taking down existing unserviceable sheet metal enclosure, complete all as specified and directed.
Checking of water cooler, any capacity, at site, including transporting to workshop in E/M yard, dismantling of water cooler and taking down of compressor any capacity and type, including cutting and brazing of suction / discharge tubing, complete all as specified and directed.
Sealed compressor unit of water cooler 60 / 120 litre cooling capacity and make suitable for existing water cooler, complete all as specified and directed. MAKE:- Copeland, Usha , Tecum sheh, Voltas, Blue Star, Accel, Hitachi, LG.
Sealed compressor unit of water cooler 40 / 80 litre cooling capacity and make suitable for existing water cooler, complete all as specified and directed. MAKE:- Copeland, Usha , Tecum sheh, Voltas, Blue Star, Accel, Hitachi, LG.
Gas charging in water cooler with appropriate quantity of refrigerant gas after fixing new compressor including replacement of filter strainer and testing on completion, complete all as specified and directed.
Labour only for detecting and rectification of leakage in existing water coolers of any capacity and ensuring the complete system leak proof and charging of refrigerant gas with appropriate quantity of refrigerant suitable for water cooler including replacement of fitter strainer and testing on completion, complete all as specified and directed.
Labour only for disconnecting of existing electric connection and water connection of water cooler, opening the condensor fan motor blade, electrical accessories and spare parts of system, carefully servicing of serviceable parts, replacement of un-serviceable parts, oiling of fan motor etc., reassembling all spare parts including rewiring of internal connection of water cooler, re-connecting electric and water connection, testing and commissioning, complete all as specified and directed. NOTE:- (i) Warn out or unserviceable spare parts to be replaced shall be measured and paid separately as 'Supply and fix' under respective items of this Schedule. (ii) Replacement of nut and bolts, washers etc., shall deemed to be included in unit rate quoted. (iii) Minor repair of chassis by brazing / welding work shall also deemed to be included in unit rate quoted.
Supply and fix following spare parts for water coolers of any capacity, complete all as specified and directed :-
Running capacitor 25 / 36 mF ± 5%, 440 Volt AC supply. MAKE:- Usha / Asian / Crompton Greaves / Sriram / Havells / Epicos/ Totaline as approved by GE.
Running capacitor 20 / 10 mF ± 5%, 440 Volt AC supply. MAKE:- Usha / Asian / Crompton Greaves / Sriram / Havells / Epicos / Totaline as approved by GE.
Starting capacitor 60 / 70 mF. MAKE:- Usha / Asian / Crompton Greaves / Sriram / Havells / Epicos / Totaline as approved by GE.
Starting capacitor 40 / 50 mF. MAKE:- Usha / Asian / Crompton Greaves / Sriram / Havells / Epicos / Totaline as approved by GE.
Starting capacitor 80 mF. MAKE:- Usha / Asian / Crompton Greaves / Sriram / Havells / Epicos / Totaline as approved by GE.
Start Relay for water cooler, any capacity.
Over load protector, make and capacity shall be same as that of existing
Thermostat of capacity as exisitng at site.
Condensor motor 0.02857 (1/35) hp, single phase, 230V.
Condensor motor 0.04167 (1/24) hp, single phase, 230V.
Condensing coil
Plastic drain hose pipe, of length not exceeding 1.5 metre.
Push cock / lift cock, brass, chromium plated.
Capillary Tube, of length not exceeding 0.60 metre.
Float Valve 12.70 mm (1/2") including assembly brass made
Detection and rectification of leakage of storage tank of water cooler by brazing, soldering / welding as required at site or at work shop and repalcement of unserveciable spare parts such as Nipple adaptor, Push cock, Float valve and Bush, nut, bolt, washer, rubber / plasting packing for smooth functioning and testing for leak proof, complete all as specified and directed. NOTE:- The unit rate quoted shall deemed to be include the cost of replacement of spares as mentioned above and no extra claim what-so-ever shall be admissible at a later stage.
Preparation of old surfaces of water cooler and applying one coat of synthetic enamel paint of approved tint using spray machine, complete all as specified and directed.
Replacement of drain tray with PVC pipe for water cooler, electroplating (chromium plating) of drain tray after repair by denting including refixing back in original position, complete all as specified and directed.
Repair / maintenance of refrigerator, cleaning of indoor panel, servicing of serviceable parts, replacement of worn out parts, testing for smooth functioning of refrigerator, re-assembling all spare parts including rewiring of internal connection of fridge, testing and commissioning, complete all as specified and directed. NOTE:- (a) Worn out or unserviceable spare parts to be replaced shall be measured and paid separately as 'Supply and fix' under respective item of BoQ. (b) Nut / bolt and washers etc., shall also deemed to be included in the unit rate quoted. (c) Minor repair of chassis by brazing / welding work shall also deemed to be included in unit rate quoted.
Replacement of unserviceable compressor from refrigerator any capacity by cutting and brazing of suction / discharge tubing including charging of required quantity of refrigerant gas complete including testing and commissioning for smooth functioning, complete all as specified and directed. NOTE:- (i) Compressor and spare parts shall be measured and paid separately under respective items of BoQ as 'Supply and fix'. (ii) Replacement of nut / bolts and washers shall also deemed to be included in unit rate quoted. (iii) Minor repair of chassis by brazing / welding work shall also deemed to be included in unit rate quoted.
Detecting and rectifying leakage and ensuring the complete system leak proof and charging of refrigerant gas with appropriate quantity suitable for refrigerator including testing for smooth functioning, complete all as specified and directed.
Sealed compressor unit of refrigerator, 160 to 240 litre cooling capacity, complete all as specified and directed.
Sealed compressor unit of refrigerator, 280 to 340 litre cooling capacity, complete all as specified and directed.
Supply and fix following spare parts of refrigerators, suitable for existing size and make at site, complete all as specified and directed :-
Relay
Over load protector
Thermostate
Cooling coil
Condensing coil
Bulb Holder
Bulb pin type / screw type, 15 Watt
Door switch
Chilled tray
Vegetable tray
Bottle supporter
Capillary Tubing not exceeding 0.36metre
Opening of the automatic voltage stabilizer of Capacity 5 KVA / 4 KVA for repair, detection of fault and its repair, cleaning of serviceable parts, replacement of unserviceable or worn out parts, soldering of terminal connection and testing after repair, painting with one coat of synthetic enamel paint externally, complete all as specified and directed.
Opening of the automatic voltage stabilizer of Capacity 2 KVA / 3 KVA for repair, detection of fault and its repair, cleaning of serviceable parts, replacement of unserviceable or worn out parts, soldering of terminal connection and testing after repair, painting with one coat of synthetic enamel paint externally, complete all as specified and directed.
Opening of the automatic voltage stabilizer of Capacity 1 KVA, single phase, for repair, detection of fault and its repair, cleaning of serviceable parts, replacement of unserviceable or worn out parts, soldering of terminal connection and testing after repair, painting with one coat of synthetic enamel paint externally, complete all as specified and directed. NOTE:- (for item No. 26 to 28 of BoQ, here-in-before) :- (a) Worn out / unserviceable spare parts to be replaced with new spare parts shall be measure and paid seperately as 'Supply and fix' under respective items of BoQ (b) Provision of flexible 3 core sheathed cable of size 40/.0076, 23/.0076, 70/.0076, as the case may be, to be provided for at least 1.5 metre shall deemed included in the unit rate quoted.
Supply and fix following spare parts suitable for voltage stabilizer of any make and any capacity, complete all as specified and directed :-
Volt meter (0-300 volts).
Control relay.
IC controlled circuit for 5 KVA / 4 KVA.
IC controlled circuit for 3 KVA.
Control transformer rating input 170 to 250 Volt and output 230 Volt.
Low / high voltage cut-off and TDR system.
Main transformer for 5 KVA / 4 KVA.
Main transformer for 3 KVA
Main transformer 1 KVA
Opening of the Desert Cooler of any capacity and make, dismantling of complete items and its repair, cleaning of serviceable parts, replacement of unserviceable or worn out parts, opening of Fan motor from their brackets, scraping out of old paint of complete body (internally & externally) of Desert Coolers including making good, smoothen the surface and applying spray painting with one coat of synthetic enamel paint for external surfaces / internal surfaces, replacement of wooden wool pad - 3 Nos and re-fixing of Fan Motor and Pump, replacement of internal wiring and rotary switch with pump and Fan motor connection and testing after repair, complete. NOTE:- (i) Overhauling / Oiling of fan motor, Vertical pump replacement, Nuts, bolts washers / elbow, if required shall be deemed to be included in unit rate quoted. (ii) Cost of replacement of grass pad shall deemed to be included in quoted rate. (iii) Unserviceable spare parts to be replaced shall be measured and paid separately as 'Supply and fix' under respective item of this BoQ. (iv) Minor repair of chassisby brazing / welding work shall also deemed to be included in unit rate quoted. (v) Provision of PVC Sheathed cable of 23/.0076 up to 1.5 meter in replacement if required shall be deemed to be included in the unit rate quoted.
Supply and fix following spare parts suitable for Desert Coolers of existing make or existing capacity, complete all as specified and directed :-
Fan motor of 0.1667 (1/6) hp to 0.10 (1/10) hp, 230V, AC electric of same capacity and same make
Blade for kit Fan.
MS Bracket for kit Fan Motor
Submersible Pump set suitable for desert coolers of fractional horse powers MAKE:- CG/Bajaj/Havells/Vansal/Summer cool / Zolta (Khaitan).
Rotory Switch
Piano type Switch, 5 Amp 230 Volt AC
Front Directional Grill
PVC flexible pipe 10 mm dia
Side panel made out of PGI Sheet 1 mm thick of size not less than 0.5 metre width and 0.7metre height.
Storage tank made out of PGI Sheet 1 mm thick of size not less than 0.7 m X 0.7m and height 0.2metre
Rewinding of fan motor Kit fan, 450 mm sweep with super enameled copper wire (gauge / weight of copper coils shall be same as per existing dismantled fans), including varnishing complete all as specified and directed. NOTE :- (a) Removing the defective fan and rectifying after repair including removing of defective parts, burnt winding carefully, cleaning and re-assembling the fan after repair / servicing including oiling, greasing, washer, lock bolts, connector etc. depositing the unserviceable fans to store yard of AGE E&M and testing complete.
Metal bush bearing for ceiling fan / exhaust fan / cabinet / pedestal fan of any make / sweep, complete all as specified and directed.
Capacitor 3.15 / 4 mF + 5% 440V AC. MAKE:- Usha/ Asian/ Crompton Greaves/ Sriram/ Havells/ Epicos/ Totaline as approved by GE
PVC sheathed white colour three core copper flexible cable of size 23/.0076, complete all as specified and directed
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for Ceiling Fan of 1200 mm sweep size of fans of any make, complete all as specified and directed.
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for Ceiling Fan of 1400 mm sweep size of fans of any make, complete all as specified and directed.
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for exhaust Fan of 450 mm sweep size of fans of any make, complete all as specified and directed.
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for exhaust Fan of 380 / 400 mm sweep size of fans of any make, complete all as specified and directed.
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for exhaust Fan of 300 mm sweep size of fans of any make, complete all as specified and directed.
Rewinding of fan, complete with super enameled copper wire (gauge / weight of copper coil shall be same as per dismantled fans), including quick varnishing for exhaust Fan of 225 / 230 mm sweep size of fans of any make, complete all as specified and directed. NOTE :- (for Sl. item No. 36 to 41 of BoQ, here-in-before) : (i) Collection of fan from AGE E&M office under contractor own arrangement for repair of the same, removing defective parts, burnt winding carefully, cleaning and re-assembling the fan after repair including oiling, greasing, washer, lock bolts, connector etc.replacement of worn out / unserveciaval parts, if required shall deemed to be included in unit rate quoted (ii) Depositing the the thus repaired / serviced fans in the storeyard of AGE E&M and testing complete (iii) Spare parts shall be measured and paid seperately under respective items of this schedule as 'Supply and fix'.
Ball bearing size No. 6201 for ceiling / exhaust fan
Ball bearing size No. 6202 for ceiling / exhaust fan
Ball bearing size No. 6203 for ceiling / exhaust fan
Capacitor 2.5 mF rating. MAKE:- Usha/ Asian/ Crompton Greaves/ Sriram/ Havells/ Epicos/ Totaline as approved by GE.
Rotor shaft for Ceiling / exhaust fan of any make / sweep
Twisted two core copper flexible cable of size 23/.0076 from connector to the ceiling rose, fixed in repair
Taking down from site, transporting to workshop and Over hauling only ceiling fan of any sweep / make as existing at site i.e., opening of fan and cleaning ball bearing, filling grease / oil and changing of nut, screw, check nuts and bolts as required including cleaning of body, blades, down rods, canopies etc., and re-assembling including refixing at site, complete all as specified and directed. NOTE:- (i) Worn out or unserviceable spare parts to be replaced shall be measured and paid separately as 'Supply and fix' under respective items of BoQ. (ii) Replacement of nut, bolts and washers shall deemed to be included in unit rate quoted by contractor. (iii) Minor repair of chassis by brazing/ welding work shall also deemed to be included in unit rate quoted.
Spray painting of fan of any size with two coat of synthetic enamel paint (white) after cleaning of body, blades, down rods from dust, dirt, oil, grease etc. including re-writing MES fan Nos. on the body of fan, using black paint, complete all as specified and directed.
Supply only canopy for ceiling fan suitable for any sweep / make as required, complete all as specified and directed.
Rubber reel for ceiling fans, complete all as specified and directed.
Clamp for down rod complete with rubber reel and nut / bolts for ceiling fans, complete all as specified and directed.
Fan blade aluminium, painted with white colour and suitable for 1200 / 1400 mm sweep ceiling fan, complete all as specified and directed.
Fan hook made out of 40mmx6mm MS flat iron suitable for hanging of ceiling with proper size of nut, bolt and washers to be fixed in pipe of 40 mm bore dia, fixed in repairs, complete all as specified and directed.
Supply only best quality bearing grease in 1Kg Packing, complete all as specified and directed. MAKE:- SKF or techno-commercial equivalent make as approved by GE
Taking out old rusted / unserviceable louver shutter of exhaust fan and supply and fix rust proof heavy duty aluminium frame louver shutter suitable for 250mm / 300mm sweep exhaust fan, complete all as specified and directed.
Taking out old rusted / unserviceable louver shutter of exhaust fan and supply and fix rust proof heavy duty aluminium frame louver shutter suitable for 380mm / 400mm / 450mm sweep exhaust fan, complete all as specified and directed.
Solar battery charger of capicity 150W, max voltage 18.0V and max current 8.35A with short circuit current 8.70A and open circuit voltage 22.5V and system voltage 1000V with 10Sqmm copper conductor battery charging lead with brass clamp, complete all as specified and directed. MAKE:- Model No. JP-12X150 of Jakson or techno-commercially equivalent make as approved by GE.
GI tubing 40mm bore medium grade in required length and grouting in wall for hanging of ceiling fan, fixed in repair, including making good of disturbed surface of walls to match with existing surface, complete all as specified and directed.
Mild steel Anchor bolt / fasterner pin type 8mm dia, 100mm long for fixing of exhaust fan / geysers etc., complete all as specified and directed.
Repair / maintenace and serving to UV / Kent RO water purifier by replacing filter elements, connector pipes, solonoid valve, delivery valve and testing, complete all as specified and directed. NOTE:- Spare parts shall be measured and paid separately.
Kent RO pre carbon filter, complete all as specified and directed.
Kent UF membrane 8" size, complete all as specified and directed.
Kent RO inline carbon filter 8" size, complete all as specified and directed.
Kent RO diaphragm pump,150 DP, complete all as specified and directed.
Kent UV assembly with UV lamp of suitable capacity, complete all as specified and directed.
Kent SMPS 2.5Amp, 24 DC with wires, complete all as specified and directed.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5metre in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, tubular poles or laying of pipes, or for removal / laying of cables etc., not exceeding 10 sq m on plan and not exceeding 1.5 m in depth and getting out in soft / loose soil including dressing / trimming sides and levelling / grading and ramming of bottoms of excavation, complete all as specified and directed.
Returning, filling in, in soils, including spreading, levelling, watering and well ramming in layers not exceeding 25cm., complete all as specified and directed.
Removing surplus excavated soils to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.50m above the starting point, complete all as specified and directed.
Spreading of natural, clean and dry river sand in trenches for cable protection, complete all as specified and directed. NOTE:- Punned thickness shall only be measured and paid.
Supply and lay burnt clay fly ash bricks class 'B', old size, designation 75, size 230mm x 115mm x 75mm, laid in trenches for cable protection with length of brick equal to width of trench, complete all as specified and directed.
Steel tubing, light grade, ISI marked, galvanised including short lengths, laid in trenches / fixed to walls / ceilings or laid in floors / laid in ducts / laid under road crossing for cables, complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps, plugs and unions etc.,), 50mm bore of pipe, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable GI pipe shall be measured and paid separately under respective items of this Schedule.
Steel tubing, light grade, ISI marked, galvanised including short lengths, laid in trenches / fixed to walls / ceilings or laid in floors / laid in ducts / laid under road crossing for cables, complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps, plugs and unions etc.,), 32mm bore of pipe, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable GI pipe shall be measured and paid separately under respective items of this Schedule.
XLPE insulated, screened, PVC bedded, galvansied steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 V, grade, ISI marked as per IS-7098, cross-sectional area 16 sq.mm, 4 core, laid in trenches / on poles / walls including provision of suitable hardware accessories, connecting up, testing on completion and commissioning including taking down existing unserviceable cable of any type and depositing the retrieved materials in MES storeyard Varanasi, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable cable of any type, sand cushioning to cables and bricks as cable protection shall be measured and paid separately under respective items of this Schedule.
XLPE insulated, screened, PVC bedded, galvansied steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 V, grade, ISI marked as per IS-7098, cross-sectional area 10 sq.mm, 4 core, laid in trenches / on poles / walls including provision of suitable hardware accessories, connecting up, testing on completion and commissioning including taking down existing unserviceable cable of any type and depositing the retrieved materials in MES storeyard Varanasi, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable cable of any type, sand cushioning to cables and bricks as cable protection shall be measured and paid separately under respective items of this Schedule.
XLPE insulated, screened, PVC bedded, galvansied steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 V, grade, ISI marked as per IS-7098, cross-sectional area 10 sq.mm, 2 core, laid in trenches / on poles / walls including provision of suitable hardware accessories, connecting up, testing on completion and commissioning including taking down existing unserviceable cable of any type and depositing the retrieved materials in MES storeyard Varanasi, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable cable of any type, sand cushioning to cables and bricks as cable protection shall be measured and paid separately under respective items of this Schedule.
XLPE insulated, screened, PVC bedded, galvansied steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 V, grade, ISI marked as per IS-7098, cross-sectional area 6 sq.mm, 2 core, laid in trenches / on poles / walls including provision of suitable hardware accessories, connecting up, testing on completion and commissioning including taking down existing unserviceable cable of any type and depositing the retrieved materials in MES storeyard Varanasi, complete all as specified and directed. NOTE:- Necessary excavation and earthwork for taking down old and unserviceable cable of any type, sand cushioning to cables and bricks as cable protection shall be measured and paid separately under respective items of this Schedule.
Restringing of existing overhead line ACSR conductor and earthwire of any size including opening from insulators, tightening upto permissiable sag, binding properly and refixing of cradles with safety precaution, complete all as specified and directed. NOTE:- Each row / span of ACSR conductor and earth wire shall be measured separately
Bore hole for passing cable through / insertion in 80 / 50mm dia GI pipe under PCC road / taxi track / runway / hard standing upto the depth of 450mm to 1200 mm, complete all as specified and directed. NOTE :- (i) Cost of equipments, tools & plants, material required for boring shall deemed to be included in unit rate quoted. (ii) GI pipe 80/50 mm dia shall be measured and paid separetely.
Supply and erection of steel tubular pole, swaged type 410-SP 31(9.0m long) as per IS:2713 (part I to III) 1980 complete with cast iron base plate, pole cap, mild steel bolt, nuts and screws including dismantling of exsiting pole, complete all as specified and directed. The quoted rate shall deemed to be inclusive for the provision of following works:- (a) Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.57 m deep for pole foundation and getting out in soft / loose soil, RFR in the excavated soil after fixing the pole in foundation, ramming earth around in layer not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 m. (b) PCC 1:4:8 type D2 (using 40mm graded crushed stone aggregate) in foundation 900mm x 600mm cross section and planting depth 1.5 m for concrete encasing the pole upto GL.
Sl. Item No. 81.00 Contd… (c) PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) for plinth block / collar above GL 500mm high and 450mm dia. (d) Painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminium paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5m above plinth block. (e) Writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of approved shade not exceeding 5cm height including numbering of pole. NOTE:- Manufacture's test certificate shall be produced before execution work. MAKE:- National tuubing Co. Kanpur or BCW Kanpur or M/s Sohan Lal & Sons or United Engineers, Kanpur.
Under water luminiarie 7 watt LED light for connecting under water lighting purpose of fountain, Corrosion resistant, Nickel plated brass housing, water proof with flanges of top coloured glass with rubber gasket on both sides , mounted in brass frame with all accessiories and LED, fixed in repairs, complete all as specified and directed.. MAKE:- Model : LTUW7x1HPLED of C&S or Model No. CGDMX512 of Crompton or techno-commerically equivalent model in Havells.
Taking down existing non functional security / street light fittings from pole / wall / pipe of any type / capacity for repair and refixing in position after replacement of spares / accessories such as ballast, starters, ignitors, lamps etc., including making electric connection with PVC insulated aluminium conductor service cable 4 sq.mm 2 core and testing, complete all as specified and directed. NOTE:- Spare parts to be replaced shall be measured & paid separately under respective items of this Schedule.
Taking down existing high mast pole light any type and wattage for repair including replacement of unserviceble spares / accessories such as ballast, starters, ignitors, lamps etc., including making electric connection, erecting in the same position after repair and testing, complete all as specified and directed. NOTE:- Spare parts to be replaced shall be measured & paid separately under respective items of this Schedule.
CFL, 4-pin, 36 watt in building security light fitting, complete all as specified and directed. MAKE:- - Cat No. LTAF001 of C&S or Cat No. LHBF08104028 of Havells or Cat No. 36W CFL 4P 6500/2700K of Crompton
HPSV choke 400 watt, 240 volt AC 50 Hz copper wound, complete all as specified and directed. MAKE:- Cat No. HDBI 40S/MH of Crompton or Cat No. LTAS004 of C&S or Cat No. LHBG08140036 of Havells
HPSV choke 250 watts, 240 V, AC 50 Hz copper wound, complete all as specified and directed. MAKE:- Cat No. HDB25S/MH of Crompton or Cat No. LTAS002 of C&S or Cat No. LHBW00125036 of Havells
HPSV choke 150 watts, 240 V, AC 50 Hz copper wound complete all as specified and directed. MAKE:- Cat No. HDBI15 S/MH of Crompton or Cat No. LTAS003 of C&S or Cat No. LHBW20115036 of Havells
HPSV choke 70 watts, 240 V, AC 50 Hz copper wound, complete all as specified and directed. MAKE:- Cat No. HDBI7S/MH of Crompton or Cat No. LTAS001 of C&S or Cat No. LHBW07170036 of Havells
HPSV tubular lamp 400 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - SV400W Tubular of Crompton or Cat No. LTAS002 of C&S or Cat No. LHSS22040099 of Havells
HPSV tubular lamp 250 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - SV250W Tubular of Crompton or Cat No. LHSS22025099 of Havells
HPSV tubular lamp 150 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - SV150W Tubular of Crompton or Cat No. LHSS22015099 of Havells
HPSV tubular lamp 70 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - SV70W Tubular of Crompton or Cat No. LHSS16107099 of Havells
Ignitor for 70,150, 250 & 400 watt fitting, fixed in repairs, complete all as specified and directed. MAKE:- Cat No. IGN112S/MH of Crompton or Cat No. LHGEAJENNA1999 of Havells or Cat No. LTAG001 TO 005 of C&S
HPMH lamp 400 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - MH400W SE Tubular of Crompton or Cat No. LHSM12140699 of Havells
HPMH lamp 250 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - MH400W SE Tubular of Crompton or Cat No. LHSM12140699 of Havells
Supply and fix HPMH lamp 150 watts, 240 V, AC 50 Hz, complete all as specified and directed. MAKE:- Product code - MH400W SE Tubular of Crompton or Cat No. LHSM12140699 of Havells
T-5 LED tube rod 2' long 24 watt, complete all as specified and directed. MAKE:- Crompton / Havells / Wipro
LED tube rod 20/22 watt, complete all as specified and directed. MAKE:- Crompton / Havells / Wipro
GI bracket for security light and street light fittings fabricated with GI tubing 40 mm dia 'medium grade', 1.2 m long including bending to angle of 120 degree and fixed in repairs, complete all as specified and directed.
Mild steel clamp fabricated with mild steel flat iron 50mm x 6 mm including nuts and bolts with washers suitable for fixing of GI bracket on PCC/ steel poles, fixed in repairs, complete all as specified and directed.
LED street light luminaires 24/25 watt with pressure die-cast aluminium housing with heat resistant toughned glass and IP65 protection, complete including connection on pole or building, including taking down of old / unserviceble street light fitting of any type and size, complete all as specified and directed. MAKE:- Cat No. LSTO-25-CDL of CG or Cat No. LHETAXU7UN6W024 of Havells or Cat No. LTESS10X2.5HPLED/LS of C&S
LED street light luminaires 45 watt with pressure die-cast aluminium housing with heat resistant toughned glass and IP66 protection, complete including connection on pole or building, including taking down of old / unserviceble street light fitting of any type and size, complete all as specified and directed. MAKE:- Cat No. LSTO-45-CDL of Crompton or Cat No. LHETAXU7PN6J045 of Havells or Cat No. LTESS18X2.5HPLED of C&S
LED street light luminaires 90 watt with pressure aluminium die-cast powder coating housing and frame with heat resistant, high efficiency, toughned glass with EPDM gasket for IP66 protection, complete assembly with LED, driver and accessories pre-wiredup to terminal block, including connection on pole or building, including taking down of old / unserviceble street light fitting, complete all as specified and directed. MAKE:- Cat No. LSTO-90-CDL of Crompton or Cat No. LHETAXU7IN6J090 of Havells or Cat No. LTESS40X2.5HPLED/LS of C&S
LED integral flood light luminaires 90 watt aluminium die-cast powder coating housing and frame with long life LEDs, loop-in-loop-out connector, 10 A G.F.P for each wiring heat resistant, high efficiency toughned glass with EPDM gasket for IP65 protection, complete assembly with LED, driver and accessories pre-wired up to terminal block, including connection on pole or building, including taking down of old / unserviceble flood light luminaire, complete all as specified and directed. MAKE:- Cat No. LR18-971-XX-57-XX of Wipro or Cat No. LTESS10X2.5HPLED of C&S
LED integral flood light luminaires 120 watt in powder coated with aluminium die-cast housing and frame,high efficiency,long life LEDs,loop in loop out connector,10 A G.F.P for each wiring heat resistant toughned lear glass cover and IP 66 protection complete assembly with LEDs, driver and accessaries pre-wired up to terminal block in control gear compartment, including connection on pole or building, including taking down of old / unserviceble street light fitting, complete all as specified and directed. MAKE:- Cat No. LR18-971-XX-57-XX of Wipro or Cat No. LTEFI120WHPLED of C&S or Cat No. LHEPCZU7P46J120 of Havells
LED integral flood light luminaires 150 watt in powder coated with aluminium die-cast housing and frame, high efficiency, long life LEDs,loop in loop out connector,10 A G.F.P for each wiring heat resistant toughned lear glass cover and IP 66 protection complete assembly with LEDs, driver and accessaries pre-wired up to terminal block in control gear compartment. including connection on pole or building, including taking down of old / unserviceble HPSV / MH street light fitting any type and any wattage, complete all as specified and directed. MAKE:- Cat No. LR18-971-XX-57-XX of Wipro or Cat No. LHEPCZU7P46J150 of Havells or Cat No.LTESS10X2.5HPLED of C&S
Shackle type porcelain, vitreous, white, brown or green insulator inluding one galvanised strip 31mm x 3mm, 12 mm dia, galvanised iron nuts, bolts and washers and 75 mm height & 90 mm dia suitable for 1100 V grade, including taking down old / unserviceble insulators, complete all as specified and directed. MAKE:- Jaipuria Brothers or techno-commercially equivalent in BHEL or Jayshree Insulators
Hot press moulded PVC junction box of size 230mm x 170 mm x105 mm with 200A TPN Aluminium bus bars mounted / fixed on porcelain insulator shock and rust proof, cable entry form bottom and other sides, 100% weatherproof, with pole mounting arrangement temper-proof, fire retardant class FV-0 as per IS 11731 part -II or V-O as per UL-94 including flat iron clamp of size 25mm x 3 mm fixed in repairs, complete all as specified and directed. MAKE:- Sintex / Naithani plastic works / Supreme industries
Electronic street light control timer switch, operating automatic / mannually with sheet metal encloser box wall/pole mounting type including heavy duty clamp made out of mild steel sheet 3.15 mm thick duly painted with two coat of synthetic enamelled paint over a coat of red oxide primer, of capacity 12 KW, 3 phase, 415 / 230 V, 50 Hz, ISI marked suitable to accommodate the following with and including their provision, including taking down existing feeder box any size :- (a) Three phase control switch MCB TPN 63A, 10 kA breaking capacity \ - 01 No (Incoming) (b) Auto controle switch (c) Heavy duty 3 Phase Contactor ML-3 with axulllary contact - 01 No (d) sun light senser complete to operate before sun rise & after sun set (e) Electronic timer -01 No. MAKE:- Havells / L&T / Legrand
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, un-armoured, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 4sq.mm, including taking down old / unserviceble service wire, complete all as specified and directed. MAKE:- Finolex / Plaza / Havells
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, un-armoured, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 6sq.mm, including taking down old / unserviceble service wire, complete all as specified and directed. MAKE:- Finolex / Plaza / Havells
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor, un-armoured, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sq.mm, including taking down old / unserviceble service wire, complete all as specified and directed. MAKE:- Finolex / Plaza / Havells
PVC insulated, FR grade, PVC round sheathed copper conductor multi core round (flexible) industrial cable 1100 V grade with bright annealed electrolytic bare copper conductor, size 16 sq.mm 4 core confirming to IS-694-1990, including taking down old / unserviceble cable any type from semi high / high mast poles of any height and connecting, complete all as specified and directed.
PVC insulated, FR grade, PVC round sheathed copper conductor multi core round (flexible) industrial cable 1100 V grade with bright annealed electrolytic bare copper conductor, size 10 sq.mm 4 core confirming to IS-694-1990, including taking down old / unserviceble cable any type from semi high / high mast poles of any height and connecting, complete all as specified and directed.
Energy saving LED garden light fitting, decorative, bollard, of capacity 9 watt with opal diffuser and aluminium reflector, complete with all accessories and fixing arrangement on PCC block of size 45mm x 45 mm alogwith fixing nuts, bolts and PVC insulated aluminium conductor, stranded type, size 4.0 sq.mm 2 core, including taking down old / unserviceble garden light fittings any type and wattage, complete all as specified and directed. MAKE:- Cat No. LTGLCW9WLED of C&S or Cat No. LHEVBDP7IN6K008 of Havells or Cat No. LPTO-CDL/M of Crompton
Supply only LED street light / Flood light fitting driver / choke 60 / 70 / 75 watt, 240 V, AC 50 Hz, electronic type, complete all as specified and directed. MAKE:- Crompton / Philips / Havells / Bajaj / C&S
Supply only LED street light / Flood light fitting driver / choke 90 watt, 240 V, AC 50 Hz, electronic type, complete all as specified and directed. MAKE:- Crompton / Philips / Havells / Bajaj / C&S
Supply only LED street light / Flood light fitting driver / choke 40 / 45 watt, 240 V, AC 50 Hz, electronic type, complete all as specified and directed. MAKE:- Crompton / Philips / Havells / Bajaj / C&S
Supply only LED street light / Flood light fitting driver / choke 25 / 30 watt, 240 V, AC 50 Hz, electronic type, complete all as specified and directed. MAKE:- Crompton / Philips / Havells / Bajaj / C&S
M/s A.K Construction
H.B. Traders
M/s A.KUMAR ELECTRICALS
M/S UJJAWAL ENTERPRISES
M/s multienterprises
PANDEY TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .