| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.2 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹30.3 L+₹4.8 L (18.6%)Rejected-AOC HOUSE NO 2 4 136 LINGREDDY MANSION BLOCK NO IV OPP HANUMAN TEMPLE TADBUND SECUNDERABAD 500009 | SECUNDERABAD | HYDERABAD | TELANGANA | 500009 | L2 | Rejected-AOC Not being L1 | |
| 3 | L3₹31.4 L+₹5.9 L (23.1%)Rejected-AOC PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | L3 | Rejected-AOC Not being L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical NOT HAVING REQUISITE WORK CATEGORIES i.e. |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
13 Dec 2021, 6:00 pmClosed
GARRISON ENGINEER UTILITY SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
REPAIRS/REPLACEMENT AND MAINTENANCE OF SEWAGE TREATMENT PLANT, FIRE FIGHTING SYSTEM AND CENTRAL ACs/CASSETTES TYPE ACs AND AHU UNITS AND CONNECTED ALLIED WORKS AT CDM SECUNDERABAD UNDER AGE E/M NO 1 OF GE (UTILITY) SECUNDERABAD
2021_MES_488969_1
GE(U)/SEC/TOKEN/43 OF 2021-2022
Open Tender
Miscellaneous Works
Item Rate
180 days
SECUNDERABAD
AS PER NIT
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER UTILITY SECUNDERABAD
₹70,000
Yes
1 Sept 2022
17 Nov 2021
20 Dec 2021
17 Nov 2021
13 Dec 2021
1 Dec 2021
Amount
M&L for preventive maintenance and tesing of fire fighting system control panel consisting zone type microprocessor based panel, fire/smoke/flame detectors and connected to CO2 cylinder bank of two zones consisting of 06 cylinders in each zone of 125 kg each by creating artificial smoke/fire in the presence user/CDM and MES representative and resetting the system after testing at site and preparing the test result sheet complete all as specified and directed.
M&L for preventive maintenance, tesing and attending complains of fire alarm system having wireless control panel consisting zone type microprocessor based panel,wireless photo electric fire/smoke detectors with artificial smoke/fire in the presence of user/CDM and MES representative including clearing the minute particles with air blower of smoke detectors and resetting the setting after testing in Library, SP block and Ashwamedha block complete all as specified and directed. Note: Testing should be done by Ceasefire/visonic company.
M&L for filling of CO2 gas in 45 kg cylinders of CO2 bank including disconnecting the cylinders from manifold and refixing carefully with necessary teflon thread seal tape and hardware at site complete all as specified and directed.
Supply and replacement of 1/4'' highly inflamable hose pipe assy of length 300mm (as per sample) and is connected to CO2 gas cylinder master valve to slave valve assy and approved ISI std and specified and directed.
Supply and replacement of 1/4'' highly inflamable hose pipe assy of length 500mm (as per sample) and is connected to CO2 gas cylinder master valve to header pipe and complete all as approved ISI std and specified and directed.
Taking out and dismantling of U/s CO2 Master valve assembly from the cylinder and cleaning of all the dismantled parts of cyliner and replace the damaged CO2 master valve complete with 24 solenoid and manual release lever with new at site and testing the same on completion alll as specified and as directed.
Taking out and dismantling of U/s CO2 slave valve assembly from the cylinder and cleaning of all the dismantled parts of cyliner and replace the damaged CO2 slave valve complete with pneumatic actuator and manual lever with new at site and testing the same on completion alll as specified and as directed.
M&L 10Kg Standalone Suppression System- HFC236 fa ceiling mounted fire extiguisher clean agent stored pressure guage weight 14.8Kg, empty weight 4.8Kg can height 316MM, diameter 300MM, dischrage time less 10Secs, Auto dischrage mechanism on temperature rise applicable on class A,B,C and electrically started fire, can construcrion: Deep drawn & CO2, mig welded valve construction forging & machining, internal coating of Can: Epoxy coating external coating of can: Epoxy polyster powder coating sheet metal thickness: 2.0MM helium leak detection tested, 5 Years warranty. Make: Product code CF-000770 OF CEASEFIRE or equivalent as approved by GE
M&L 5Kg Standalone Suppression System- HFC236 fa ceiling mounted fire extiguisher clean agent stored pressure guage weight 7.7Kg, empty weight 2.7Kg can height 267MM, diameter 230MM, dischrage time less 10Secs, Auto dischrage mechanism on temperature rise applicable on class A,B,C and electrically started fire, can construction: Deep drawn & CO2, mig welded valve construction forging & machining, internal coating of Can: Epoxy coating external coating of can: Epoxy polyster powder coating sheet metal thickness: 1.6MM helium leak detection tested, 5 Years warranty. Make: Product code CF-000771 of CEASEFIRE or equivalent as approved by GE
Supply , Installation Commissioning and testing of wireless Panel : Operating frequency range : 868.15 MHz to 869.85 MHz maximum radiated power 5 dBm (3 MW) operting frequency chnnels : 7 communication range with translator or expander module, IP rating :42 dimensions : 85 mm * 85 mm weight (with out batteries) : 134 gms, primary power cell : CR123A (3V & 1.2Ah) secondary power cell : CR2032A (3V & 0.2Ah) Oprating Temperature: - 30 degree C to +55 degree C, maximum trolerated humidity (no condensing) : 95% RH Complete all as specified and directed .
Supply, fixing and testing of wireless photo electric smoke detector comprising with following specification complete all as specified and directed. Specifications:- (i) Cover range : 50 Cubic meter to 100 Cubic meter (ii) Battery type : 3V CR 123A (iii) Battery expected life : 5 year (iv) Weight : 165 gram (v) Operating temperature : 10 degree C to 50 degree C (vi) Operating environment : Indoor (vii) Dimension : 120 mm x 58 mm
S&F of suitable at site 3V CR123A Lithium Battery of wireless photo electric smoke detector with having life of 5 year, along with testing after fixing of detector incl taking down old Unsv battery complete all as specified and directed. Make : Panasonic as approved by GE
Supply, installation, commissioning and testing of smoke detector of type Photoelectric / Optical with base with self inbuilt intelligence and compared to EN-45 addressable type complete all as specified and directed. Make: Reliance/Zeco Wizmart/Notifier as approved by GE
Supply, installation, commissioning and testing of Heat detector type Photoelectric / Optical with base with self inbuilt intelligence andcompared to EN-45 addressable type complete all as specified and directed. Make: Reliance/Visonic/Notifier as approved by GE
Testing and Commissioning Pressure test the system with dry Nitrogen upto 300 PSI and rectifiying the leakages , pressure hold upto 300 PSI for 48 Hrs , Vaccumizing the system upto 500 micrones & commissioning the unit, test running etc as per requirements (Refrigerant gas shall be paid seperate)
M&L for Cleaning/descaling of cooling coil fins of IT center AHU of 66TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing all as directred by Engr-in-charge. Make : ACCEL as approved by GE
M&L for Cleaning/descaling of cooling coil fins of Library AHU of 33TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing all as directred by Engr-in-charge.
M&L for Cleaning/descaling of cooling coil fins of Ductable ACs of 11 TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing all as directred by Engr-in-charge
Repairs of Indoor PCB Controls of 11 TR AC as specified and directed.
S&F of New Controls with remote for 11 TR Ductable unit as specified and directed. Make:- HITACHI as approved by GE
S&F of PCB of 11 TR HITACHI Outdoor unit as per requirement of site. Make:- HITACHI as approved by GE
S&F of Electronic Thermostate including replaceing of U/S Old Thermostate as per requirement of site. Make:- HITACHI/VOLTAS as approved by GE
S&F of liquid line filter 5/8 ae per requirement of site all as specified and directed
Supply and Charging of Refrigerant Gas R-410/407C or equivalnt in Froen/Mafron family in sealed cylinders all as directed by Engr-in-charge
Supply and fill Compressor Oil Make : Sheetal (IOC) or equivalent as approved by GE
Supply, fixing and commissioning Scroll Compressor of Capacity 11 TR with all its specification including removing of Old Unsv compressor as per requirement of site. Make:- HITACHI/VOLTAS as approved by GE
M&L for Servicing of Compressor Suction and discharge Shut-off Valves by replacing Teflon washers and hard ware for proper functioning all as directed
S&F for replacement of the following unsv items of LT panel board of the AC plant and air cooling system :
MCCB 32 Amps, 3 phase 3 pole, 25 KA, 415 volts with fixed magnetic settings complete. Make : L&T type DNO-100C as approved by GE
MCCB 63 Amps , 3 phase 3 pole, 25 KA, 415 volts with fixed magnetic settings complete. Make : L&T type DNO-100C as approved by GE
Front Mounting Add-on aux. Contact Block MNX A2. Make :- L&T or equivalent as approved by GE
Power contactor 3 pole 25 amps 415 volts type ML-3. Make : Cat Part No 3TS3300 of SIEMENS or Equivalent as approved by GE.
Power contactor 3 pole 25 amps 415 volts type ML-3. Make : Cat Part No LC1E2501M7 of SCHNEIDER or Equivalent as approved by GE.
Over load relay 3 phase 440 volts 28 to 42 amps. Make : L&T type ML-3 as approved by GE
MCCB 100 Amps , 3 phase 3 pole, 25 KA, 415 volts with fixed magnetic settings complete. Make : L&T type DNO-100C as approved by GE
Rewiring of 11 TR outdoor unit fan motor as specified and directed.
M&L for servicing and over hauling of 66/33 TR AHU Blower motor of 7.5 HP including varnishing the stator and replacing the worn out drive end/driven end bearings and greasing and reassembling and testing complete all as directed
S&F for replacement of UNSV "V" belts suitable for 7.5 HP air blower motor size of "V" belt complete, all as specified and directed .
M&L for servicing and overhauling of air curtain for prevention dust and conditioned air losses, single phase 220V 50 Hz, made out of MS/CRCA Sheet of minimum thickness 18 gauge finished with two coats of red oxide and final coat of synthetic enemell paint (oven backed) with MS/CRCA 18 gauge square perfoated suction grills alluminium alloy fans and single phase electric motor, nozzles etc, complete with fitting and accessories so as to produce 1-1.5 m/sec air velocity at floor level for door opening for size 70" x 78" complete all as specified and directed.
S&F PVC insulated flexible stranded copper conductor of size 16 sqmm x 4 core complete all as specified and directed. Make :- Havells/ Polycab/KEI as approved by GE
Repair/Maintenance, excluding spares but including regualr maintenance of the Sewage treatment plant of capacity 50 Cum/day installed at CDM Dhruva under AGE E/M No 1 including carrying out complete maintenance /servicing/ repair as requied of all the sub systems viz control panels, compressor blower, pump motors, lamella plant, filter press, filtration plant & sodium hyprochlorite dosing plant (with all the accessoires ) breakdown maintenance and replacement of unserviceable parts, re-fixing of old serviceable parts/new parts if any inclduing the following and all as specified and directed by Engineer-in-Charge
Note :- (i) New parts if any shall be paid under separate items as supply only (ii) Unit rate quoted by tenderer is of checking of system monthly by technician and necessary servicing and repair job signed by JE /Engr-in-Charge (iii) Unit rate quoted by tenderer is of checking of system fortnightly by Engineer and necessary servicing and repair job signed by JE /Engr-in-Charge (iv) In addition to above specific emergency complaints receiving telephonically from time to time shall be attended within 24 hrs after receiving the same (v) The scope of work includes the charges required for removing, repairing, refixing, carrying out electrical termination and fixing/installing testing commissioning etc and all as directed (vi) The work has to be carried through ion exchange company authorized representative.
M&L for emptying and cleaning/removal of hold up sewage from and sludge from drains including cleaning of Bar Screen chamber of STP of capacity 50 Cum/Day all as specified and directed by Engr-in-Charge
M&L for removal of sewage and garbage from oil grease chamber of STP capacity 50 Cum/Day with the help of sewage pump mounted on portable bowser complete all as specified and directed by Engr-in-charge
M&L for removal of sewage and garbage from collection tank with the help of sewage pump mounted on portable bowser and replacement of air diffusers with unserviceable distribution pipe network of STP of capacity 50 Cum/Day all as specified and directed by Engr-in-Charge
M&L for removal of sewage and garbade from Aeration tank of STP of capacity 50 CUM /day with the help of pump mounted on portable bowser/manual including cleaning of distribution piping network complete all as specified and directed
M&L for replacement of FMR Fluidized Bio-Media suitable for STP of capacity 50Cum /Day all as specified and directed by the Engr-in-Charge
Supply of New clarifier plates suitable for STP of capacity 50 Cum/day incl taking down old unsv all as specified and directed by the Engr-in-charge
Supply of New Micron Catridges along with Housing suitable for STP of capacity 50 Cum/day incl taking down old unsv all as specified and directed by the Engr-in-charge
Rectification of UV system and supply of spare as per requirement all as specified and directed.
Supply of Membrane diffuser suitable for STP of capacity 50 Cum/day incl taking down old unsv all as specified and directed by the Engr-in-charge
M&L for removal of sewage and garbage from lamella clarifier including painting with one coat of red oxide and two coat of sysnthetic enamael paint and cleaning of fiver setting plated of lamella claffier complete all as specified and directed by Engr-in-Charge
M&L for emptying cleaning of sand media filter including welding work etc complete all as specified and directed by Engr-in-Charge
M&L for epoxy coating and sand media filter vessel internally suitable for STP of capacity 50 Cum per day complete all as specified and directed by Engr-in-Charge
M&L for replacement of filter media of sand media filter unit as described by Ion Exchage precipitation including testing of the same complete all as specified and directed by Engr-in-Charge
M&L for repalacement of existing gasket and fasterner of sand media filter unit including nut, bolt and washers all as specified and directed by Engr-in-Charge
M&L for emptying cleaning of activated carbon unit including welding work etc complete all as specified and directed by Engr-in-Charge
M&L for epoxy coating of activated carbon unit vessel internally suitable 50 CuM per day STP compelte all as specified and directed by Engr-in-Charge
M&L for replacement of filter media of activated carbon unit suitable 50 Cum per day capacity STP precipitation including testing of the same complete all as specified and directed by Engr-in-Charge
M&L for replacement of existing gasket and fasterner of active carbon unit including nut bolt and washers all as specified and as directed by Engr-in-Charge
Dismantling the unserviceable part of sewage treatment compressor blower and replace with new spare part including testing after completion all as specified and directed by Engr-in-Charge
M&L for servicing and over hauling of 7.5 HP induction motor including varnishing the stator and replacing the worn out drive end/driven end bearings and greasing and reassembling and testing complete all as directed at STP
Supply only the following spares for repairs of pump set of 7.5/10 HP capacity:-
Ball bearing
Impellers
PCV fan
Gland rope
M&L for servicing and over hauling of 2HP induction motor including varnishing the stator and replacing the worn out drive end/driven end bearings, greasing,reassembling and testing complete all as directed AT STP
M&L for servicing and over hauling of 1 HP induction motor including varnishing the stator and replacing the worn out drive end/driven end bearings, greasing, reassembling and testing complete all as directed
Supply only the following spares for repairs of Mono block pump set of 1.0/2.0 HP capacity:-
Ball bearing
Impellers
PCV fan
Gland rope
M&L for servicing and over hauling of 5 HP Blower motor including varnishing the stator and replacing the worn out drive end/driven end bearings, greasing, reassembling and testing complete all as directed AT STP
M&L for cleaning of sewage well including chocking of all incoming sewage line entering to sewage well for dewatering and desuldging of slurry of sewage pump
M&L for De- watering sewager cleaning machine of cap 3000 ltrs and depositing in MCD main hole at distance of 1 Km
M&L for Desludging of slurry using buckets and pulleys of depth total depth 7.5 mtr slurry average depth 2.5 mtr including depositing at a distance not exceeding 1000 mtr from starting point of sewager pump
M&L for scrapping of walls of well including and removing of materials not exc 50 mtr from starting point all as directed
M&L for de watering, De sludging and De silting of septic tanks, man holes, sludge chambers and the like by mannual or mechanical means depositing in tankers and disposal of the same at the place exceeding distance of 2 KM and not exc 3 KM where directed and sprinkling of bleaching on the disposed material 3 KG per Cum. (the rate includes transportation, bleaching )
Supply only Water treatment chemical Bio Clean Septic Powder available complete all as specified and directed
Supply only Water treatment chemical sodium hypo Chloride consisting 14% chlorine content diluted ClNao, complete all as specified and directed.
Supply only Water treatment chemical enzyme-2 (DAP consisting 18:46:0, 18% Nitrogen and water super phosphates 46% by minimum weight, packed in 50 Kg Polythene bag complete all as specified and directed.
Supply only Activated Carbon Filter media (ACF), Grade IV-900, size of layer as complete all as specified and directed. Makes :Granular/Norit as approved by GE Note: ACF Media combination quality & quantity shall be as directed & recommended by OEM only.
Supply only Activated sand Filter media (ASF), complete all as specified and directed. Note: ASF Media combination quality & quantity shall be as directed & recommended by OEM only. (a) Daily consumption quantity of each item viz, Chemical Bio Culture Bacteria solution, Sodium Hypochloride etc shall be submitted.Also daily consumption of all chemicals shall be recorded in register and maintained at site. (b) The manufacturer shall comply and guarantee the authenticity of the product by providing Test Certificate with Hologram which will be provided by the Authrorised Distributor at the distribution point for each Batch of Product delivered on their letter head. (c) The manufacturer will affix its hologram on each and every drum/container/bag. If the said product is delivered without the said hologram and/or it is seen to be tampered, then the product can be discarded as spurious.
M&F for MBBR fludised bio-media of vergin PPUV stablized material,cylindrical with external fins structure,black colour,22mm dia x 16mm height ,specific gravity 0.9 to 0.95 gms/sqcm all as specififed and as directed . Make: TP Aqua/Cool tech/Hydrotech as approved by GE
M&L Bactria culture for STP for developing MLSS and control odor complete all as directed by Engr-in-Charge. Make: Organic plus or its techno commercial equivalent make as approved by GE
Supply only TCCA 90% Chlorine (Trichloroisocyanuric Acid), effective content of chlorine % :>=90, Content of water % <= 0.5, PH Value of 1% Solution : 2.7 to 3.3, Granular Chlorine/Tblet in packing of 50 Kg complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for laying of mains / Poles, stay, cables and the like not exc 10 sq m on plan and not exc 1.5 m in depth and getting out in Hard / Dense soil complete all as specified and directed.
M&L for Supply, spread and filling approved river sand in cable trenches as cushioning of under ground cables including punning down of sand in layers complete all as specified and directed. Note:- Thickness of sand cushion after punning down will only be measured and paid.
Supply and lay un-reinforced precast concrete cable cover block, class LV, Type I flat size 250 x 150 x 40 mm laid dry in trenches over under ground cables complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Supply & laying only XLPE insulated PVC sheathed armoured heavy duty LT UG electric cable with aluminium conductor 1100 volt grade laid in trenches / fixed on wall / pole of cross sectional area of cable 16 Sqmm, 4 core including taking down old unserviceable cables complete all as specified and directed.
All as per item No 80 above but cross sectional area of cable 25 Sqmm, 3.5 core.
Supplying, errecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminum paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
S&F in replacement of LED flood fitting of 120W pressure die cast aluminium body , IP66 on existing pole with provisioning of 2 runs of cable PVC insulated Multi core unsheathed 1100 volts grade 4 Sqmm multistranded with aluminium conductor from fitting to junction box including provision of necessary brakets for fixing of fitting complete all as specified and directed. Make :- BAJAJ/HAVELLS/PHILIPS as approved by GE
S&F cable junction box thermoplastic body IP 66 , size 225mmx295mmx122mm suitable for helogen free and weather proof for out door installation with metric knockout for cable entry suitable for cable size 10-25 sqmm including 01 No SP MCB single pole of capacity 5 to 30 Amps 240 Volts and connecting up complete, MS clamp fabricated from 25x3mm MS flat iron with boltd all specified and as directed. Make: Hensil/Neptune/sintex as approved by GE
S&F in repairs CI foot valve leather sheet type / flange type suitable for 80 mm dia GI suction heavy duty includung replacement of nuts, bolts washers, gaskets and flanges etc. complete all as directed and specified by Engr-in-charge.
S&F in repairs CI foot valve leather sheet type / flange type suitable for 50 mm dia GI suction heavy duty includung replacement of nuts, bolts washers, gaskets and flanges etc. complete all as directed and specified by Engr-in-charge.
S&F in repairs PVC foot valve leather sheet type / flange type suitable for 50 mm dia GI suction heavy duty includung replacement of nuts, bolts washers, gaskets and flanges etc. complete all as directed and specified by Engr-in-charge.
Supply and laying of 3-layer PP-R Polypropylene random copolymer pipes SDR 7.4 & SDR 11 UV Stablised and antimicrobial welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings laid in trenches etc all as specified and directed of following sizes:-
32 mm bore.
40 mm bore.
50 mm bore.
75 mm bore.
110 mm bore.
S&F 32 mm PP-R Gate valves ( brass insert) as per requirement of the site complete all as specified and directed
S&F 40 mm PP-R Gate valves ( brass insert) as per requirement of the site complete all as specified and directed
S&F PVC pipes of pressure rating 6 kgf/cm2 laid in trenches complete all as specified and directed
25 mm bore.
40 mm bore.
S&F 63 mm PVC pipes of pressure rating 4 kgf/cm2 laid in trenches complete all as specified and directed
Supply and Fix 75 mm PVC pipes of pressure rating 4 kgf/cm2 laid in trenches complete all as specified and directed
S&F in existing line 15 mm stop valve cast copper alloy, screwed down , high pressure , with crutch handle, screwed both ends for iron pipe or union and fixed complete all as specified and directed.
S&F PP Ball Valve 40mm bore complete all as specified and directed.
S&F PP Ball Valve 63mm bore complete all as specified and directed.
S&F PVC Flush Valve 40mm bore complete all as specified and directed.
S&F PVC Flush Valve 63mm bore complete all as specified and directed.
M&L for emptying and cleaning/removal of hold up sewage from and sludge from rain water harvesting tanks including cleaning of gravel filter,Mesh chamber of Drip irrigation system all as specified and directed by Engr-in-Charge
M&L for servicing and over hauling of 3 HP Open well submersible pump set including varnishing the stator and replacing the worn out drive end/driven end bearings, greasing, reassembling and testing complete all as directed
M&L for servicing of Solar water Heater 200 LPD HHC System including changing of gasket, minor spares part as per requirement on site complete all as specified and directed.
Removing unserviceable and thermosate fixing the new one as requirement on site all as specified and directed.
M&L for servicing of 20 KW Solar power plant ,invertor, DC wiring including minor Spare part upto Rs 1000 each after disconnection the DC/AC Cable and resetting the plant after testing complete all as specified and directed.
S&F of Charge Controller unit (8 Amps or required on site) for Solar Light 28 Watt incl taking down old Unsv one complete all as specified and directed.
S&F of Solar LED Street light 28 Watt incl taking down old unsv one complete all as specified and directed.
omsai thermax engineers
Universal refrigeration and Engineering Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .