Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹49.4 LAccepted-Finance | ₹49.4 L | L1 | Accepted-Finance Being lowest |
| 2 | L2₹49.8 L+₹41,490 (0.84%)Rejected-Finance | ₹49.8 L+₹41,490 (0.84%) | L2 | Rejected-Finance Other than lowest |
| Sl No | Description | Qty | Unit | M/S KALSI ENGINEERS AND CONTRACTORS L1 | M/S J S ENGINEERS L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm with 04 legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) ACB 630 Amp 4 pole 50 KA, Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.
(b) Alum bus bar 1000 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 400 Amp, 50 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 No.s
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 03 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | 6,00,000 ₹6,00,000 | 4,20,000 ₹4,20,000 Lowest |
| 2.00 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm with 04 legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 400 Amp, 50 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 600 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 315 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 01 No.
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 06 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | 3,00,000 ₹3,00,000 | 2,36,115 ₹2,36,115 Lowest |
| 3.00 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm with 04 legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 315 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 500 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 250 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos.
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 01 No.
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 03 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | 2,50,000 ₹2,50,000 | 1,86,570 ₹1,86,570 Lowest |
| 4.00 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm with 04 legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 250 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 400 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 200 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos.
(b) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | 1,50,000 ₹1,50,000 | 1,39,500 ₹1,39,500 Lowest |
| 5.00 | Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT bus bar box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from MS sheet supported with 04 legs of 45cm long made of iron angle 25x25x4mm thick totally encloused ,dust, weather & vermin proof, 3.15mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 400 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement with Digital Multifunctional meter Showing V,I, PF , HZ etc with suitable CT ratio also with MCCB 4P 250 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 2.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete including taking down old unserviceable one complete all as specified and directed.
Note:- (i) Bus bar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
(ii) Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 2 | Each | 50,000 ₹1,00,000 Lowest | 92,000 ₹1,84,000 |
| 6.00 | Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT bus bar box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from MS sheet supported with 04 legs of 45cm long made of iron angle 25x25x4mm thick totally encloused ,dust, weather & vermin proof, 3.15mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 250 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement with Digital Multifunctional meter Showing V,I, PF , HZ etc with suitable CT ratio also with MCCB 4P 160 Amp, 25 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 2.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete including taking down old unserviceable one complete all as specified and directed. Note:- (i) Bus bar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
(ii) Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 2 | Each | 90,000 ₹1,80,000 | 45,000 ₹90,000 Lowest |
| 7.00 | Supply, installation and commissioning and testing of LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm with 04 legs of 45cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming:-
(a) MCCB 4 pole, 250 Amp, 25 KA, 415 volts AC with adjustable thermal and fixed magnetic setting- 01 No. (b) Aluminium bus bar 400 Amps TPN - 01 Set
(c) Digital voltmeter 0-500 volts with selector switch - 01 No.
(d) Digital Amp meter 0-300 Amp with selector switch & CTs - 01 No
(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set
Outgoing:-
(a) MCCB 4 pole, 160 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting - 02 Nos
(b) MCCB 4 pole, 125 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting- 01 No. (c) MCCB 4 pole, 100 Amp, 16 KA, 415 volts AC adjustable thermal and magnetic setting- 02 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | 1,90,000 ₹1,90,000 | 75,000 ₹75,000 Lowest |
| 8.00 | M&L in replacement for earthing complete with copper earth plate electrode of size 60cm x 60cm x 3.15mm thick buried directly in ground (earth pit not less than 2.25 meters below ground level) with top edge of earth plate not less than 1.5 meters below ground level surrounded on all sides by 150 mm thick charcoal & common salt starting from ground below earth plate upto 150mm above Copper plate in alternate layers connected to copper strip 20x3 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, PCC (concrete chamber of size 300 mm x 300 mm x 300 mm inside dimension) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish , internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire mesh of 22 gauge, 80 mm thick PCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI pit all as shown in electrical plate No 5 of MES SSR Part-I (2009) as specified including provision of 40mm bore medium grade GI pipe for earth strip protection and 20 mm bore for watering complete , all excavation and earth work & connecting the earthing to an earthing test point /LT Panel/ Transformer as specified and testing on completion for desired result complete all as specified and directed.
Note :- Excavation for earthing shall be only through manually but not through JCB or any other machine. | 20 | Each | 4,000 ₹80,000 Lowest | 23,000 ₹4,60,000 |
| 9.00 | Supply and fix in replacement of GI strip of size 32 x 6 mm for earth continuity conductor or main earthing lead fixed to wall burried in ground fixed alongwith poles complete all as specified and directed. | 40 | RM | 150 ₹6,000 | 110 ₹4,400 Lowest |
| 10.00 | Supply, laying, jointing and testing in repair XLPE cable insulated,armoured, heavy duty electric cable with aluminium conductor,1100 volts grade, cross-sectional area 400 Sqmm 3.5 core complete all as specified and directed. | 150 | RM | 1,500 ₹2,25,000 Lowest | 2,500 ₹3,75,000 |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
12 Aug 2026, 6:00 pmClosed
GE NAGROTA
GE NAGROTA
SPL REPAIR/REPLACEMENT OF LT PANELS/CABLES/ GARDEN LIGHTS AND CONNECTED E/M ITEMS AT VARIOUS LOC UNDER GE NAGROTA
2026_MES_775215_1
CANO GEN/TOKEN-71/2026-2027
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE NAGROTA
Class D Category b(i)
8 documents required · 8 mandatory
₹500
GE NAGROTA
₹92,000
Yes
22 Sept 2026
10 Jul 2026
17 Aug 2026
10 Jul 2026
12 Aug 2026
24 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) ACB 630 Amp 4 pole 50 KA, Manual draw out type with Microprocessor release, Ics=100% of Icu, LCD display, Thermal memory, Zone selectivity, Current & Voltage Measurement, Advance protection, over temperature protection, fault history, V/V and O/V release - 01 No.
(b) Alum bus bar 1000 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 400 Amp, 50 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 No.s
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 03 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | - | - |
| 2 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 400 Amp, 50 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 600 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 315 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 01 No.
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 06 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | - | - |
| 3 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 315 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 500 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 250 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos.
(b) MCCB 4 pole, 200 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 01 No.
(c) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 03 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | - | - |
| 4 | Supply, installation and commissioning and testing of LT panel cubical type CPRI Approved certified suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3.15mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm legs of 45 cm long covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming :-
(a) MCCB 4 pole, 250 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting
with Ics = 100 % Icu - 01 No.
(b) Alum bus bar 400 Amp TPN - 01 Set
(c) Digital Multifunctional meter Showing V, I, PF, HZ etc with suitable CT ratio-01 No.
(d) Indicator lamp LED type (RYB) complete with bakelite fuse fitting- 01 set
Outgoing :-
(a) MCCB 4 pole, 200 Amp, 36 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos.
(b) MCCB 4 pole, 125 Amp, 25 KA, 415 volts Adjutable Thermal and Magnetic setting with Ics = 100 % Icu - 02 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | - | - |
| 5 | Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT bus bar box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick totally encloused ,dust, weather & vermin proof, 3.15mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 400 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement with Digital Multifunctional meter Showing V,I, PF , HZ etc with suitable CT ratio also with MCCB 4P 250 Amp, 36 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 2.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete including taking down old unserviceable one complete all as specified and directed.
Note:- (i) Bus bar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
(ii) Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 2 | Each | - | - |
| 6 | Supply, Fixing , Commissioning and testing of CPRI approved outdoor cubical type LT bus bar box suitable for 415 V, 3 Phase , 4 wire 50 Hz , AC Supply system fabricated from MS sheet supported with legs of 45cm long made of iron angle 25x25x4mm thick totally encloused ,dust, weather & vermin proof, 3.15mm thick for outer shell and 2 mm thick for inner shell having MS section not less than 50x50x6 mm thick having TPN aluminium busbar of capacity 250 Amps mounted on porcelain insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement with Digital Multifunctional meter Showing V,I, PF , HZ etc with suitable CT ratio also with MCCB 4P 160 Amp, 25 KA, 415 Volts 50 Hz with adjustable thermal and adjustable magnetic setting and provn for incoming and outgoing cables with glands including control wiring with minimum 2.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB ,painting with two coat of smoke grey synthetic enamel paint over a coat of red oxide primer, complete including taking down old unserviceable one complete all as specified and directed. Note:- (i) Bus bar box shall be mounted on brickwork in CM 1:4 not less than 30 cm above ground level with suitable foundation, rendering 15 mm in CM 1:6 and two coats of cement base paint and the rates shall be inclusive in the quoted rate.
(ii) Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 2 | Each | - | - |
| 7 | Supply, installation and commissioning and testing of LT panel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, floor mounted, outdoor type factory fabricated duly powder coated inside and out side, outer cover made out of 3mm thick CRCA sheet, internal cover and partition made out of 2 mm thick CRCA sheet with angle iron 50 mm x 50 mm x 6mm covered from all side with front and back openable, weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system, wiring with suitable size copper cable and embeded in brickwork in CM 1:4 not less than 45 cm above ground level with suitable foundation for fixing panel of required size in ground with nuts, bolts and washer etc. complete comprising of following including taking out the old unserviceable panel complete all as specified and directed.
Incoming:-
(a) MCCB 4 pole, 250 Amp, 25 KA, 415 volts AC with adjustable thermal and fixed magnetic setting- 01 No. (b) Aluminium bus bar 400 Amps TPN - 01 Set
(c) Digital voltmeter 0-500 volts with selector switch - 01 No.
(d) Digital Amp meter 0-300 Amp with selector switch & CTs - 01 No
(e) Indicator lamp LED type (R, Y, B) complete with bakalite fuse fitting - 01 Set
Outgoing:-
(a) MCCB 4 pole, 160 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting - 02 Nos
(b) MCCB 4 pole, 125 Amp, 25 KA, 415 volts AC adjustable thermal and magnetic setting- 01 No. (c) MCCB 4 pole, 100 Amp, 16 KA, 415 volts AC adjustable thermal and magnetic setting- 02 Nos
Note: Contractor will have to produce Purchase voucher, Manufacturer test certifiacte at the time of RAR/FB duly signed by all concerned. | 1 | Each | - | - |
| 8 | Earthing complete with Copper earth plate electrode 60cm×60cm× 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to Copper earth strip of size 20x3 mm as earthing lead by means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. | 20 | Each | - | - |
| 9 | Supply and fix in replacement of GI strip of size 32 x 6 mm for earth continuity conductor or main earthing lead fixed to wall burried in ground fixed alongwith poles complete all as specified and directed. | 40 | RM | - | - |
| 10 | Supply, laying, jointing and testing in repair XLPE cable insulated,armoured, heavy duty electric cable with aluminium conductor,1100 volts grade, cross-sectional area 400 Sqmm 3.5 core complete all as specified and directed. | 150 | RM | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
Tender71.pdf
Tender Documents • 1.04 MB
BOQ_870894.xls
BOQ • 1.68 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .