Executive Engineer
Office of the Executive Engineer, Purba Medinipur Electrical Division, P.W.Dte, Tamluk, Hospital More
Electrical Installation work for proposed District Court at Tamluk, in the district of Purba Medinipur----SITC of Fire Detection System.
2020_WBPWD_270928_1
PWD/EE/PMED/eNIQ-09/19-20/4th Call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Tamluk
Please refer Tender documents.
5 documents required · 5 mandatory
₹35,000
Tamluk
2 Sept 2020
17 Feb 2020
5 Mar 2020
17 Feb 2020
2 Mar 2020
17 Feb 2020
20 Feb 2020
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base as required.Temp Range of this Detector shall be confined between (-) 5 Deg C to (+) 50 Deg C, minimum Ingress Protection should be IP:40 and Relative Humidity should be not less than 95%. (Approval standards:VdS, EN54; (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. Temp Range of this MCP shall be confined between (-) 5 Deg C to (+) 50 Deg C, minimum Ingress Protection should be IP:52(Approval standards:VdS, EN54; (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90db) cum strobe (strength of light 10cd) complete with inbuilt isolator as required.Temp Range of this Hooter Cum Strobe shall be confined between (-) 5 Deg C to (+) 50 Deg C, minimum Ingress Protection should be IP:42 (Approval standards:VdS, EN54; (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supply, Installation,Testing & Commisioning of Analogue Addressable Intelligent Heat Detector with fixed & rate of rise temperature function with decentralise intelligence, soft addressable type, with inbuilt fault isolator as per NFPA style 7 wiring complete with base as required.Temp Range of this Detector shall be confined between (-) 5 Deg C to (+) 50 Deg C, minimum Ingress Protection should be IP:40(Approval standards:VdS, EN54; (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supply, Installation, Testing & Commissioning of Addressable monitor module complete with inbuilt isolator as required. shall be confined between (-) 5 Deg C to (+) 50 Deg C for monitoring of pressure switch, flow switch, pump running etc. (Approval standards:VdS, EN54; (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supply & Laying of 2 Core 1.5 sq.mm FRLS copper Cable (Make. MEM / Polycab/ KEI/Glostar) with 20mm NB PVC rigid conduit pipe on the surface of the wall. (Make : Precission-Medium) (Make: KEI/Havells/RR)
Supply, Installation, Testing & Commissioning of Response Indicator for Alarm Indication of above False Celling Detector; (Make: Siemens / Honeywell / Securiitol / Bosch)
Supply, Installation, Testing & Commissioning of Intelligent Soft Addressable Microprocessor Based 2 Loops Fire Alarm Control Panel,panel shall be 120 Detectors or Devices in any flexible combination and shall be able to give pin point location of all fire/fault conditions. Vendor should consider necessary hardware for Panel to Panel Networking through Fiber Optics Cable. The Panel shold have provision for future expansion & integration with Central Fire Graphics Monitoring System through open protocol like Modbus or TCP/IP Gateway. The panel shall have in built rectifier, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. (Make: Siemens / Honeywell / Securiton/ Bosch/ Jhonson Control)
Supplying & Laying 4 C multimode Cable through 19mm PVC rigid conduit (FRLS) on surface of the wall. (Make: RR/Havells/KEI) For networking between two Fire panels.
Supply & Installation of incoming switch. (Make: Molex / D-Link/Matrix)
GLYPTIC
SAFE GUARD (INDIA)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .