| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.7 LAccepted-AOC NO S 7 2ND CROSS 2ND MAIN KEB LAYOUT SANJAYANAGAR BANGALORE 560094 | BENGALURU URBAN | KARNATAKA | 560094 | L1 | Accepted-AOC Being lowest bidder and reasonable | |
| 2 | L2₹33.7 L+₹8.6 L (34.5%)Rejected-AOC | L2 | Rejected-AOC Not being lowest bidder | |
| 3 | L3₹37.6 L+₹12.5 L (50.1%)Rejected-AOC | L3 | Rejected-AOC Not being lowest bidder | |
| 4 | L4₹38.3 L+₹13.2 L (52.7%)Rejected-AOC | L4 | Rejected-AOC Not being lowest bidder | |
| 5 | L5₹40.2 L+₹15.2 L (60.6%)Rejected-AOC | L5 | Rejected-AOC Not being lowest bidder |
Tender Value
Refer Docs
EMD Value
₹74,000
Closing Date
23 Nov 2020, 6:00 pmClosed
GE I R nd D West Bengaluru
GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
COMPREHENSIVE MAINTENANCE AND REPAIRS TO STAND BY DG SETS INSTALLED AT LRDE, FAR FLUNG, PUMP HOUSES OF PHASE-I UNDER GE (I) R ND D (WEST) BENGALURU
2020_MES_381959_1
GE(I) R ND D (WEST)/BAN/40 OF 2020-21 8837E8
Open Tender
Civil Works
Item Rate
330 days
Benaluru
Refer NIT for details
8 documents required · 8 mandatory
₹500
Yes
GE I R nd D West Bengaluru
₹74,000
Yes
11 Dec 2020
24 Oct 2020
30 Nov 2020
26 Oct 2020
23 Nov 2020
10 Nov 2020
26 Oct 2020 - 9 Nov 2020
Amount
Item of execution
Maintenance including servicing of stand by DG Set 500 KVA at Technical Bldg, Sub Station (for lighting and power points) . Make of Engine : Kirloskar , Make of Alternator : Stamford, Model No : DV 10 TA for smooth functioning and carrying out complete check of governer, breather, etc., cleaning of DG sets externally, checking of AMF panel, batteries etc , carrying out periodic 'A' and 'B' checks as prescribed by manufactures (As per annexure 'A' to Sch ‘A’) checking of voltage, frequency, power factor etc. complete all as specified and as directed. NOTES:- The Quoted rate is deemed to be inclusive of the following :- (i) Overhauling of Radiator (ii) Calibration of FIP (iii) Diesel tank cleaning of DG Set etc., which shall be executed once in a contract period (iv) Labour element required for replacement of spares including testing catered for hereinafter in the BOQ, as per site requirement all as specified and as directed.
All as per Sl Item No. 1 here in before but 500 KVA DG Set at Tech Bldg Sub Station(for central AC plants) . Make of Engine : Kirloskar , Make of Alternator : Stamford, Model No: DV 10 TA
All as per Sl Item No. 1 here in before but 380 KVA DG Set at DRC Bldg Sub Station. Make of Engine : Cummins Sl No-25388161, Make of Alternator : Stamford, Model No: M-13C134575
All as per Sl Item No. 1 here in before but 320 KVA DG Set at RADL Sub Station. Make of Engine : Cummins , Make of Alternator : Stamford, Model No : NTA -855 G2-1
All as per Sl Item No. 1 here in before but 320 KVA DG Set at Service Centre - 1, . Make of Engine : Cummins , Make of Alternator : Stamford, Model No : NTA -855 G2-1
All as per Sl Item No. 1 here in before but 200 KVA DG Set at MAIN PUMP HOUSE . Make of Engine : KOEL , Model No : SL - 8800 TA.
All as per Sl Item No.1here in before but 166 KVA DG Set at Admin Sub Station. Make Engine : Cummins Make of Alternator : Jyothi Ltd. Model No : NT 743 GI
All as per Sl Item No. 1 here in before but 125 KVA DG Set at RTP, Make of Engine : Greaves , Make of Alternator : Kirloskar. Model No TD 246.
All as per Sl Item No. 1 here in before but 100 KVA DG Set at NEW PUMP HOUSE PH -III . Make of Engine : KOEL , Model No : 6BTA5.9 - G5.
All as per Sl Item No. 1 here in before but 110 KVA DG Set at APNFM Bldg, Make of Engine : Cummins , Make of Alternator : Kirloskar Ltd. Model No NTC 495
All as per Sl Item No. 1 here in before but 82.5 KVA DG Set at CAMEC Bldg, LRDE . Make of Engine : KOEL, Model No : 4R1040TAGI
All as per Sl Item No.1 here in before but 75 KVA DG Set at PUMP HOUSE PH - 3 . Make of Engine : KOEL , Model No : 6B-66 TC.
All as per Sl Item No. 1 here in before but 75 KVA DG Set at MLCP, Make of Engine : Kirloskar , Make of Alternator : Kirloskar Ltd.
All as per Sl Item No. 1 here in before but 63 KVA DG Set at HMT COLONY . Make of Engine : LEYLAND, Model ALU 400/1.
All as per Sl Item No. 1 here in before but 62.5 KVA DG Set at Service Centre-I, Phase-I. Make of Engine : Kirloskar, Make of Alternator : Kirloskar Ltd.
All as per Sl Item No. 1 here in before but 10 KVA DG Set at DAD HOSTEL . Make of Engine : KOEL , Model No : RB-33.
Supply only B Check kit for 500 KVA Kirloskar DG Set Model : DV 10 TA
Supply only B Check kit for 380 KVA CUMMINS DG Set Model : M 13C134575
Supply only B Check kit for 320 KVA CUMMINS DG Set Model : NTA 855-G2-1
Supply only B Check kit for 200 KVA koel DG Set Model : SL 8800 TA
Supply only B Check kit for 166 KVA CUMMINS DG Set Model : NT 743 G1
Supply only B Check kit for 125 KVA Greaves DG Set Model : TD 2V6
Supply only B Check kit for 100 KVA KOEL DG Set Model : 6B TAS.9-G5
Supply only B Check kit for 110 KVA CUMMINS DG Set Model : NTC 495
Supply only B Check kit for 82.5 KVA KOEL DG Set Model : 4R1040TAGI
Supply only B Check kit for 75 KVA KOEL DG Set Model : 6R-66 TC
Supply only B Check kit for 75 KVA KOEL DG Set , Make : Kirloskar
Supply only B Check kit for 63 KVA ASHOK LEYLAND DG Set Model : ALU 400
Supply only B Check kit for 62.5 KVA Kirloskar DG Set Model : HA 694 TC
Supply only B Check kit for 10 KVA Kirloskar DG Set Model : RB 33
Supply only Engine Oil SEA 15W-40W- Make :- (VOLVOLINE/IOC/CASTROL)
Supply only radiator coolant complete all as specified and as directed. Make :- (VOLVOLINE/IOC )
Servicing of Self Starter assembly of 24 Volt DC (Make - Delco Remi / Lucas TVS) by disconnecting from engine and dismantling the same, cleaning all accessories, renewal of worn out parts like brushes, contact plates, jumping leads and seals, re-varnishing the field coil, armature and reassembling the same, refitting the engine, testing and commissioning complete all as specified and as directed.
Servicing of Self Starter assembly of 12 Volt DC (Make - Delco Remi / Lucas TVS) by disconnecting from engine and dismantling the same, cleaning all accessories, renewal of worn out parts like brushes, contact plates, jumping leads and seals, re-varnishing the field coil, armature and reassembling the same, refitting the engine, testing and commissioning complete all as specified and as directed.
Power contactor 4 pole 150 A, coil rating 240 volts of 100 KVA DG Sets including dismantling old one complete all as specified and as directed.
Power contactor 4 pole 255 Amps, coil rating 240 volts of 110 to 125 KVA DG Sets including dismantling old one complete all as specified and as directed.
Power contactor 4 pole 325 Amps, coil rating 240 volts of 200 KVA DG Sets including dismantling old one complete all as specified and as directed.
Power contactor 3 pole 350 Amps, coil rating 240 volts of 166 KVA DG Sets including dismantling old one complete all as specified and as directed.
Power contactor 3 pole 160 Amps, coil rating 240 volts of 500 KVA DG Sets including dismantling old one complete all as specified and as directed.
Supply only switch mode power supply electronic battery charger panel mounting of capacity 24 volt 180 AH and dismantling old one complete all as specified and as directed.
Supply only switch mode power supply electronic battery charger panel mounting of capacity 12 volt 180 AH and dismantling old one complete all as specified and as directed.
HRC fuse 100/200/250 Amps DIN type in AMF panel including dismantling burnt unserviceable HRC fuse all as directed.
Supply only rubber hoses suitable for radiator of 500 KVA capacity DG sets including testing complete all as directed.
Supply only rubber hoses suitable for radiator of 300 to 380 KVA capacity DG sets including testing complete all as directed.
Supply only rubber hoses suitable for radiator of 200 to 225 KVA capacity DG sets including testing complete all as directed.
Supply only rubber hoses suitable for radiator of 30 to 125 KVA capacity DG sets including testing complete all as directed.
Battery lead copper conductor cable, PVC unsheathed multi stranded of size 25 sq.mm, single core along with lug connector at one end and terminal at another end including tinning 02 Nos (1.5 RM each lead) and 01 No (60 cm lead) along with terminals at both ends including tinning complete all as specified and as directed.
Supply only fan belts suitable for DG sets of capacity 500 KVA as per the existing sample and size all as directed.
Supply only fan belts suitable for DG sets of capacity 300 to 380 KVA as per the existing sample and size all as directed.
Supply only fan belts suitable for DG sets of capacity 200 to 225 KVA as per the existing sample and size all as directed.
Supply only fan belts suitable for DG sets of capacity 100 to 125 KVA as per the existing sample and size all as directed.
Supply only fan belts suitable for DG sets of capacity 30 to 82.5 KVA as per the existing sample and size all as directed.
Supply only flexible fuel pipe suitable for DG Sets of capacity 500 KVA as per the existing sample and size all as directed.
Supply only flexible fuel pipe suitable for DG Sets of capacity 300 to 380 KVA as per the existing sample and size all as directed.
Supply only flexible fuel pipe suitable for DG Sets of capacity 200 to 225 KVA as per the existing sample and size all as directed.
Supply only flexible fuel pipe suitable for DG Sets of capacity 100 to 125 KVA as per the existing sample and size all as directed.
Supply only flexible fuel pipe suitable for DG Sets of capacity 30 to 82.5 KVA as per the existing sample and size all as directed.
Supply only Automatic Voltage Regulator with voltage / stability / Fro adjustment for 225 to 500 KVA DG Set all as per Kirloskar, Cat Part No. F6.814.11.0.00. AVATVAR30 or equivalent model in other makes specified complete all as specified and as directed.
Supply only Automatic Voltage Regulator with voltage /stability/Fro adjustment for 10 to 200 KVA DG Set all as per Kirloskar, Cat Part No. 2H.811.32.0.00 TVAR20 or equivalent model in other makes specified complete all as specified and as directed
Maintenance free Lead acid battery 12 volt 180 AH complete all as specified and as directed.
Sealed Maintenance Free Generator starting pulse Battery system 24 volts, Factory charged of capacity 32 Ah complete all as specified and as directed.
Supply only Mild steel fan blade suitable for radiator of 500 KVA DG set complette all as specified and as directed.
Supply only Mild steel fan blade suitable for radiator of 200 to 380 KVA DG set complette all as specified and as directed.
Supply only Mild steel fan blade suitable for radiator of 40 to 125 KVA DG set complette all as specified and as directed.
Supply and fix on-load change over switch in sheet steel enclosure of 400 Amps complete all as specified.
Supply and fix on-load change over switch in sheet steel enclosure of 630 Amps complete all as specified.
Supply, install and testing of ACB 4 P, 415 V, with thermal magnetic release (Manual dawout type) of capacity 630 Amps, including taking out one complete all as specified and as directed.
Supply, install and testing of sliding gate motor input voltage 230 V, AC input power 370 W, speed of open 12 m / minute, output torque 20 Nm, with standard accessories viz., Remote controller - 2 Nos, Clutch keys -2 Nos for manual operation, mounting base plates, etc, Gear box etc., including taking down and remitting the same in storeyard of AGE E/M R&D West, complete all as specified and as directed.
Supply only distilled water for topping up in batteries of DG set complete all as directed.
Supply only Restro plus rust remover all as directed.
Sahara Engineers
B5BUILDING SOLUTIONS
H S S ENGINEERS AND CONTRACTORS
kamadhenu Electricals
Lucky Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .