Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.0 CrAccepted-AOC | ₹24.0 Cr | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹24.8 CrRejected-Finance | ₹24.8 Cr | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹25.5 CrRejected-Finance | ₹25.5 Cr | L3 | Rejected-Finance Not Being Lowest |
| 4 | L4₹26.2 CrRejected-Finance | ₹26.2 Cr | L4 | Rejected-Finance Not Being Lowest |
| 5 | L5₹26.5 CrRejected-Finance | ₹26.5 Cr | L5 | Rejected-Finance Not Being Lowest |
Tender Value
₹24.5 Cr
EMD Value
₹15 L
Closing Date
25 Oct 2023, 6:00 pmClosed
CE Bathinda Zone
HQ Chief Engineer Bathinda Zone Bathinda Mil Stn - 151004
PROVN OF KLP (PHASE-I OF TWO PHASES) UNDER GE (P) BATHINDA
2023_MES_617587_1
CE BTZ/BTD/TOKEN-06 OF 2023-24
Open Tender
Civil Works
730 days
Bathinda
As per NIT
9 documents required · 9 mandatory
₹3,000
GE (P) Bathinda
₹15 L
Yes
20 Nov 2023
7 Sept 2023
27 Oct 2023
7 Sept 2023
25 Oct 2023
11 Oct 2023
Amount
Lump sum price worked out by the tenderer for “BUILDING /STRUCTURE WORKS" as listed in Schedule ‘A’ Section - I
Sch 'A' Sec - II, (INTERNAL ELECTRIFICATION WORKS)
Material and labour for concealed Point wiring for one light point/fan point /bell point controlled by one switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches/ socket / regulator etc, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch/socket/regulator etc complete all as specified and as directed. (switch, socket, regulator shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
All as per above Srl item No. 03 but for one socket out let 5/6 Amps point controlled by one switch (on same board) complete all as specified and as directed by Engineer-in-charge. (switches, sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
All as per above Srl item No. 03 but for one socket out let 5/6 Amps point controlled by one switch (on independent board and not below the any other switch board) complete all as specified and as directed by Engineer-in-charge. (switches , sockets etc. shall be measured and paid separately under appropriate item of BOQ/Sch A).
Material and labour for concealed Point wiring for one light point controlled by two Nos- two way switch (using red, black and green colour wires as colour coding) complete with 1.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switch, including provn of 1.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switches complete all as specified and as directed. (switches shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate. ).
Material and labour for concealed Point wiring for one socket out let 15/16 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 2.5 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 2.5 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch, socket complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate).
Material and labour for concealed Point wiring for one socket out let 25 Amps point controlled by one switch (on independant board) (using red, black and green colour wires as colour coding) complete with 4 Sqmm (nominal cross section area) single core FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) drawn through and including PVC conduit 20mm dia (medium duty, ISI marked) with all fittings and all accessories i.e. pipe bend, pipe hook, elbow, junction boxes etc., including Pressed steel powder coated sunken terminal box suitable for modular switch socket (Min 50mm deep and 1.6mm thick sheet, suitable size ) concealed in wall, including inner and outer plates (cover plate) suitable for fixing the modular switches / socket, including provn of 4 Sqmm single core FRLSH PVC insulated multi strand copper conductor wire continues as earth wire connected to earth dolly etc. including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3), including fixing of switch, socket complete all as specified and as directed. (switch, socket shall be measured and paid separately under appropriate item of BOQ as supply only but cost of labour for fixing the same shall deemed to be included in the unit rate).
Supply and hanging /fixing ceiling fan 1200 mm sweep AC Supply (Input Voltage Range ; 120 to 280V), BLDC type, 5 star rated, BEE and ISI Marked super enamelled, copper winding of 'B' class insulation, single phase, maximum 30W (± 10%), Temperature rise 40 degree maximum without remote with and including capacitive regulator, 03 No blades, down rod including accessories, white colour, total harmonic less than 10%, 5 speed, hanging in position including making connection with flexible cord three core twisted copper conductor of suitable size from ceiling rose to fan complete all as specified. Note :- (i) Serial Number as issued by Engr-In-Charge of celing fan and GE Office name shall also be written on fan with red colour permanent marker and fixing of regulator on switch board, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50Hz, 900RPM, size 300mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement in wall and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing exhaust fan (heavy duty) steel body, AC single Phase 230V, 50 Hz, 900RPM, size 450mm sweep with blades and frame including self closing GI louvers off mode protection against birds etc mounted in suitable opening arrangement in wall and connecting up and including three core PVC Insulated PVC Sheathed copper conductor flexible cable 24/0.2mm drawn in flexible PVC conduit and hanging on wall with 4 Nos steel fastners 10mm dia 100mm long and making good the disturbed surface complete all as specified and as directed by Engineer-in-charge. Note :- (i) Serial Number as issued by Engr-In-Charge of fan and GE Office name shall also be written on fan with red colour permanent marker, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 4 Way 415V, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCCB/MCB shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 250 Amp rated bus bar) VTPN, 8 Way 415V, suitable for mounting MCCB/MCB, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCCB/MCB shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) TPN, 6 Way 415V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) TPN, 4 Way 415V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 12 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 8 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be same make as MCBs, DB shall be provided with level marking indicating the incoming and outgoing circuits on always as specified. The DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge. Note :- MCB/Isolator etc shall be measured and paid separately under appropriate item of BOQ.
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 6 to 32 Amps, FP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 40 Amps, FP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 63 Amps, FP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 6 to 32 Amps, TP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 415 volts AC supply, 63 Amps, TP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 6 to 32 Amps, DP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, DP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 63 Amps, DP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 06 to 32 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 40 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing MCB ‘B’ curve suitable for 230 volts AC supply, 63 Amps, SP with over load and short circuit protection and rupturing capacity not less than 10 KA, fixing in DB complete all as specified and as directed by Engineer-in-charge
Supply and fixing blanking plate suitable for any type of DB complete all as specified and as directed by Engineer-in-charge.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 4 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 6 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 25mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 6 Sqmm single core (05 run i.e 4 runs for main 3 phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 32mm dia minimum (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Five runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 10 Sqmm single core (05 run i.e 4 runs for main 3 phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 32mm dia minimum (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Five runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Supply and fixing LED tube light fitting polycarbonate housing 1 x 18 Watt, appx 4 feet long, with decorative box linear, housing environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to tube fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts. (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) LED Driver of the same make as of the luminaire. (h) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (j) Surge protection minimum 2.5 kV. (k) CCT : Minimum 6000K (l) CRI : Minimum 80 (m) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED light fitting 1 x 10 Watt, appx 2 feet long with decorative ultra ceiling square profile linear LED lighting fixture with extruded polycarbonate environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) CRCA pre coated housing with plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : Minimum 6000K (m) CRI : Minimum 80 (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing LED light fitting 1 x 5 Watt, appx 1 feet long with decorative ultra ceiling square profile linear LED lighting fixture with extruded polycarbonate environment friendly, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 5°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Current THD Max10% and voltage THD max 5% (f) IP rating : IP-20. (g) CRCA pre coated housing with plastic end cap. (h) LED Driver of the same make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection minimum 2.5 kV. (l) CCT : Minimum 6000K (m) CRI : Minimum 80 (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing energy efficient LED security light fitting of 25W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street luminaire, with driver, including electric connection with using 2 core flexible copper conductor cable 1Sqmm from ceiling rose to light fitting, fixing the light fitting with new bracket made out of GI tubing light grade 25mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 25x3 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP66. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Minimum 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing surface mounted LED light fitting with wide light window for maximised glare free output complete fitting with separate electronic driver and high brightness LED 34/36 Watt flat panel of size 2x2 feet, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting and all accessories with following specifications and all as directed:- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP20. (g) CCT : 6500K (h) CRI : Morethan 80 (j) CRCA pre coated housing. (k) LED Driver of the make as of the luminaire. (l) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (m) Surge protection minimum 3 kV. (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing recessed LED ceiling light fitting with wide light window for maximised glare free output, suitable for ceiling cutout 595x595mm modular grid/POP ceiling finishes complete fitting with separate electronic driver and high brightness LED 34/36 Watt flat panel of size 600x600mm, including electric connection with using 2 core flexible copper conductor cable 23/0.00076 from ceiling rose to light fitting, complete fitting and all accessories with following specifications and all as directed:- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 45°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP20. (g) CCT : 6500K (h) CRI : Morethan 80 (j) CRCA pre coated housing. (k) LED Driver of the make as of the luminaire. (l) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (m) Surge protection minimum 3 kV. (n) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Material and labour for concealed wiring for TV antenna connection complete with coaxial RG-6 heavy duty PVC insulated sheathed cable with copper conductor having single strand of 0.7 mm dia and a aluminium wire net drawn through PVC conduit complete all as specified and as directed. (TV antenna connection socket outlet, terminal box, conduit with fittings shall be measured and paid separately under appropriate item of BOQ).
Material and labour for Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing and including modular type (1 module) 2 pin TV antenna connection socket outlet round flush type duly marked with symbol of TV and making good disturbed surfaces of walls by using CM (1:3) complete all as specified and as directed.
Material and labour for concealed wiring for telephone connection complete with PVC insulated sheathed cable with copper conductor having single strand of 0.4 mm dia twin core (one pair) taped for telephone wiring drawn through PVC conduit complete all as specified and as directed. (Telephone connection socket outlet and terminal box, conduit with fittings shall be measured and paid separately under appropriate item of BOQ).
Material and labour for Pressed steel powder coated sunken terminal box of size 100mm x100mmx50mm concealed in wall, including inner and outer plates (cover plate) suitable for fixing and including modular type (1 module) telephone connection socket outlet flush type duly marked with symbol of telephone and making good disturbed surfaces of walls by using CM (1:3) complete all as specified and as directed.
Material and labour for concealed in wall rigid non matallic PVC conduit 20mm dia (medium duty, ISI marked) for telephone wiring inclusive of all fitting & accessories such as tees, bends, elbow, reducer, junction box, pipe hooks etc, bell mouth tube ends including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed.
Material and labour for concealed in wall rigid non matallic PVC conduit 25mm dia (medium duty, ISI marked) for cable TV wiring inclusive of all fitting & accessories such as tees, bends, elbow, reducer, junction box, pipe hooks etc, bell mouth tube ends including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed.
Supply only modular switch 6Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular switch 6/16Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular switch 25Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular switch 6Amps, single pole, two way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Bell Push switch, 6Amps, single pole, one way (1 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Socket outlet multipurpose type 6 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Socket outlet multipurpose type 6/16 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
Supply only modular Socket outlet multipurpose type 25 Amp, flush type (2 module) complete all as specified and as directed by Engineer-in-charge.
Supply and fixing Batten holder polycarbonate cased body (B22 base), top line series, with back plate complete all as specified and as directed.
Supply and fixing Ceiling Rose, polycarbonate, isolated body, surface bakelite 3 terminal, 240 volts, 5/6 Amp complete all as specified and as directed.
Supply and fixing electric calling Bell Ding Dong type, AC 230 Volts single pole including making elctric connection complete all as specified and as directed by Engr-in-charge.
Supply and fixing tempra plug and socket DB suitable for 3 pole, netural and earth (3P+N+E) as per IEC-61439-3, flush/surface mounting having netutaral link and including MCB TP 63 Apm complete all as specified and as directed by Engr-in-charge.
Material and labour for concealed Flame proof Point wiring (using red, black and green colour wires as colour coding for single phase circuits) complete with 1.5 Sqmm (nominal cross section area) FRLSH PVC insulated unsheathed and multi strand copper conductor cable 1100 volt (ISI marked) for main point and for continues as earth wire connected to earth dolly etc. (Phase, netural and earth wire) drawn through and including ERW rigid conduit stove enamelled conduit with all flame proof fittings and all flame proof accessories (duly tested by CMRI) i.e. pipe bend, union socket, reducer, elbow, pipe hook, connectors, junction box, insepction elbow etc , for light/fan points including cutting chases in wall and making good disturbed surfaces of walls/ceiling/floors etc. by using CM (1:3) complete all as specified and as directed. Note :- (i) MCB and DB shall be measured and paid separately under appropriate item of BOQ).
Supply and fixing CMRI certified flameproof 1x16 Watt LED tube light fitting, well glass luminaire suitable for RF LED lamp, recommended for Gas/Vapour group of IIA & IIB and zone 1 & 2, IP65 protection, Epoxy finish LM6 die cast aluminium housing with heat resistant toughened glass, including inbuilt electronic driver, 2 kv surge protection, internally pre-wired, LED lamp, connector block etc complete with all other accessories including making electric connection connecting with twin core twisted flecible copper conductor cable and connector block, tobe fixed flush to wall/ceiling surface complete all as specified and as directed by Engineer-in-Charge. Specification for LED luminaire (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : IP65. (g) CRI : Morethan 80 (h) CCT : 6500 K. (i) LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended)
Supply and fixing CMRI certified flameproof exhaust fan of size 300mm, single phase, with 1440 RPM , 0.25 HP, 1120 CFM, complete with all other accessories including making electric connection connecting with twin core twisted flecible copper conductor cable and connector block, complete all as specified and as directed by Engineer-in-Charge.
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section - III (Part-I)
Sch 'A' Sec - III (Part-II), (INTERNAL WATER SUPPLY WORKS)
Supply and fixing health faucet fancy type, CP including 1.2 meter long 8mm dia flexible tube and including wall hook and fixing material complete all as specified and as directed by Engineer-in-charge.
Supply & fixing CP connection 15 mm size of length 450 mm with CP nuts and fixed complete all as specified and as directed by Engineer-in-charge.
Subtotal
Lump sum price worked out by the tenderer for “ROAD, PATH & CULVERT WORKS" as listed in Schedule ‘A’ Section -IV (Part-I)
Sch 'A' Sec - IV (Part-II), (ROAD, PATH & CULVERT WORKS)
Supply and laying/fixing 60 mm thick (M-35 grade) precast interlocking tile/paving block factory casted (made by using PVC/ Rubber moulds on Vibrating Table Machine) using grey cement and no pigment, any shape haxagon / trigular / zigzag / I-shaped etc, as directed, confirming to relevant IS, laid over and including 25mm thick layer of sand cushining and filling the interstices etc with sand complete all as specified and as directed.
Material and labour for Thermo plastic paint road marking 2mm thick painting (lines, dashes, arrows, letters etc) with road safety spikeries glass beads @ 8% by weight including preparation of new or previously treated road surfaces and applying paint by using special applicator machine with heating arrangement complete all as specified and as directed.
Supply and fixing metal tubular Delineator made out of ABS round body fitted with 02 Nos 65mm dia highly reflective reflectors made out of PMMA and mounted on 45/50mm dia mild steel pipe 600mm height duly podwer coated and thermo plastic elastomer 3 bands of green, red and yellow reflector radium tape of 25mm wide strips with anti theft steel net for reflector protection including embedding in PCC (1:2:4, type B1) block size 150x150x300mm including necessary earthwork complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “AREA DRAINAGE WORKS)" as listed in Schedule ‘A’ Section -V (Part-I)
Sch 'A' Sec - V (Part-II), (AREA DRAINAGE WORKS)
Material and labour for Pre-cast factory made RCC drain of size and shape as directed by GE alongwith male and female ends for proper joining, made of 75mm thick RCC M-30 using 20mm graded aggregate, duly embeded two Nos socket for hoisting including form work etc, hosting and placing at site and jointed in CM (1:4) to form uniform length and fair finish to drain upto 80cm girth (width measured @ Avg of inner and outer girth) complete all as specified and as directed by Engineer-in-Charge. Note : Reinforcement shall be measured and paid separately under appropriate item of this Sch.
Subtotal
Lump sum price worked out by the tenderer for “SEWAGE DISPOSAL WORKS" as listed in Schedule ‘A’ Section - VI (Part-I)
Sch 'A' Sec - VI (Part-II), (SEWAGE DISPOSAL WORKS)
Supply and laying DWCPE (SN8) drain pipes 150mm nominal dia as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Supply and laying DWCPE (SN8) drain pipes 200mm nominal dia as per IS-16098 (Part-II), laid in trenches on and including bed 100mm thhick beding comprising of well compacted clean poorly graded gravel, gravel/sand mixture with little or no fines to required slope, including all accessories/fittings/jointing ring, jointing and testing complete all as specified and as directed by Engineer-in-Charge. Note : Excavation, earth work and pedestal /anchorage if required shall be measured & paid separately under appropriate item of BOQ/Sch A.
Supply and fixing LLDPE septic tank of capacity 5 users (minimum 2000 ltr) designed to carry sewage and sludge water, including excavation and earth work in any type of soil, installed over and including 100mm thick PCC (1:4:8) type D-2 including all necessary fittings for connecting to inlet and out let, complete all as specified and as directed.
Soakage well of size 1.20 m dia and 3.00 m effective depth, excavation in any type of soil, foundation in PCC 1:3:6, walls of random rubble dry and coursed stone block masonry with top ring of M25 concrete including RCC cover slab in M25, inlet pipes of RCC/DWC, complete filled with brick bats, complete all as shown on drawing, specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “SECURITY FENCING AND GATE WORKS" as listed in Schedule ‘A’ Section - VII
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY AND SUPPLY OF TREATED WATER WORKS" as listed in Schedule ‘A’ Section - VIII (Part-I)
Sch 'A' Sec - VIII (Part-II), ( EXTERNAL WATER SUPPLY AND SUPPLY OF TREATED WATER WORKS)
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9, bore 150mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-9, bore 100mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-7, bore 200mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-7, bore 150mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supplying, laying, jointing and testing Ductile iron pipe (ISI marked) class K-7, bore 100mm, confirming to IS : 8329-2K, spigot & socketed ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including rubber tyton joints (Push-on joint) complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Supply and fixing cast iron sluice valve 150 mm dia with flanged ends class PN 1.0 (ISI marked) confirming to IS:14846-2000, drilled type, steel spindle, CI gate with brass ring, iron wheel handle, suitable for CI/DI pipe line, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 200 mm dia with flanged ends class PN 1.0 (ISI marked) confirming to IS:14846-2000, drilled type, steel spindle, CI gate with brass ring, iron wheel handle, suitable for CI/DI pipe line, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing cast iron sluice valve 100 mm dia with flanged ends class PN 1.6 (ISI marked) confirming to IS:14846-2000, drilled type, steel spindle, CI gate with brass ring, iron wheel handle, suitable for CI/DI pipe line, complete including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing 100 mm bore cast iron body foot valve flanged ends swing type, confirming to IS: 4038 (ISI marked) including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing 100 mm bore cast iron body non return valve (NRV) with bypass arrangement, confirming to IS 5312 (ISI marked), both flanged ends and drilled, including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Supply and fixing 50 mm bore cast iron body non return valve (NRV), confirming to IS 5312 (ISI marked), both flanged ends and drilled, including jointing material such as nuts, bolts, washers and rubber sheet insertion at both ends etc complete all as specified and as directed.
Supply and fixing cast iron double air relase valve isolating type (ISI marked), flanged type and drilled, confirming to IS-14845, suitable for 80mm bore pipe including jointing material such as nuts, bolts, washers and rubber sheet insertion 3.0mm thick at both ends etc complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 200 X200 X400 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 120 X120 X120 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 90 X90 X90 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Material and labour for Construction of brick masonary valve pit chamber size 75 X75 X75 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC (1:2:4) type B-1 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:3) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed.
Supply and fixing DI fitting upto 200 mm bore pipe line for reducing/bends (any type radius and angle) tapers any type, straight, bend, increasing decreasing or double socket extra Tee pieces single branch Y 'Junction' double branch cross collers cap etc complete all as specified and as directed. Note:- Make of DI fittings shall be same make as DI pipe or as per recommendation of DI pipe manufacturer.
Supplying, installing, commissioning and testing of Horizontal split case cetrifugal pump set 1450 RPM having an output of minimum 1300 LPM at a head of 50 mtr coupled to 3 phase 415 volt squirel case induction motor of adequate capacity complete with and including following :- (a) Necessary wiring for interconnection between starter & pump set with 1100 volt rated FR PVC insulated unarmoured cable of minium 10 sqmm 3 core copper cable (b) Single phase preventer (current sensing type) (c) Necessary light grade GI pipe protection for cabling from pump set to LT panel. (e) Bourden pressure gauge 100mm dia pressure rating 0-10 kg/Sqcm. (f) MS pipe flanged type class B of size 100 mm bore upto foot valve from suction end of pump. (g) PCC foundation in type B-2, 1:2:4 using 20mm graded aggregate, 20cm above ground level and 30cm below grond level including grouting of eye bolts nut etc. for pump set of adequate size or as per manufacturers recommendations. Note: All other items/material required for fixing pumpset shall be included in cost quoted. (ii) Foundation drawing shall be approved by GE before fixing the pump set.
Supplying, installing, commissioning and testing of Non-clog vertical Submersible pump for handling sewage water and having discharge of minimum 141 LPM and 21M head, 415 Volts, 50 Hz, 2900 RPM, 'F' Cl insulation, IP 68 protection, 40 degree centigrade operating temperature with CI Impellor, CI motor body, CI pump housing, stainless steel shaft and delivery pipe size of 50mm including hoisting submersible sewage pump into sewage collection tank using suitable stainless steel heavy duty (Gde 316) chain and anchoring with hook on top of sewage tank with necessary nuts, bolts, washers etc complete all as specified and directed.
Material and labour for jointing of Steel water tubing of 50 mm bore dia ISI marked heavy grade galvanised including tube fittings Viz Tees, Socket bends elbows, union nipple etc screwed and socketed joints for hanging of submersible pump including clamps complete all as specified and as directed.
Supply and fixing PVC Insulated overall sheathed 3 core submersible flat copper cable 1100 volts grade 2.5 sqmm including PVC conduit of suitable size with accessories all as specified and directed.
Supplying, installing, commissioning and testing complete of manufacturer or OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven Generating Set, radiator cooled, with AMF panel capable of delivering 40KVA (32 KW) or nearest higher rating 415 volts AC 3 phase, 4 wire system of supply, 50Hz. The DG set shall consist of diesel engine coupled through flexible coupling to matching alternator and mounted on foundation pads on common base frame in the CPCB approved acoustic enclosure (the complete set confirming to and test certificate as per CPCB-II norms and as specified) with AMF control panel standardised by manufacturer, inbuilt fuel tank, flexible exhaust pipe, incl necessary PCC foundation as per manufacturer instructions complete all as specified and as directed and comprising with the following:--
Engine (Prime mover) : Diesel Engine 1500 RPM of suitable BHP as recommended by manufacturer (at rated RPM), water cooled, 4 cylinder, inline, 4 stroke, confirming to ISO 3046 / BS 5514 with turbo charged air cooled , 1x88 AH 12 Volts batteries start, mechanical FIP, Electronic Governor, pulse tuned exhaust manifold, stainless steel exhaust flexible connection complete with flywheel and all standard fittings/fixture as per manufacturing practice including suitable engine control panel with tachometer, lub oil temp and pressure gauge, water temp starter, dynamo, fuel tank, fuel and lube oil filter, Dry type replaceable paper element air cleaner etc.
Alternator : AC alternator, self-excited, self-regulated, self-ventilated, brushless design, confirming to BS 2613/5000, 3 phase, 415 volts, 4 wire rated line current min 56 Amps output at PF 0.8, 1500 RPM, insulation class ‘H’ enclosure IP 23 complete with AVR with ± 1% voltage regulation, directly coupled to and matched with engine.
Anti-vibration pad for mounting engine alternator assembly on the base frame/plate.
Base frame/plate made out of structural steel as per manufacturer’s recommended design/specifications.
Acoustic Enclosure : Engine Alternator assembly mounted on AV mounts with silencer and SS exhaust bellow suitable optimised to meet stringent noise emission standards as laid down by MOEF/CPCB. Base rail with draw out type fuel tank provided with drain plug, air vent, inlet and out let connection, level indicator, manhole etc.
01 No 12 volt x 88 AH maintenance free batteries complete with suitable size copper lead.
AMF control panel : RAL 9003 white powder coated control panel made out of CRCA sheet provided with AMF system (automatic starting of main failure) and Start Stop push button for manual operating, provide with MCCB of suitable rating with short circuit protection, controller which display voltage, current, KW, PF, Frequency, KWH, lube oil pressure, indicating lamps for ‘load ON’ and ‘set running’ current transformer of suitable rating etc, aluminium bus bar of suitable rating with incoming and outgoing termination complete all as per manufacturer’s recommended design/specifications.
The contractor shall supply following maintemance spare part and tool kit for the generator set :- (i) Fuel filter - 02 Nos (ii) Lube oil filter - 01 No (iii) Air filter - 01 No (iv) V-belt - 02 Sets (v) Tool kit socket set - 01 No (vi) DE Spanner set - 01 No (vii) Ring Spanner set - 01 No (viii) Clamp meter - 01 No
Note :- (i) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted. (ii) DG set should be sound proof as per latest policy (iii) Cost of maintenance free batteries as per recommendations of manufacture shall deemed included in unit rate quoted by contractor (iv) Cost of PCC foundation as per recommendations of manufacturer shall deemed included in unit rate quoted by contractor. (v) Initial filling of lubricating oil/coolant and fuel required for testing of DG set shall be provided by the contractor without any extra cost. (vi) Exhaust from DG set shall be as per latest CPCB [II] norms. Alternatively emission control device within overall cost quoted shall be provided (vii) Pre commissioning test shall be carried out by rep of Accepting Officer. All necessary equipment’s, consumables and T&P required for successful completion of the test shall be arranged by the contractor and cost for the same shall deemed included in unit rate quoted by contractor.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (indoor type for 415 volts, 3 phase, 4 wire AC supply, free standing, floor mounting) cubical type suitable size made out of CRCA epoxy powder coated 2mm thick sheet, factory fabricated having modern fabrication and testing process process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front open able hinged independent door for each compartment and common open able hinged door from rear side, with locking arrangement (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on pedestal frame made out of MS channel of size ISMC 50mm, both side properly welded and all vertical corner grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) including painting to pedestal frame with spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer. Danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, copper bus bar 150 Amps
MCCB 100 Amps, Four pole, adjustable thermal magnetic protection, 16 KA, 415 V AC supply - 01 No (Incoming)
MCCB 63 Amps, Four pole, adjustable thermal magnetic protection, 16 KA, 415 V AC supply - 02 No (Outgoing)
MCB SPN 10 Amp C curve, 10 KA capacity - 01 No
Single phase preventor - 02 No
On load Change over switch 4 pole of current raring 63 A (open execution type) - 01 No
Fully automatic Star-delta starter 25-30 HP - 02 Nos
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 50 Amps
MCCB 20 Amps, TP, adjustable thermal magnetic protection, 16 KA, 415 V AC supply - 01 No (Incoming)
MCB 10 Amps, TP, C series, 10 KA, AC supply - 02 No (for DOL starters)
Power Contactor, 9A - 02 No (For DOL Starters)
Overload Thermal relay (4 - 6A) - 02 No (For DOL Starters)
Indicator LED for ON and OFF Indication - 02 No (For DOL Starters)
Push button START & STOP - 02 No (For DOL Starters)
Rotary Switch 3 Phase - 01 No (For DOL Starters)
Ultra sonic Non-contact type water level sensor (for sewerage water) with PLC - 01 No
Single phase preventor - 02 No
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supplying, laying, jointing and testing (for header) Ductile iron pipe (ISI marked) class K-9, bore 200mm, confirming to IS : 8329-2K, flanged ends centrifugally cast, with cement mortar lining inside and metallic zinc coating with finishing layer of bituminous paint on outside the pipe, including jointing material such as nuts, bolts, washers and rubber sheet 3.0mm thick etc complete all as specified and as directed. Note : (i) Earth work, DI specials/ fittings shall be measured and paid separetly. (ii) Test Certificate for pipes from manufacturer shall be produced. No payment shall be entertained without Test Certificate.
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION, LIGHTNING PROTECTION, HIGH MAST LIGHT AND ELECTRIC SIREN WORKS" as listed in Schedule ‘A’ Section - IX (Part-I)
Sch 'A' Sec - IX (Part-II), (EXTERNAL ELECTRIFICATION, LIGHTNING PROTECTION, HIGH MAST LIGHT AND ELECTRIC SIREN WORKS)
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing wire of size 4 mm dia by means of GI bolts/nuts/washers and protected by 15 mm bore GI light grade pipe upto test point or upto main switch board, HT/LT equipments, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing wire upto test point or upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
Material and labour for Earthing complete with galvanised iron earth plate electrode of size 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including GI earthing strip 32x6mm by means of GI bolts/nuts/washers and protected by 40 mm bore GI light grade pipe upto test point or upto main switch board / electric equipment / pole / lightning arrestor / HT/LT equipments / GODO switch etc, fixing with 02 Nos nuts and bolts and protection pipe fixed with and including flat iron clamps, bolts, nuts and washers. Earth plate shall be surrounded by alternate packed layer 15 cm thick of charcoal or coke and common salt all around bottom and top. 20 mm bore GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) including necessary form work, excavation and earth work in any type of soil, returning filling and disposal of surplus soil to a distance not exceeding 50m, Pit cover 40mm thick made with RCC (1:2:4) type B1 (using 20 mm graded stone aggregate) including TMT reinforcement 8mm dia @ 75mm c/c both way, MS handle 12mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified & shown in electrical plate No. 3 of SSR 2009 (Part-I) complete all as specified and as directed by Engineer-in-charge. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and GI earthing strip upto electric equipment from top of earth plate shall be included in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engineer-in-charge.
Supply and fixing energy efficient LED street light fitting of 45W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaire, with driver, fixing the light fitting with and including bracket made out of GI tubing light grade 32mm dia, 1.2 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron of size 25x4 mm with suitable nuts and bolts for fixing of bracket including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer, complete fitting with all accessories and following specifications, complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficacy of luminaire should be minimum 100 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) IP rating : Minimum IP65. (g) IK rating : Minimum IK07 (h) Built in potted LED Driver of the make as of the luminaire. (j) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (k) Surge protection 10 kV (inbuilt + extended) (l) CCT : 5700 K. (m) CRI : Morethan 70 (n) Lens - High Efficiency wide angle lens. (o) BIS Approved fixtures and driver (p) Rated life time : 50000 burning hrs @L70 (Average 10 to 12 hrs daily)
Supply and fixing three core core (3x1.5sqmm) flexible flat/round cable, copper conductor multistranded, PVC insulated and overall PVC sheathed, 1100 volt, drawn through LT steel tubular poles or drawn through GI pipe along PCC pole for connection to street light from junction box to light complete all as specified and as directed. Note :- GI Pipes if required same shall be measured and paid seperately under respective item.
Supply and fixing cable junction box of Size 210mm x 155mm x 92mm or any other higher size (Suitable for Pole mounting) complete with fixing accessories. Junction box should be insulated and made out of polycarbonate with glass fiber re-inforced material. The polycarbonate junction box shall be environment frinedly, recyclable, UV resistant, halogen and silicon free, anti acid and anti corrosive. The junction box knock out on four side wall and following specifications and all as directed by Engr-in-Charge :- (a) The junction box shall be rated for degree of IP 65 (ingress protection) in accordance with IEC 60529. (b) The gasket material shall be polyurethane or silicon and gasket shall be internally embedded. (c) Junction Box must meet the provision laid down in IEC 60998-1, IEC-60695-22, IEC 60670-2 to 5 and grey color according to RAL-9011/ 7035. (d) The manufacturer of junction box shall submit a copy of IEC certificate and glow wire test for 960 degree. (e) Junction box shall be fire retardant and self extiguishing in accordance with IEC60695-2 to 11, DIN VDE 0304 Part-3, UL94 V-2 flammability standard. (f) The impact strength of polycarbonate enclosures /boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK08. (g) Junction box shall have 4 pole tinned copper bus bar of size 25mmx3mm complete with one number 6 Amp MCB SP 10KA (h) Manufacturer should submit routine test certificate for junction box. (j) Clamps and screws for fixing of junction box shall be made of SS
Supply and fixing Cable route indicator, duly engraved with 'LT CABLE 1100 VOLT' on cast iron round plate 150 mm dia, 8mm thick with provision of 500 mm long (minimum) single leg/stand of angle iron 40x40x5 mm, welded/riveted on back side of plate, fixed and grounted in position with with PCC (1:3:6) type C-1, using 20 mm graded stone aggregate block of suitable size complete all as specified and as directed by Engineer-in-Charge.
Material and labour for cable route indicator post 900mm long made of precast cement concrete (1:2:4) type B-1, using 20mm graded stone aggregate, rounded tops as directed and embeded in ground of size 350x150x450mm below ground and 300x100x450mm above ground, applying two coats of cement base paint on plastered surface including writing letters (like LT/HT UG cable, __ feeder etc.) with synthetic enamel paint in brown colour in suitable size including earth work and form work complete all as specified and as directed.
Material and labour for boring of holes under main road pavement, hard standing or any other situation by manual mean for accommodate 40mm to 100mm bore GI tube (light grade) in the drilled holes, including returning, filling in the end working space including removal of surplus soil and making good the surface complete all as specified and as directed. Note ; (GL pipe and cable shall be measured and paid separately)
Supply & fixing of automatic street light control switch with infrared sensor based Nature Switch & voltage monitoring system (VMS). Nature switch operation should be based on Natural Light Lux level. Required illuminance level for Switching ON is ≤ 30 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have pert night operation facility of min. 4 hrs. to max 12 hrs. VMS should have Adjustable over & under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The sensor & VMS along with suitable Power Contractor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Terninate proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. sensor & VMS By-Pass option) with 3nos. Contractors, 3 Nos incoming MCBs & 3 Nos outgoing MCBs of 16-20 Amps each & Circuit wiring (Copper) of min. 10 sqmm complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing LED Post Top light fitting of 25W, 230 volts AC outdoor type, decorative design, Glare-free and better uniformity, for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete compete fitting with all accessories and LED lamp, fixing on and including 50mm dia GI pipe light grade of length 2.5 mtr, embeded in PCC block of size 0.3x0.3x0.5m made with PCC (1:2:4) type B-2 using 20 mm graded crushed stone aggregate, including making electric connection with suitable size of wire, complete fitting with all accessories and following specifications complete all as specified and directed by Engineer-in-Charge :- (a) Lumen system efficiency of luminaire should be minimum 100 lumen per watt. (b) Input voltage range : 140 to 270 volts. (c) Temp operating range : Minus 10*C to plus 50*C (d) Power factor : Minimum 0.95 (e) THD : Max 10% (f) CRI : More than 70 and CCT : 5700K (g) IP rating : IP 65 (h) IK rating : minimum IK 07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should e complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10kV (inbuilt +extended) (m) Lens - High Efficiency wide angle lens. (n) BIS approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Supplying and laying synthetic rubber mat insulated for voltage upto 11 KV for electrical purpose as per IS 15652-2006 (superseding IS 5424) suitable for electrical shock safety of size 2 meter x 1 meter x 2.5 mm complete all as directed.
Sand cushioning, with dry and clean river fine sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved sand free from vegetations, grass and other deleterious substances shall be used.
Supplying, erecting, testing and commissioning Raising and Lowering type (16 metre height high mast system hot dip galvanised inside and outside) in single dip, suitable for wind velocity as per IS 875 part 3 with only one longitudinal seam weld per section but without circumferential weld including accessories viz head frame, 2 point suspension system with steel wire rope 6 mm dia 7/ 19 gauge, double drum winch, galvanised lantern carriage arrangement suitable for and with 8 nos Luminaires symetrically lightning finial, LED aviation obstruction light of 9/10 watt,lighting arrestor spikes, foundation bolts,nuts, anchor plates, templates, trailing cable and intergral power tool for raising and lowering operation of high mast with and including following technical specification:
(a) HIGH MAST SYSTEM Height of Mast - 16 m No of sections - two Material construction - S355 grade as per BS-EN10025 Base dia and top diameter (A/F) - 360 mm and 150 mm respectively Plate thickness and section length - Top - 3mm X 5420 mm , Botton- 4mm X 10980 mm Cross section of Mast - 20 sidde polygon standard for of galvanisation - As per BS EN ISO 1461/BS729/IS2629 Size of opening and door at base - 1200 mm X 250 mm Diameter of base plate - 520 mm Thickness of base plate - 25 mm Lightning protection finial - GI single spike Maximum Wind speed - 50 m/s as per IS 875 (Part-III) Number of foundation bolts - 6 Nos PCD of foundation bolts - 445 mm Type/diameter/length of foundation bolts - TS 600/24 mm dia/850 mm long
(b) LUMINAIRES CARRIAGE Material of construction - 50 NB ERW Class 'B' MS pipe Diameter of carriage ring (mm) - 535 mm (ID) minimum Construction - 8 arm welded 2 sections Load carrying capacity 16 Luminarie (c) WINCH / POWER TOOL Type/SWL of winch - Double Drum /SWL 350 Kg Method of operation - Integral Motor I Motor Capacity - 1 HP Three Phase No of Speed - 6 Pole, Single Speed
(d) STAINLESSS STEEL WIRE ROPE Grade/Construction - AISI304.7/I9 Construction No of Ropes - Two continuous Diameter (mm) - 6 mm Braking load capacity (minium) - 1450 Kg x 2
(e)FEEDER PILLAR Powder coated CRCA steel sheet feeder piller housing 3.15 mm thick (minimum) suitable for outdoor application with 63 amp four pole MCB incomer, Nature switch, 16 amp, 420 volts suitable for automatic switching ON and OFF of the luminaries, 9 Amp two contactors and raise lower push buttons for motor operation, incoming terminals of 50 Sqmm and outgoing terminals of 16 sqmm for power cable and 2.5 sqmm for motor mounted on suitable foundation (f) FOUNDATION Construction of suitable shallow foundation as recommended by OEM with M20 grade concrete for high mast considering the safe soil bearing capacity at site as 10T/sqm at 2 m depth
(g) TRAILING CABLE PVC insulated PVC scheathed 1100 volt grade ISI marked multistranded copper conductor cable 6 core 2.5 sqmm (h) FLOOD LIGHT LUMINAIRE Eight number LED flood light luminaires having a nominal system lumen output of minium 20000 lumens at a minimum system efficacy of 100 lumens per watt and total power consumption not more than 200 watt including driver. it has a rated system life time of 50000 buring hours at L70 and should have a color temperature of 6500 K, CRI>80, THD<10% and PF>0.95 complete & surge protection not less than 10KV.
(J) Automatic light control switch with infrared sensor based Nature Switch & voltage monitoring system (VMS). Nature switch operation should be based on Natural Light Lux level. Required illuminance level for Switching ON is < 30 Lux and for Switching OFF > 10 Lux. The Sensor should also have pert night operation facility of min. 4 hrs. to max 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The sensor & VMS along with suitable Power Contractor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Terninate proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operaation (i.e. sensor & VMS By-Pass option) with 3nos. Contractors, 3 nos. Incoming MCBs & 3 nos. Outgoing MCBs of 16-20 Amps each & Circuit wiring (Copper) of min. 10 sq.mm
Supply, installing, commissioning and testing of 20 KVA ONLINE IGBT UPS with inbuilt isolation transformer three phase input : 340 to 460 V, 50 Hz and three phase out put : 415 V +/-10% AC 4 wire along with battery stand and battery interlink cable, backup 30 minutes including Sealed Maintenance Free batteries 30 nos, 42AH/12 V each as per manufacturer's recommendation complete all as specified and as directed and following specifications :-
AC Output (i) Regulation (Steady state) - +/- 1% (ii) Dynamic Regulation - +/- 3% with 100% step load of 0.8PF&3.1CF and recovery in (iii) Transient Response - Less than 40 milliseconds (iv) Total Harmonic Distortion - <2% for 100% linear load & <5% for 100% non-linear load
Output Frequency (i) Inverter Mode - 50 Hz +/- 0.1 Hz (ii) Overall Efficiency - >/-88% (iii) Overload Capacity - Overload Capacity
Bypass (i) Static Bypass - Static bypass to ensure seamless transfer to mains (ii) Manual Bypass - Manual / Maintenance Bypass
Protection and Controls - Input and Output MCB, Soft start features for rectifier and inverter, Battery current limiting protection, Built-in overload protection, Output Short circuit protection
Isolation Transformer - In-built isolation Transformer should be provided at the output
Battery charger (i) Type of Charger : Constant voltage-constant current (ii) Battery recharge time to 80% - 8 hours after 100% discharge (iii) Rectifier - IGBT
Inverter (i) Inverter technology - IGBT power devices pulse width modulation technology (ii) Crest Factor - 3.1 (iii) Output Wave form - Sinusoidal
Indications - Mains ON/OFF, Inverter normal/fail, Battery low, Load on Bypass
LCD display - Torch screen LCD display for information, Input voltage, Output Voltage, Output current, Output frequency, Battery Voltage, Battery Charge/ Discharge current
Audible alarms with indication - Mains failure, Battery low, Over temperature, Inverter trip, Load on Bypass
General (i) Acquostic Noise Level - </- 60dB (ii) Relative Humidity - 95% non-condensing (iii) Cooling - Forced Air Cooling
Supply and fixing Electric siren ISI marked horizontal double mounting single phase 220/240V AC supply, 50Hz, 6000RPM, having audible range 1.5KM copper wound complete all as specified and as directed and following specifications :- (i) Audible range (Diametrical) : 1.5 KM, Supply Voltage : 220/250V AC supply, Base Mounting : Horizontal, Siren type : Double Ended, Motor H.P rating 1/4, Motor rated RPM : 6000, IP Protection : IP -55, (ii) Nameplate Details:- (a) Model No, (b) Voltage, (c) Wattage, (d) Insulation level (e) Load current at full volume at supply voltage etc. Note :- Mfg test certificate from manufacturer shall be produced by contractor.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (indoor type for 415 volts, 3 phase, 4 wire AC supply, free standing, floor mounting) cubical type suitable size made out of CRCA epoxy powder coated 2mm thick sheet, factory fabricated having modern fabrication and testing process process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front open able hinged independent door for each compartment and common open able hinged door from rear side, with locking arrangement (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on pedestal frame made out of MS channel of size ISMC 50mm, both side properly welded and all vertical corner grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) including painting to pedestal frame with spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer. Danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Air circuit breaker 4 Pole 800 amps ,415 Volt of breaking capacity not less than 50 KA with electronic/ micro processor release(EDO type) - 01 No (Incoming)
Four Pole, copper bus bar 1200 Amps
MCCB 320 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCCB 250 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCCB 200 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 02 No (Outgoing)
MCCB 160 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCB 16-32 Amps, TPN, C series, 10 KA, 415V AC supply - 02 No (Outgoing)
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 400 Amps
MCCB 250 Amps, Four pole, adjustable thermal magnetic protection, 36 KA, 415 V AC supply - 01 No (Incoming)
MCCB 100 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 02 No (Outgoing)
MCB 16-32 Amps, TPN, C series, 10 KA, AC supply - 03 No (Outgoing)
MCB 10 Amps, DP, C series, 10 KA, AC supply - 02 No (Outgoing)
On load Change over switch 4 pole of current raring 250 A (open execution type) - 01 No
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 300 Amps
MCCB 200 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Incoming)
MCCB 160 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCB 16-32 Amps, TPN, C series, 10 KA, AC supply - 02 No (Outgoing)
MCB 16-32 Amps, DP, C series, 10 KA, AC supply - 01 No (Outgoing)
On load Change over switch 4 pole of current raring 200 A (open execution type) - 01 No
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 250 Amps
MCCB 160 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Incoming)
MCCB 40 Amps, Four pole, adjustable thermal magnetic protection, 16 KA, 415 V AC supply - 02 No (Outgoing)
MCB 32 Amps, TPN, C series, 10 KA, AC supply - 06 No (Outgoing)
MCB 32 Amps, DP, C series, 10 KA, AC supply - 02 No (Outgoing)
On load Change over switch 4 pole of current raring 160 A (open execution type) - 01 No
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT panel board (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar 400 Amps
MCCB 250 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Incoming)
MCCB 160 Amps, Four pole, adjustable thermal magnetic protection, 25 KA, 415 V AC supply - 01 No (Outgoing)
MCCB 40 Amps, Four pole, adjustable thermal magnetic protection, 16 KA, 415 V AC supply - 02 No (Outgoing)
MCB 32 Amps, TPN, C series, 10 KA, AC supply - 02 No (Outgoing)
MCB 32 Amps, DP, C series, 10 KA, AC supply - 02 No (Outgoing)
On load Change over switch 4 pole of current raring 250 A (open execution type) - 01 No
Indicating lamps set RYB - 01 Set of three
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning and testing of factory made LT feeder Pillar Box (CPRI approved) (out door for 415 volts, 3 phase, 4 wire AC supply) cubical type suitable size, outer shell made out of 3.15 mm thick CRCA epoxy powder coated sheet and inner shell made out of 2mm thick CRCA epoxy powder coated sheet, factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns, totally enclosed busbar chamber fully comparted type to accommodate the incoming and outgoing each switch gear shall have be independent opening and having provision for front and rear side opening with double door with hinges including locking arrangements (chromium plated 19 mm dia fancy lock) including provision of rubber beading and brass cable glands for each cable to make it weather and vermin proof, provision of air fins for ventilation, The Four Pole bus bar shall be insulated with colour code heat shrinkable sleeve and shall be mounted on suitable size "F" class insulator at an interval not more than 250 mm through out the length of each bus bar, panel shall be mounted on angle iron frame and 04 No legs made from angle of size 40 x40 x5mm, legs shall be 750 mm long, 450 mm grouted in blocks of PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) with 300 mm ground clearance, frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, danger notice plate for LT with conventional skull and bones duly riveted/pasted to the panel door, complete including all connections incoming / out going all as directed by Engineer-in-charge and comprising of following accessories :-
Four Pole, Aluminium bus bar of size 40x5mm
MCCB 40 Amps, Four pole, fixed thermal magnetic protection, 16 KA, 415 V AC supply - 01 No
Internal power and control wiring with suitable size PVC insulated multistranded copper wire.
Note :- (i) All type of spares such as glands, lugs, nuts, bolts etc, necessary excavation and earthwork, PCC work and making good disturbed surfaces shall deemed to be included in the quoted unit rate. (ii) Drawing of panel shall be approved by GE before fabrication.
Supply, installing, commissioning & testing of platform mounted transformer 500 KVA, 11/0.433KV, 50 Hz, step down, outdoor type, ONAN Cooled oil immersed copper wound energy efficient transformer, complete with first filling of IS-335 ISI marked filtered & dehydrated transformer oil and other standard fittings/accessories and 7 position OFF load circuit tap changer (Tapping range + 7.5% in steps of 2.5% Each) with vector group Dyn-11, with provision of HV and LV cable box suitable for making connection of incoming HT cable and outgoing LT cable all as per IS 1180-2014 (Level-2) and complete with and including all required accessories for installation of transformer all as specified and directed. The transformer shall comprises following:
(i) 03 Nos porcelain bushings with copper rod on HV side. (ii) 01 cable end box on LV side consisting of 04 Nos bushing. (iii) Oil conservator tank with filter type drain plug and oil level gauge. (iv) Dehydrating breather with first fill of silica gel (v) explosive vent ,oil level gauge, oil drain filter valve, lifting hooks, oil filling hole with cap/plug with connection plate, Air release valve plug complete. (vi) 01 Nos 100mm dia, dial type thermometer, vapour pressure type having range 0-120 degree with metal guard. (vii) 02 Nos earthing terminals on tank cover to facilitate fixing of 50x6mm GI earth strip for earthing of body including rating plate and terminal marking plate. All date shall me marked on Rating plate. (viii) First fill of unused and new transformer oil,IS-335 Marked filtered and tested upto 60KV die electric strngth at 2.5 mm air gap between testing electrode. (ix) Buchholz relay-01 No.
Supply, installing, commissioning & testing of HT 12 KV, 3 phase 50 Hz totally metal clad withdraw able type vacuum circuit Breaker INCOMER CUM OUTGOING (ICOG) panel with Copper bus bar of suitable rating, horizontal isolation type VCB of capacity minimum 630 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC not less than 2.5mm thickness for load bearing section and not less than 2 mm thickness for non - loaded bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25kA/0.1 Sec, No. of operation of Vacuum interrupter Bottles for better performance. (i) Mechanical life - 30,000, (ii) Rated Current - 10,000 & (iii) Rated short circuit current - 100KA All the main components like VI/VCB/Relays/Meters shall be of same make. Panel and VCB parameters are as below:- (i) Rated Voltage level/PF withstand voltage/Impulse level : 12KV/28kV/75 KVP. (ii) Continuous current rating: minimum 630A. (iii) Short circuit withstand current : minimum 25 KA for 3 sec. (iv) One No minimum 630 Amps horizontal draw out type vacuum circuit breaker in 12 KV metal clad floor mounting panel complete with following :-
(a) Manually and motor operated (230V,AC,50Hz) spring charged type, manually and electrically open (electrical - 110VDC ) operation type, incorporating mechanical as well as electrical ON/OFF indication "OFF" push button, test/service position limit switches, with minimum 6NO+6NC breaker auxiliary contact in service position. (b) manual Charging of breaker should be done without opening the front door. (c) Cast resin current transformer 11KV, 50-25/5A, core1: class 1.0,15VA for 3 phase, core2 : 5P10,15VA.- 03 Nos (d) Cast resin potential transformer 11KV/V3/110V/V3/110V/3, 50 VA, CI 1.0,CI 3P and HT Fuse at the primary end and 04 pole MCB at the secondary end of the PT (Confirming related IS specification).
Protection arrangements for the breaker shall comprise of the following : (i) U/V.O/V,E/F,O/C, S/C with modbus protocol and drawout type- Numerical Type (ii) Auxiliary transformer protection - All the Relays shall belong to a common platform and shall be of single make with Electromechanical Relays in Draw-out casing.
Note:- (a) Pre commissioning test shall be carried out by SEI. All arrangement for the same shall be made by contractor with in over all cost quoted. (b) Make of Numerical protection relay and VCB Panel shall be same. (c) Drawing for HT Panel shall be got approved from GE before fabrication of panel. (d) Panel shall be suitable for internal Arc test of 1 Sec.
Supply and fixing Aviation obstruction light fitting, twin type, IP 65 protection, comprising of aluminium alloy housing with polycarbonate enclosure and accessories complete with LEDs to be fixed on the top OHR with fixing accessories as shown on drawing complete all as specified and as directed.
Material and labour for Sub main wiring (using colour coding such as red, black, white and green colour or as directed) for connection to aviation light at top of OHR to DB with 3x1.5 Sq.mm single core FRLSH PVC insulated unsheathed multistranded copper conductor 1100 V grade (03 run i.e 2 runs for main phase and nutral, 01 run for earthing) drawn through and including 20mm bore PVC rigid conduit (heavy duty, ISI marked) fixed along RCC pillar/wall surfaces from top of OHR to DB including all fittings and fitting arrangements such as bends, elbows, tees, end cap, PVC clamps, rawl plug, screw, couplers, lock unit, saddles, pipe hooks, terminal box etc. complete all as specified and as directed and as shown on drawing. Note :-Three runs of copper conductor and one run of PVC conduit including accessories shall be measured and paid as one unit.
Supply and fixing (concealed flush to wall) factory made DB (made out of CRCA sheet not less than 1.2mm thick, fitted with DIN channel neutral link and 200 Amp rated bus bar) SPN, 4 Way 240V, suitable for mounting MCB/Isolator etc, conforming to IS-13032, DB shall be semi glosy finished with epoxy polyster based powder paint sprayed and backed at high temperature between powder paint process to ensure smooth finish and protection against corrosion atmosphere. The DB shall be double door type with hinged door with locking arrangement, the DBs shall be of IP-43 protection class, and including making good disturbed surfaces of walls as necessaty complete all as specified and directed by Engineer-in-charge and comprising of following accessories :- (i) MCB ‘B’ curve suitable for 230 volts AC supply, 10 Amps, SPN and rupturing capacity not less than 10 KA, - 01 No (ii) MCB ‘B’ curve suitable for 230 volts AC supply, 2 Amps, SP and rupturing capacity not less than 10 KA, - 01 No
Supply, installing, commissioning and testing of cast resin Current Transformer 11KV dual type ratio 100/50/5A suitable for existing 11KV HT VCB 630A rated capacity complete all as specified and as directed. Note ;- Make of CT shall be same as per existing panel CT.
Supply, installation, testing and commissioning of Supply, installation, testing and commissioning of maintenance free earth grid (grounding) of interconnected two earth electrode of size 85 mm dia x 3 mtr long each. Metal conductor of electrode shall be Cu bounded MS rod dia 17.2 mm, length 3 mtr and interconnected strip shall be Cu bounded MS strip of 50mm x 6mm. Cu bounding of MS rod/strip should be Min 250 microns. Earth electrode of 85 mm, depth 3 mtr shall be placed in augured bore and embedding of interconnected strip shall be cast in high purity electrically effective surface area of the earth grid to lower the earth resistance. Conductive earth enhancing material shall be mix with cement in the ratio 3:1, which should not leach chemicals into the adjacent soil or underground water channels and should be in pH neutral range. Earth enhancing material should permanently protect the encased metal components of the earthing system. All hardware like nuts, bolts and washers should be of stainless steel. Electrode should withstand fault current upto 35 KA for 1 second. Electrodes top terminal be sealed permanently packed with conductive concrete and test link of Cu bonded MS strip of size 50mm x 6mm x 200mm shall be taken out to connect the equipment. No ore cast electrodes to be used including making RCC pit cover and making test point including brazing of all the joints upto the test point including testing on completion, complete all as specified and as directed. Note :- (i) Test certificate of earthing material for fault current, Ohms compliance, resistivity value from NABL Certified/ CPRI lab is must and shall be submitted by the contractor and it has to be verified by GE. (ii) Test Reports should not be more than 5 years old. (iii) Earth testing arrangement at site should be done by the contractor as per direction of Engineer-in-Charge and Satisfactorily test report forward to E8 section duly signed by all concerned along with running payment.
Supplying, installing, commissioning and testing complete of manufacturer or OEM (Original Eqpt Manufacturer) manufactured and tested static Diesel Engine driven Generating Set, radiator cooled, with AMF panel capable of delivering 100KVA (80 KW) or nearest higher rating 415 volts AC 3 phase, 4 wire system of supply, 50Hz. The DG set shall consist of diesel engine coupled through flexible coupling to matching alternator and mounted on foundation pads on common base frame in the CPCB approved acoustic enclosure (the complete set confirming to and test certificate as per CPCB-II norms and as specified) with AMF control panel standardised by manufacturer, inbuilt fuel tank, flexible exhaust pipe, incl necessary PCC foundation as per manufacturer instructions complete all as specified and as directed and comprising with the following:--
Engine (Prime mover) : Diesel Engine 1500 RPM of suitable BHP as recommended by manufacturer (at rated RPM), water cooled, 4 cylinder, inline, 4 stroke, confirming to ISO 3046 / BS 5514 with turbo charged air cooled , 1x88 AH 12 Volts batteries start, mechanical FIP, Electronic Governor, pulse tuned exhaust manifold, stainless steel exhaust flexible connection complete with flywheel and all standard fittings/fixture as per manufacturing practice including suitable engine control panel with tachometer, lub oil temp and pressure gauge, water temp starter, dynamo, fuel tank, fuel and lube oil filter, Dry type replaceable paper element air cleaner etc.
Alternator : AC alternator, self-excited, self-regulated, self-ventilated, brushless design, confirming to BS 2613/5000, 3 phase, 415 volts, 4 wire rated line current min 56 Amps output at PF 0.8, 1500 RPM, insulation class ‘H’ enclosure IP 23 complete with AVR with ± 1% voltage regulation, directly coupled to and matched with engine.
Anti-vibration pad for mounting engine alternator assembly on the base frame/plate.
Base frame/plate made out of structural steel as per manufacturer’s recommended design/specifications.
Acoustic Enclosure : Engine Alternator assembly mounted on AV mounts with silencer and SS exhaust bellow suitable optimised to meet stringent noise emission standards as laid down by MOEF/CPCB. Base rail with draw out type fuel tank provided with drain plug, air vent, inlet and out let connection, level indicator, manhole etc.
01 No 12 volt x 88 AH maintenance free batteries complete with suitable size copper lead.
AMF control panel : RAL 9003 white powder coated control panel made out of CRCA sheet provided with AMF system (automatic starting of main failure) and Start Stop push button for manual operating, provide with MCCB of suitable rating with short circuit protection, controller which display voltage, current, KW, PF, Frequency, KWH, lube oil pressure, indicating lamps for ‘load ON’ and ‘set running’ current transformer of suitable rating etc, aluminium bus bar of suitable rating with incoming and outgoing termination complete all as per manufacturer’s recommended design/specifications.
The contractor shall supply following maintemance spare part and tool kit for the generator set :- (i) Fuel filter - 02 Nos (ii) Lube oil filter - 01 No (iii) Air filter - 01 No (iv) V-belt - 02 Sets (v) Tool kit socket set - 01 No (vi) DE Spanner set - 01 No (vii) Ring Spanner set - 01 No (viii) Clamp meter - 01 No
Note :- (i) Any item left out for successful operation of AMF panel is deemed to be included in overall cost quoted. (ii) DG set should be sound proof as per latest policy (iii) Cost of maintenance free batteries as per recommendations of manufacture shall deemed included in unit rate quoted by contractor (iv) Cost of PCC foundation as per recommendations of manufacturer shall deemed included in unit rate quoted by contractor. (v) Initial filling of lubricating oil/coolant and fuel required for testing of DG set shall be provided by the contractor without any extra cost. (vi) Exhaust from DG set shall be as per latest CPCB [II] norms. Alternatively emission control device within overall cost quoted shall be provided (vii) Pre commissioning test shall be carried out by rep of Accepting Officer. All necessary equipment’s, consumables and T&P required for successful completion of the test shall be arranged by the contractor and cost for the same shall deemed included in unit rate quoted by contractor.
Subtotal
Lump sum price worked out by the tenderer for “SUMMER APPLIANCES, AIR CONDITIONING, HOT WATER SUPPLY AND MECHANICAL LAUNDRY WORKS" as listed in Schedule ‘A’ Section - X (Part-I)
Sch 'A' Sec - X (Part-II) , (SUMMER APPLIANCES, AIR CONDITIONING, HOT WATER SUPPLY AND MECHANICAL LAUNDRY WORKS)
Supply, installing, commissioning and testing of metal top deep freezer single phase 220 V, 50 Hz, 320 ltrs or next available higher capacity having double door, direct cool evaporator type, refrigerant R600a, caster lock, Temp range < - 18⁰C, Analogue temp setting, magnetic door gasket, caster wheel, inside aluminium cladding, including all inbuilt accessories complete all as specified and as directed.
Supply, installing, commissioning and testing frost free refrigerator electric driven single phase 220 volts, AC 50 Hz, 250 ltrs or next available higher capacity with BEE approved, minimum 3 star rating double door, stablizer free operation, Inverter Technology, R600a Refrigerant,LED display, including all inbuilt accessories i.e tempered glass self, deodorizer and with fruit & vegitable drawer etc complete all as specified and as directed.
Supply, installing, commissioning and testing Water Cooler fully stainless steel, electric driven single phase having approx storage capacity of 40 Ltr and nominal cooling capacity of 40 Ltr per hour including float valve and inlet PVC connection pipe of size 15 mm dia and 600 mm long of good quality complete with both ends CP nuts including electric connection through Voltage stablizer complete all as specified and as directed.
Supply, installing, commissioning and testing Water Cooler fully stainless steel, electric driven single phase having approx storage capacity of 80 Ltr and nominal cooling capacity of 40 Ltr per hour including float valve and inlet PVC connection pipe of size 15 mm dia and 600 mm long of good quality complete with both ends CP nuts including electric connection through Voltage stablizer complete all as specified and as directed.
Supply, installing, commissioning and testing Water Cooler fully stainless steel, electric driven single phase having approx storage capacity of 120 Ltr and nominal cooling capacity of 60 Ltr per hour including float valve and inlet PVC connection pipe of size 15 mm dia and 600 mm long of good quality complete with both ends CP nuts including electric connection through Voltage stablizer complete all as specified and as directed.
Supply and Installation of Desert cooler of size 26 x 26 x 33 inch or next available higher size, electric driven single phase 230 volts steel body having nominal air flow capacity of 4000 Cu M per hours, factory made GI sheet body 18 SWG and side panells of 22 SWG, water sump capacity not less than 40 ltrs, including water pump submesible type of suitable capacity ISI marked, complete including electric connection complete all as specified and as directed. Note (a) : Sufficient length of 3 core PVC sheathed round copper cable size 23/.0076 to enable fixing in to plug point shall be provided by contractor. (b) GI Pipes, float valve, stop valve, PVC connection shall be measured and paid seperately under respective item. (c) Serial Number as issued by Engr-In-Charge of cooler and GE Office name shall also be written on cooler with red colour permanent marker or paint, cost for the same shall deemed to be included in the quoted unit rate nothing extra shall be paid on this account
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 1 KVA with wall mounting bracket complete all as specified and as directed.
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 280 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2 KVA with wall mounting bracket complete all as specified and as directed.
Supply & installing of Voltage stabilizer for automatic operation having input & output voltage, Amps, Over & low voltage cutout and timer delay function etc digital display single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA with wall mounting bracket complete all as specified and as directed.
Supply and fixing (concealed in wall or as directed) single pole and neutral sheet metal enclosure (AC Box) with a two pin and earth plug and socket complete with one single pole MCB of capacity 20 Amps, 240 volts, AC supply complete all as specified and directed by Engineer-in-Charge.
Material and labour for concealed sub main wiring (using colour coding such as red, black, white, green colour or as directed) with 2.5 Sqmm single core (03 run i.e 2 runs for main phase and neutral, 01 run for continues as earth wire) FRLSH PVC insulated unsheathed multistrand copper conductor cable drawn through and including PVC conduit 20mm dia (medium quality ISI marked), for independent circuit including all fitting arrangement i.e. PVC clamp, rawl plug, screw, PVC junction box, tee, bend etc. and including cutting of chases in wall and making good disturbed surfaces of walls as per original complete all as specified and as directed. Note :- Three runs of copper conductor cable and one run of PVC conduit including accessories shall be measured and paid as one unit (one RM length) for payment and extra length of cables required for connection to MCBs/DB shall not be measured and the cost for the same shall deemed to be included in the unit rate.
Supply, installing, commissioning and testing of electric water heater (Geyser, vertical type) storage type ABS body of capacity 25 litre, BEE approved 5 Star rating, 230 V , single Phase, AC supply, inner tank made out of heavy duty stainless steel sheet with feroglas coated (Designed with single weld line, factory tested with hydraulic pressure as per latest IS code) complete with all accessories such as safety valve, thermostate, NRV, connection piece PVC connection for hot and cold water of suitable length, three core PVC insulated PVC Sheathed copper conductor flexible cable including 15 Amp plug suitable for existing socket and fixing material, 04 no Nut bolt grouting in wall in PCC (1:2:4) using 12.5mm graded stone aggregate for hanging the geyser and making good the disturbed surface complete all as specified and directed by Engr-in-Charge.
Supply, installing, commissioning and testing of electric water heater (Geyser, vertical type) storage type ABS body of capacity 50 litre, BEE approved 5 Star rating, 230 V , single Phase, AC supply, inner tank made out of heavy duty stainless steel sheet with feroglas coated (Designed with single weld line, factory tested with hydraulic pressure as per latest IS code) complete with all accessories such as safety valve, thermostate, NRV, connection piece PVC connection for hot and cold water of suitable length, three core PVC insulated PVC Sheathed copper conductor flexible cable including 15 Amp plug suitable for existing socket and fixing material, 04 no Nut bolt grouting in wall in PCC (1:2:4) using 12.5mm graded stone aggregate for hanging the geyser and making good the disturbed surface complete all as specified and directed by Engr-in-Charge.
Supply, Installing, commissioning and testing washing machine with in built hydro extractor of capacity 30Kg (per charge) front loading electrically heated and operated stainless steel body controlled through programmable logic control (PLC), auto time, auto reverse, auto stop, auto temp control, auto level control, Pneumatically operated valves for auto water inlet, auto steam inlet, auto drain, variable frequency drive for variable speed inner basket and outer body stainless steel. Heavy duty MS fabricated structure complete all as specified and as directed.
Supply, Installing, commissioning and testing Drying tumbler electrically heated and operated having front loading type auto time, auto reverse, auto stop with fully die pressed door, Inner basket stainless steel, outer drum double walled insulated with glass wool of capacity 30Kg per charge complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “ADDN/ALTN PUMP HOUSE BUILDING WORK" as listed in Schedule ‘A’ Section - XI
Sch 'A' Sec - XI (Part-II), (ADDN/ALTN PUMP HOUSE BUILDING WORK)
Supply & fixing, factory made steel window box type with side hung shutters (glazed and wiregauged) including pintol hinges, steel handle, steel peg stay, MS fillets and locking arrangement complete, including fixing of lugs in PCC (1:2:4) type B-1 (using 20mm graded stone aggregate) complete all as specified & as directed. Note :- Glass, wiremesh and grill shall be measured and paid separately under respective item of Sch A.
Subtotal
Lump sum price worked out by the tenderer for “EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORK" as listed in Schedule ‘A’ Section - XII (Part-I)
Sch 'A' Sec - XII (Part-II), (EXCAVATION, EARTHWORK AND SITE DEVELOPMENT WORK)
Surface excavation not exc 30 cm deep and getting out in soft/ loose soil complete all as specified and as directed. (For road work)
Grubbing up/digging out roots of tree girth exceeding 30cm and not exceeding 100cm including filling holes and leveling off ground, stacking of roots for measurement and removing after measurement including removing all unserviceable material from site and clearing site complete all as specified and as directed.
Grubbing up/digging out roots of tree girth exceeding 100cm and not exceeding 150cm including filling holes and leveling off ground, stacking of roots for measurement and removing after measurement including removing all unserviceable material from site and clearing site complete all as specified and as directed.
Grubbing up/digging out roots of tree girth exceeding 150cm and not exceeding 200cm including filling holes and leveling off ground, stacking of roots for measurement and removing after measurement including removing all unserviceable material from site and clearing site complete all as specified and as directed.
Grubbing up/digging out roots of tree girth exceeding 200cm and not exceeding 250cm including filling holes and leveling off ground, stacking of roots for measurement and removing after measurement including removing all unserviceable material from site and clearing site complete all as specified and as directed.
Subtotal
VIJAY JINDAL BUILDERS PVT LTD
BANSI BUILDER AND CONTRACTORS PVT LTD
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
A.V BUILDERS
ENGINEER CONSTRUCTION PVT. LTD.
Saru Enterprises Pvt Ltd
A S CONSTRUCTION COMPANY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid