XEN Electrical Division No.II
XEN Electrical Division No.II HPPWD Shimla-2
Providing electrical installation
2019_PWD_32664_1
ED.II.GA.Tender/19-20-5566-67 dated 11.11.2019
Open Tender
Electrical Works
Item Rate
360 days
Shimla
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,500
EE Elect Divn No. II
₹64,500
20 Jun 2020
22 Nov 2019
18 Dec 2019
22 Nov 2019
17 Dec 2019
22 Nov 2019
Amount
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. Group-C
Light Point
Fan Point
Call Bell Point
Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required.
2x1.5 Sq. mm.
Wiring for circuit / sub-main with 4x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.1.5 Sq.mm. (4x1.5+2x1.5) HRFRLS/PVC insulated single core copper conductor cable for earthing as required.
Supplying & fixing of G.I. modular boxes of following sizes along with modular base and cover plate for modular switches in recess as required:-
6 Module (205mmx78mmx50mm)
2 modules (78mmx78mmx50mm)
Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required.
S.P. 5/ 6 Amps one way Modular switch.
5 pin, 5/ 6 Amps Modular socket outlet.
S.P. 15/ 16 Amps one way Modular switch.
6 pin,15/16 Amps Modular socket outlet.
Supplying and fixing call bell / buzzer, suitable for D.C./A.C. single phase,230 volts complete as required:-
Supplying and fixing sheet metal bus-bar chamber suitable for 100 Amp. 415 volts capacity with 4 No. copper strip bus-bars each of length 300mm & cross-sectional area (25.4mmx3.17mm), enclosure made from 1.6 mm thick M.S. sheet having overall dimensions (380mmx400mmx150mm) nominal with all accessories including connections, earthing the body etc. as required:-
Providing and fixing following rating and breaking capacity MCCB in the existing cubical panel board including drilling holes in the cubicle panel, making connections, etc. as required.
100 Amp. -10 KA
125 Amp. -16 KA
250 Amp. -25 KA
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Single pole. Cat-A.
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Double pole. Cat-A.
Triple pole. & Neutral Cat-A.
Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual current circuit breaker (RCCB), having a sensitivity current up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 Amps. Cat-A.
63 Amps. Cat-A.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Double door-8 way
Double door-12 way
Double door-6 way
Single door-4 way
Earthing with copper earth plate 600mm x 600mm x 3mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and coke for G.I. or copper plate earth electrode complete as required.
Providing and laying earth connections from earth electrode with 6 SWG (4 mm dia.) copper Wire in 15 mm dia. G.I. pipe from earth electrode etc. as required.
Providing and fixing 6 SWG (4 mm dia.) G.I. wire on surface or in recess for loop earthing as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm long copper tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required.
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Supplying and laying copper tape 32mmx6mm thick from earth electrode directly in ground as required.
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-
Armoured cable 10 sq. mm (twin core)
Armoured cable 16 sq. mm (twin core)
Armoured cable 16 sq. mm (four core)
Armoured cable 50 sq. mm (3.5 core)
Armoured cable 70 sq. mm (3.5 core)
Armoured cable 120 sq. mm (3.5 core)
Armoured cable 150 sq. mm (3.5 core)
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes by means of Expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, providing and fixing of Non-return valve, Dead weight safety valve, 2 No C.P. connection rods 18" long, making good the damages, electrical connections, safety valve connections, testing and commissioning etc. as required:-
25 Liter capacity water heater (Cat-A)
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:-
Exhaust Fan, Light duty, (Domestic) 300 mm sweep
Exhaust Fan, Heavy duty, 300 mm sweep
Providing and installation of following type of surface mountingCubic LED panel 36watt 2 x2 feets in white finish with anti glare polycarbonate diffuser and seprated energy efficient constant current, non-integral, electronic driver; suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc. as required. Make: Philips, Syska, Bajaj, Twinkle ,Panasonic or any other approved by Engineer-in-Charge.
LED surface panel 2x2 feets 36 watt
Providing and installation of following type of surface mountingCubic LED panel 22watt 1x1 feets in white finish with anti glare polycarbonate diffuser and seprated energy efficient constant current, non-integral, electronic driver; suitable for input voltage: AC 220-240 V, 50/60Hz, complete with all accessories, connections, testing and commissioning etc. as required. Make: Philips, Syska,Bajaj,Twinkle,C&S, Panasonic or any other approved by Engineer-in-Charge.
Surface Mounted Cubic LED panel 1x1 20/22 watt
Providing and installation of following type of ultra slim decorative LED Batten suitable for 100 lumens/watt with minimum 2 year warranty with extruded aluminium heat sink, with antiglare polycarbonate diffuser and energy efficient constant current, integral electronic driver, suitable for input voltage: 220-240 V, 50/60 Hz, complete with all accesories, including mounting clips & loop in loop wire, connections, testing and commissioning etc. as required, Make: Philips, Syska, Bajaj,Twinkle,C&S, Panasonic or any other approved by Engineer-in-Charge:
LED Batten Light 1200 mm 18W
Providing and fixing SS Enclosure for DU / DH MCCBs, suitable for 4-Pole MCCBs etc. as required. Make: L&T, Schneider, Siemens, ABB, C&S,Standard etc.
SKB 5/6/7 Frame FP (Standard Make) suitable for 100A & 125A MCCBs Cat. No. ISEGFP
SKB 1/2 Frame FP (Standard Make) FP suitable for 250A MCCB Cat. No ISEAFP
Kalra Hardware and Electric Store
D.S Ranta Electrical Contractor
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.PDF
finance_47098.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .