Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC B 101 SURAJ TOWER MIRA BHAYANDER ROAD OPP SAI PETROL PUMP MIRA ROAD EAST THANE 401107 | MIRA ROAD EAST | THANE | MAHARASHTRA | 401107 | L1 | Accepted-AOC QUOTED L1 | |
| 2 | L2₹11.0 L+₹1.3 L (13.0%)Rejected-AOC | L2 | Rejected-AOC NOT ADMITTED | |
| 3 | L3₹12.9 L+₹3.1 L (31.6%)Rejected-AOC | L3 | Rejected-AOC NOT ADMITTED | |
| 4 | L4₹12.9 L+₹3.1 L (32.1%)Rejected-AOC MAYURESH BHARAT CHS PLOT NO 170 181 B 09 SECTOR 21 NERUL NAVI MUMBAI 400706 | THANE | MAHARASHTRA | 400706 | L4 | Rejected-AOC NOT ADMITTED | |
| 5 | L5₹13.8 L+₹4.0 L (40.8%)Rejected-AOC | L5 | Rejected-AOC NOT ADMITTED |
Tender Value
Refer Docs
EMD Value
₹29,200
Closing Date
6 Dec 2021, 6:00 pmClosed
CWE (SUBS) MUMBAI
Commander Works Engineer Subs NCHC Powai Bhandup Post Office Mumbai 400 078
PROVISION OF FIRE ALARM AND DETECTION SYSTEM IN NS-205 AT MO (MB) GHATKOPAR UNDER GE (NW) BHANDUP
2021_MES_477963_2
8407/E8
Open Tender
Civil Works
Item Rate
180 days
GHATKOPAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (NW) BHANDUP
₹29,200
Yes
28 Jan 2022
18 Nov 2021
9 Dec 2021
18 Nov 2021
6 Dec 2021
24 Nov 2021
Amount
Supply, Installation, Testing and commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel for 1 loop LCD display, 1000 event plus 1000 alarm log historyevents. The panel shall be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices. The panel shall work with, 240 volts AC power supply, automatic battery charger, 2 x 12 Volts, DC sealed lead acid batteries sufficient for 24 hours normal working and 01 hrs in alarm condition. The fire alarm system shall comply with requirements of NFPA Standard 72 for The system shall be electrically supervised and monitor the integrity of all conductors. Panel and detector shall be of same make as approved by the GE and all sensor shall be battery backed up. Panel shall be Underwriters Laboratories listed, semi flush type and / or surface mount type as per requirement all as directed, Make : Notifier
Supply and fixing 12VDC~7AH Battery along with suitable connection complete all as specified and directed.
Supply, installation, testing and commissioning of Fibre optics Network Card with all accessories and suitable operation with exissting system complete all as specified and directed.
Supply, installation, testing and commissioning of Addressable Multi-criteria Photo-Thermal Detector with sensitivity range of 0.5 to 4.0% obs/ft. The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector shall be designed to meet UL Design criteria.Make : Notifier
Supply, installation, testing and commissioning Addressable Manual Call Point (Pull down / Break Glass Type). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the device and shall be Underwriters Laboratories Listed, semi flush type, Make: Notifier
Supply, installation, testing and commissioning of addressable type Hooter cum Flasher flame proof type, rated at 75 dB at 3 metre for Audible annunciation and 75cd flashing at 1 Hz for visual indication with and including Control Module, complete all as specified and directed, Make of Hooter : FCG/ Baliga, Make of Control Module : Notifier/Advanced /Bosch.Notes for item No 15 : (i) The hooter shall be Central Mining Research Institute and Petroleum & Explosives Safety Organisation approved. (ii) The Control Module shall be UL Listed
Supply, installation, testing and commissioning of Isolator module to electrically isolate different section of detetor loop with and necessary back box & accessories, complete all as specified and directed, The isolator module shall be UL Listed, Make :- Notifier
Supply, installation, testing and commissioning of Addressable Control Module necessary back box &accessories, complete all as specified and directed, The isolator module shall be UL Listed
Supply, installation, testing and commissioning of addressable type Hooter cum Flasher flame proof type, rated at 75 dB at 3 metre for Audible annunciation and 75cd flashing at 1 Hz for visual indication with and including Control Module, complete all as specified and directed, Make of Hooter : FCG/ Patco/Baliga, Make of Control Module : Notifier/Advanced /Bosch.Notes for item No 15 : (i) The hooter shall be Central Mining Research Institute and Petroleum & Explosives Safety Organisation approved.(ii) The Control Module shall be UL Listed
supply and fix 1/2" Gland with suitable accessories complete all as specified and directed
Supply and Laying of 2 Core 1.5 Sqmm copperconductor,GI armoured,FRLS cable confirming to IS 1554 (Part-1) in trenched/fixing along wall/floor/ceilling with and including GI saddles,clamps,Nylon cable ties etc,complete all as specified and directed. Make :Polycab/ Finolex/ Havells Notes : (i) Excavation and earth work, protection pipes shall be measured and paid for separately.(ii) Cable shall be as per Fire Norms & red in colour
Supply and Laying of 6 Core Multi Mode Optic Fiber Cable Full armoured in the trenches/ fixed along wall/floor/ ceiling with and including GI saddles, clamps, Nylon cable ties, complete all as specified and directed, Make : Polycab/ Finolex/ Havells Note : Excavation and earth work, protection pipes shall be measured and paid for separately
Splicing termination of Fibre optics network cable with all required accessories complete all as specified and directed
Excavation in trenches not exc 1.5M wide and not exc 1.5M deep for cables, pipe etc and not exc 10 Sqm on plan and not exc. 1.50 metre in depth for poles etc and getting out in any type of soil, complete all as specified and directed
Programming, testing and commissioning Charges including graphics progamming on SCADA PC all as specified and directed
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .