Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.1 LAccepted-AOC | L1 | Accepted-AOC LOWEST AND REASONABLE | |
| 2 | L2₹24.3 L+₹47,440 (1.99%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹25.4 L+₹1.6 L (6.73%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹36.9 L+₹13.0 L (54.8%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
4 Jul 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF SRINAGAR
CWE AF SRINAGAR
REPAIR MAINT OF HT DISTRIBUTION NETWORK ISOLATORS 11 KV BUS BAR PANELS AVR AND OTHER CONNECTED WORKS UNDER GE AF SRINAGAR
2022_MES_525670_1
CWE(AF)SGR/SGR-13/2022-23
Open Tender
Civil Works
Item Rate
180 days
AF SRINAGAR
AS PER NIT
8 documents required · 8 mandatory
₹500
GE AF SRINAGAR
₹56,000
Yes
3 Aug 2022
23 May 2022
6 Jul 2022
23 May 2022
4 Jul 2022
20 Jun 2022
60 days
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 meter deep for taking out HT underground cable and laying of new underground cable in replacement and getting out in soft / loose soil complete all as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cms. thick in soft / loose soil complete all as specified and directed.
Removal of surplus soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed.
Material and labour for sand cushioning in trenches including spreading and consolidation in layers of 8cm thick before laying the cable & 15 cm thick after laying the cable and punned down to form a bed complete all as specified and directed.
Supplying and laying Un-reinforced precast concrete cable cover factory made' of class HV, Type 1 with peak, of size 300 mm x 180 mm x 40 mm complete all as specified and directed.
Supply and fixing in replacement 100 mm dia galvanized iron tube light grade for protection of cable at road crossing complete all as specified and as directed.
Supply and fixing in replacement 80 mm dia galvanized iron tube light grade for protection of cable at road crossing complete all as specified and as directed.
Supply, Laying, jointing, and testing in replacement of underground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade(Earthed) and cross sectional area 120 sqmm 3 core confirming to latest IS and ISI marked complete all as specified and as directed.
Supply, Laying, jointing, and testing in replacement of underground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade(Earthed) and cross sectional area 95 sqmm 3 core confirming to latest IS and ISI marked complete all as specified and as directed.
Taking out carefully unserviceable XLPE HT underground cable of size 95 Sqmm /3-Core to 120 Sqmm /3-Core from trenches / Pipes including taking out bricks, complete all as specified and as directed. (Serviceable Bricks obtained shall be cleaned and stacked properly for reuse)
Laying only XLPE insulated, PVC inner sheathed, armoured, HT underground cable of size 95 Sqmm / 3-core to 120 Sqmm/ 3-Core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing etc complete all as specified and directed. Note:- (i) Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule.
Material and labour for dehydration / filtration of distribution transformer oil of transformer in position till the di-electric strength of transformer oil is not less than 50 KV when measured at 2.5 mm gap for one minute including filling of new transformer oil as required for top up upto oil level complete all as specified and directed. Note : - New transformer oil as required shall be measured and paid separatly under respective item as supply only.
Supply and filling new transformer oil with dielectric strength not less than 60 KV for distribution transformer when measured at 2.5 mm gap for duration of one minutes, complete all as specified and as directed.
Supply and fixing in replacement of HT feeder pillar box outdoor type factory made weather and vermin proof made out from 3.15 mm sheet supported with legs all across the panel made of angle iron 50x50x5 mm of size 1.2 mtrx1 mtrx1 mtr with 3 Nos required length Aluminium bus bar of size 40x10mm or 400 Amps for 11 KV , 11 KV post Insulator 6 Nos duly drilled hole for HT Cable connection including front and rear side openable with locking arrangment suitable for 11 KV HT and provision for incoming and out going HT cable connection including painting with two coats of smoke gray synthetic enamels paint over a coat of red oxide primer complete and providing security fence XPM jally type of 2 mtr height from ground level square type all rounded 2.5 mtr length with 9nos angle iron of 25x25x5mm of hight 2.25mtr (2mtr above ground 0.25 mtr under ground) including necessary location gate of same XPM jally all as specified and directed . Note:- Feeder piller box shall be mounted on brick platform built in PCC not less then 60 cm above ground level with suitable PCC foundation rendering 15 mm in CM (1:6), applying two coats and cement base paints and XPM jally supported on 9 nos angle iron with concrete base.
Material and labour for earthing in repair complete with galavanised steel earth plate electrode of size 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to galvanised steel earth strip of size 32x6 mm by means of bolts, nuts, check nuts and washers of galavanised iron/steel and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1 pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I. Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly.
Material and labour for earthing in repair complete with copper earth plate electrode of size 600mm x 600mm x 3mm thick buried directly in ground (earth pit not less than 2.25m deep below gound level with top edge of the earth plate not less than 1.5 m below normal gound level connected to copper earth strip of size 20x3mm by means of bolts, nuts, check nuts and washers of copper and conneted to main control board as directed and including proivison of concrete pit in PCC (1:2:4) type B1, pre cost RCC earth pit cover reinforced with 8 mm dia TMT bars @ 150mmc/c of size 54cmx54cmx8cm with two handle for lifting made out of 8mm dia MS bar, provision of funnel, wire mesh, 20mm bore galavanised steel tubing (med grade) for watering. Charcoal 250 Kg and salt 200 Kg in alternate layers, 40mm bore galavanised steel tubing light grade for protection of earth lead connection including necessary excavation and earth work and testing complete all as shown on electrical plate No 3 of SSR Part-I Note : Earth strip and protection pipe upto 7.5m is included in the unit rate of this item. Contractor shall quote his rate accordingly.
Supply, installation and testing in replacement of Lightening Arrestor expulsion type for outdoor use complete with all fittings station class discharge capacity 65 kilo Amps suitable for 11000 V including bracket, clamps, nuts and washers and connecting to earth wire complete all as specified and as directed.
Taking down defective transformer from any location of installation, transporting the same to authorised work shop for repair and returning back and installing at original location after repair including connection complete all as specified and directed.
Material and labour in replacement of opening/striping of transformer 11 KV/0.433 KV step down capacity from 63 KVA to 160 KVA including draining out oil, lifting the core & coil assembly, washing & cleaning dust, dirt and sludge deposit etc from all parts. Removing damaged/defective parts requires replacement, making internal connection servicing of tap changer and reassembling the transformer after repair and replacement work including new cork sheet gasket, packing nuts, bolts, washer etc complete as required filling fresh transformer oil and testing complete all as specified and directed.
Supply and fixing in replacement of opening/striping of transformer 11 KV/0.433 KV step down capacity from 200 KVA to 500 KVA including draining out oil, lifting the core & coil assembly, washing & cleaning dust, dirt and sludge deposit etc from all parts. Removing damaged/defective parts requires replacement, making internal connection servicing of tap changer and reassembling the transformer after repair and replacement work including new cork sheet gasket, packing nuts, bolts, washer etc complete as required filling fresh transformer oil and testing complete all as specified and directed. Note for items 19 and 20 :- Fresh transformer oil and other spare parts shall be measured under relevant items of Schedule.
Supply and fixing in replacement of burnt copper coil winding complete with suitable size/gauge of super copper enameled wire of high quality matching with existing size of wiring of transformer of capacity 100 KVA to 500 KVA complete all as specified and directed.
Supply and fixing in replacement Insulation of copper strip limb for LT side with existing coil of transformer of capacity 100 KVA to 500 KVA complete all as specified and directed.
Supply and fixing of HV porcelain bushing of 11 KV grade with gasket complete all as specified and as directed by Engr-in-Charge.
Supply and fixing of LV porcelain bushing of 1100 volts grade with gasket suitable for the following capacity of transformer :- (i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply and fixing of LT brass stud with 5 Nos brass nut, brass washers, check nuts, conical rubber bush for the following capacity of Transformer :- (i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply and fixing of HT brass stud with 3 Nos brass nut, brass washers, check nuts conical rubber bush for the following capacity of transformer:- (i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply and fixing of tap changer rotary type suitable for following capacity Transformer complete all as specified and as directed by Engr-in-Charge:- (i) 63 KVA to 160 KVA
(ii) 200 KVA to 400 KVA
(iii) 500 KVA
Supply and fixing of breather assembly with fresh filling of silica-gel (colour of silica gel should be deep sky blue) capacity in non metallic breather of transformer up to 500 KVA capacity complete all as specified and as directed.
Supply and fixing of oil level indicator suitable for Transformer up to 500 KVA capacity complete all as specified and as directed.
Supply and fixing of Oil temperature gauge as per IS specification complete as specified and directed, suitable for Transformer up to 500 KVA capacity complete all as specified and as directed.
Preparation of old painted surfaces of transformer and painting with two coats of synthetic enamel paint including writing SM No and MES No with approved colour paint with letters 30 mm high for the following capacity of transformer:- (i) 63 KVA to 200 KVA
(ii) 250 KVA to 400 KVA
Material and labour for HT Cable path indicator provided at distance of min 100 mtrs and at every joint,and turning of cable. The cable path indicator should be brown colur and fixed of min 45 cm long made of 40x40x6 mm of MS angle iron frame, complete all as specified and as directed.
Material and labour for calibration/servicing of 33 KV VCB / 11KV VCB / bus coupler by dismantling, cleaning and greasing the complete VCB with attached relays bus bar etc insulation testing, setting the contact gap by measuring as required reassembling the VCB and reinstalling back to its original position checking and repairing the current circuit panel wiring, replacement of new spares as required complete including operational testing and comrnissioning all as directed. Notes : (i) New spares will be measured and paid separately under relevant item of' this schedule. (ii) Calibration test sheet provided by authorized OEM will be submitted by the contractor.
Supply, connecting and testing tripping coil DC 30 Volt suitable for 11KV VCB panel complete all as specified and directed.
Supply, connecting and testing closing coil DC 30 Volt suitable for 11KV VCB panel complete all as specified and directed.
Supply, connecting Ammeter digital type 144 sqmm with CT ratio 100/5 and current rating 0-50 Amp suitable for 11 KV VCB panel complete all as specified and directed.
Supply, connecting Voltmeter digital type 0-15 KV PT ratio, 11KV/110 Volt suitable for 11 KV VCB panel complete all as specified and directed.
Supply and fixing LED type indicating lamp fitting R Y B suitable for 24 /30 Volt DC complete all as specified and directed.
Supply and fixing of gear system assembly with handle for charging discharging of VCBs complete all as specified and directed.
Supply and fixing of spring charging motor for VCBs complete all as specified and directed.
Supply and fixing of breaker control switch for 11 KV breakers.
Supply and fixing of Auxiliary spring set as per sample.
Supply and fixing of Vacuum interrupter type WL3379M3.
Supply and fixing of rachet assembly buterfly as per sample.
Material and labour for repair of UPS 5.0 KVA capacity single Phase 72 Volt. of Microtek.
Material and labour for repair of copper wounded battery charger input voltage 120 Volts to 240 Volts, output voltage 36 Volt along with protection DC MCB on DC side for reverse polarity, AC MCB on AC side, inbuilt stabiliser and fault indicator.
Material and labour for repair of microprocessor based over current and earth fault relay with highest element event recording & current scanning/display feature suitable for 30 Vto 110 V AC/DC .
Material and labour for repair of 12 KV indoor epoxy resin current transformer with CT ratio 750-375/5-5-2.89A match as per existing CT complete all as specified and directed.
Material and labour for carrying out primary & secondary injection test of 33 KV indoor/outdoor type current transformer (Set of three) of VCBs by using standard injection test method and checking the electrical circuits for fault condition, all relay testing and proper functioning including submitting the test report all as directed by Engr-in-charge. Note : PIT/SIT for VCB will be carried out in 6 months intervals and each primary & secondary injection test will be measured and paid.
Material and labour for carrying out primary & secondary injection test of 11 KV indoor /outdoor type current transformer (Set of three) of VCBs by using standard injection test method and checking the electrical circuits for fault condition, all relay testing and proper functioning including submitting the test report all as directed by Engr-in-charge. Note : PIT/SIT for VCB will be carried out in 6 months intervals and each primary & secondary injection test will be measured and paid.
Supply and fixing in repairs moving carbon rollers of existing size and make suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Tie & Tac brass connector suitable for 2000 KVA AVR Unit.
Supply and fixing in repairs Chain rack (double) including bearing as per existing make & model.
Supply and fixing in repairs Limit switch suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs SS coupling suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Chain assembly suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Synchronous motor suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs PCB card suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs PT unit 11000/110 volts suitable for 2000 KVA buck booster Unit as per existing make & model.
Supply and fixing Winding temperature relay complete suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Oil temperature relay complete suitable for 2000 KVA AVR Unit as per existing make & model.
Supply and fixing in repairs Buchloz relay assembly complete suitable for 2000 KVA AVR Unit/ Transformer as per existing make & model.
Supply and fixing in repairs Aux contactor suitable for 2000 KVA AVR Unit as per existing make & model.
Material and labour for anti climbing devices spikes type fabricated out of MS bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as specified and directed.
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed. Make: DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed. Make : DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed. Make: DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed. Make : DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed. Make: DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed. Make: DENSON, M-SEAL, BIRLA 3M, RAYCHEM, CABSEAL
Material and labour for replacement of Air break gang operated switch with 12 Nos insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement, consisting of MS Channel, HT post type insulator copper alloy, high pressure, assembly drop out fuses, operating rod 25mm dia GI pipe, medium grade for operating from 1.2 m above GL complete including drop out fuses conforming to IS rated voltage 11 KV and for current rating 200 Amp all as specified and directed. Make : BHEL, PACTIL OBLUM, ABB
Material and labour for cleaning of surrounding area of E&M installation around the instln bldg , transformer, GOD LT panel including plants and vegetation through grass cutting machine and manul labour by theior own arrangement complete all as specified and directed.
Material and labour for cutting of existing road surfaces up 100 mm deep & 300 mm wide and making good disturbed portion with 100mm thick plain cement concrete 1:2:4 type B-1 (using 40mm graded crushed stone aggregate) complete all as specified and directed
Material and labour for replacement of Mild steel framed work such as grills, gratings, etc with ends of bars shouldered and/ or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed ballusters walk ways; railings; frame work , bracing support of HT 11 /33 KV 2 / 4 Pole structure at EM installation and similar work conforming to Fe.290. Gde-E-165 including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
Material and labour for replacement of plate plain/chequered 6.0 mm thickness complete with necessary electric welding works complete all as specified and directed.
Material and labour for taking out of inclind HT pole & repairing and refixing the same including excavation, removal, PCC foundation complete all as specified and directed.
Material and labour for painting of steel tubular poles (perimeter) approximately 9.5 meter above GL in height including cross arms and bracings with two coat of aluminium paint including numbering of the pole, complete all as specified and directed.
Supply and fixing in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint on 4/6 pole 11 KV HT structure, complete all as specified and directed.
Material and labour for sprading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMU manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers not exc. 15 cm thick watered and rammed to true surface including surface excavation and removal complete all as specified and directed.
Supplying and fixing in replacement male contact/moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
Supplying and fixing in replacement female contact /fix contact jaw for gang operated air break device 11 KV complete all as directed.
Material and labour for maintenance of gang operated air break isolators switch out door type 12 insulators double stack, triple pole, rotating type double break per pole for 11000 volts, 3 phase, 50 Hz, AC supply system having 200 / 400 Amps capacity by oiling, greasing, adjustment of lever and making the same smooth functional complete all as specified and directed.
Material and labour for rerouting the existing HT XLPE Cable of size 70 Sqmm to 120 Sqmm including connections with suitable size of thimble at various location of E/M installation complete all as specified and as directed. Note:- (i) Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule.
Material and labour for reroute the existing HT XLPE Cable of size 150 Sqmm to 240 Sqmm including connections with suitable size of thimble at various location of E/m installation complete all as specified and as directed. Note:- (i) Earthwork, sand cushion, cable cover if required will be measured and paid separately under respective items of this Schedule.
Material and labour for replacement of Aluminium conductor, steel reinforced (ACSR) Code name : Weasel conductor for HT feeders on steel tubular/PCC poles, stretching without kinks and bends including binding wire including taking down old conductor of any type shape and size, complete all as specified and directed. Make: JAIPURIA, ALIND, ICC, NICCO
Supply and fixing in replacement of disc type, porcelain, vitreous white / brown / green insulator including one galvanised mild steel straps washers insulator bolts, washers , nut, 145 mm height, 255 mm dia for 11000 volts grade complete all as specified and directed.
Supply and fixing in replacement of pin type, porcelain, vitreous, white / brown / green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed.
Supply and fixing in replacement of conservator tank indicator as per existing capacity of transformer 63 to160 KVA complete all as specified and directed.
Supply and fixing in replacement of conservator tank indicator as per existing capacity of transformer 200 to 400 KVA complete all as specified and directed.
Supply and fixing in replacement of conservator tank indicator as per existing capacity of transformer 500 KVA complete all as specified and directed.
Repair / servecing the air break isolating switch of HT 33 KV 200/400A by replacing the defective major spare including provn of minor bolt nuts etc complete all as specified and directed. Note : Major spare part shall be measured and paid seperetly under relevent item .
Supply and fixing in replacement of Male contact / moving contact blade complete all as specified and directed.
Supply and fixing in replacement of Female contact / fix contact jaw complete all as specified and directed.
Supply and fixing in replacement of Rotating contactor pipe for upto 2000 / 400 Amps complete all as specified and directed.
Supply and fixing in replacement of MS jumper carrier complete all as specified and directed.
Supply and fixing in replacement of Back connector plate complete all as specified and directed.
Supply and fixing in replacement dropout DO fuse unit expulsion type outdoor three pole 200A suitable for HT 33 KV comprising of insulator steel base mounting frame GI nut bolt etc with 30A HT barrel type fuse complete all as specified and directed.
Supply and fixing in replacement incl testing and commissioning of GOD gang operated type air break isolating switch horizontal / vertical type mounting complete double break and operation rod of suitable length 400 A capacity and suitable for 33 KV HT supply complete all as specified and directed.
Supply and fixing in replacement of lighting arrestor zinc oxide gap less type station class suitable for 33 KV / 10KA complete with all fitting complete all as specified and directed.
Supply and fixing in replacement of single post insulator suitable for 33 KV with mounting spindle etc complete with all fitting complete all as specified and directed.
Supply and fixing in replacement of Pin insulator suitable for 33 KV with mounting spindle etc complete with all fitting complete all as specified and directed.
Supply and fixing in replacement of Disc insulator suitable for 33 KV with mounting spindle etc complete with all fitting complete all as specified and directed.
Material and labour for preparation of old painted surface of HT 33 KV MRS at 90 B Grid consisting of steel pole , cross arm, GOD pipe , clamp etc having any description and applying one caot of aluminium paint by manually complete all as specified and directed. Note : (a) The rate inclusive of painting all minor items as clamps , brackets, nut, bolt and washer which is not particularly mentioned in this item. (b) The painting work will be carried out during holiday only to avoid electric shut down.
Supply and fixing in replacement of synthetic insulating rubber mat ISI marked of size 2 mtr x 1 x mtr x 8mm 33 KV / 11 KV at MRS 90 B Grid complete with all fitting complete all as specified and directed
Supply and fixing in replacement of bolted type LM 6 alloy aluminium rigid stud type terminal connector of type universal connector suitable for 33 / 11 KV type ACSR conductor / busbar complete with all fitting complete all as specified and directed
Supply and fixing in replacement of bolted type LM 6 alloy aluminium rigid stud type terminal connector of type universal connector suitable for 33 / 11 KV type ACSR conductor / busbar complete with all fitting complete all as specified and directed
Supply and fixing in replacement of bolted type LM 6 alloy aluminium rigid parallel conductor , conductor to conductor suitable for 33 / 11 KV type ACSR conductor / busbar complete with all fitting complete all as specified and directed
Material and labour for routine repair to Power transformer of any type and any capacity after dismantling the transformer carefully opening the top cover of transformer for inspection / repair draining out the transformer oil from the housing complete, removing the carbon / sludge deposit in transformer housing core, renewal / replacement of unservisiable rubber bushes and washer, replacement of tap changer motor winding and thimble , replacement of silica gel , replacement of top cover gaskit set including jointing with pasting material, replacement of worn out and bolt , replacement of unsv LT & HT bushes , keeping the coil in electric oven chamber for 48 hr to remove the moister content , replacement of temp gauage of oil and winding , painting of complete transformer body from outside and inside . Marking of MES/SM number etc, replacement of conservator tank glass, reinstalling the core and winding inside properly, marking th all connection with suitable copper lugs, refilling of dehydrated transformer oil including dedydration, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, Meggering the HT of transformer and testing, complete all as specified and directed.
Supply and fixing earth fault protection relay 11 KV suitable for 36 volt DC auxiliary supply, complete all as specified and directed. Make : C&G, L&T, Schneider.
Supply and fixing earth fault protection relay 33 KV suitable for 36 volt DC auxiliary supply, complete all as specified and directed. Make : C&G, L&T, Schneider.
Supply and fixing over current protection realy 11 KV suitable for 36 Volt DC supply, complete all as specified and directed.
Supply and fixing control cable (armoured) 08 core 2.5 Sqmm, complete all as specified and directed.
Supply and fixing VCB charging motor suitable for 11 KV VCB and operated on 230V, 50Hz single phase supply, complete all as specified and directed. Make : Woulf, C&G, Kirloskar.
CHINAR CONSTRUCTION TRADERS
M/S LATIF AHMAD MIR
M/S ZAHOOR ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .