Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 114 BASEMENT MALL ROAD KINGSWAYS CAMP NORTH WEST DELHI DELHI 110009 | NORTH | DELHI | 110009 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹38.1 L
Closing Date
8 Sept 2021, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Director, DSCI
Delhi State Cancer Institute Dilshad Garden Delhi
Upgradation of smoke ventilation system as per National building code 2016 at Delhi State Cancer Institute (East ) Dilshad Garden, Delhi
2021_DSCI_207185_1
04/EE(E)/DSCI/2021-22
Open Tender
Miscellaneous Works
Works
60 days
Delhi State Cancer Institute Dilshad Garden Delhi
As per eligibility creteria of e-tender
9 documents required · 9 mandatory
₹0
Exempted
24 Nov 2021
18 Aug 2021
8 Sept 2021
18 Aug 2021
8 Sept 2021
18 Aug 2021
60 days
Amount
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS / high duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE 2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class "H" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc.. Motor shall be suitable for 250 °C temperature rated for 2 hours. The fans shall be as per specifications & tender drawing of following capacity:-
Air Qty. = 7250 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor
Air Qty. = 6350 CFM, Static Pressure = 25 mm Wg ,Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 3.7 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 5000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW. ,Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 2500 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 1750 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 5500 CFM , Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm ,Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 3500 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor.
Air Qty. = 2000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW, Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor,
Air Qty= 2200 CFM ,Static Pressure= 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor= Not exceed 2.2 KW., Fan Dia = 910mm (Approx.), Flow Direction: Impeller to Motor
Air Qty = 10000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 3.7 KW., Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
Air Qty. = 4000 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 1500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 3000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS / high duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE 2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class "F" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc..The fans shall be as per specifications & tender drawing of following capacity:-
Air Qty. = 7250 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm, Motor = Not exceed 2.2 KW., Fan Dia = 910mm (Approx.).Flow Direction: Impeller to Motor.
Air Qty. = 6350 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 3.7 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 5000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 2500 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 1750 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 5500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 3500 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 2000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
Air Qty. = 2200 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty.= 10000 CFM, Static Pressure = 25 mm Wg, Fan Speed = Not exceed 1450 rpm ,Motor = Not exceed 3.7 KW., Fan Dia = 910mm (Approx.)Flow Direction: Impeller to Motor.
Air Qty. = 4000 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 1500 CFM ,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor.
Air Qty. = 3000 CFM,Static Pressure = 25 mm Wg,Fan Speed = Not exceed 1450 rpm,Motor = Not exceed 2.2 KW.,Fan Dia = 910mm (Approx.),Flow Direction: Impeller to Motor
Supply,installation,testing and commissining of direct driven Tube axial flow fans suitable for installing in any position in Horizontal or vertical with adjustable pitch blade, MS / high duty GSS long Casing , cast aluminium alloy impeller complete with TEFC Sq. Cage Induction type IE 2 motor suitable for 415 volts ± 10%, 50Hz ± 3 %, 4 Pole, three phase A.C supply of class "F" insulation motor's winding with support, mountings, vibration isolators, fire retardant flexible canvass connector 150 mm deep with 25 mm slack at Outlet etc..The fans shall be as per specifications & tender drawing of following capacity:-
5000 CFM / 20 MMWG / 2.2 KW (Admin Block) Flow Direction: Impeller to Motor
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Thickness 1.00 mm sheet
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Thickness 1.00 mm sheet
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room
Damper
Actuator
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
Supplying & fixing of 18 G thick Aluminium extruded powder coated Fresh / Exhaust air weather protected louvers with bird screen type i.e. louvers blade shall be at 45° inclination with blade pitch 40 mm (with Aluminium frames if required) for ventilation with 12G GI wire mesh. as per specification and sizes will be as per tender drawing mentioned.
Supply,Installation, testing & commissioning of Gravity shutters made of 18G GI frame work & 22G GI blades with galvanised spindles & brass bushes. Blades shall be maximum 6” wide edges will be sealed with felt or flexible vinyl. The blades shall be pivoted using steel pivot pins and linked to open for 90 degrees without rattling and llow leakage closing mechanism and suitable for wall mouting / Duct Mounted with necessary framework.
Note: a. Potential free contact shall be provided with necessary modbus protocol compatible to BMS and energy management system.
Note: a. Potential free contact shall be provided with necessary modbus protocol compatible to BMS and energy management system.
POWER CABLING Supply, Installation, Testing and Commissioning of following XLPE insulated and PVC sheethed XLPE Power Cable of 1.1 kV grade Al./Cu Coductor Armoured cable of following sizes in existing Cable Tray or Surface mounted with suitable clamps, saddles, fixing bolts including connecting testing and commissioning and complete the work as per drawing and specifications.
3.5C x 95 Sq. mm al. ar. Cable (PANEL SUPPLY)
3.5C x 25 Sq. mm al. ar. Cable (PANEL SUPPLY)
3C x 4 Sq. mm Copper Cable (FOR FAN SUPPLY)
CONTROL CABLING Supply & Laying ,testing and commissioning of control cum transmission wiring of Copper conductor shielded cable for looping between indoor & outdoor VRF system & to main Central remote controller system
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (for Damper/Actuator)
Earthing Wires. Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Cable Trays Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
100 mm width X 50 mm depth X 1.6 mm thickness
Airtempengineers
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .