Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.8 LAccepted-AOC PLOT NO 8 PREMA APARTMENT VEDANTNAGAR CHHATRAPATI SAMBHAJINAGAR 431 007 M S | CHHATRAPATI SAMBHAJINAGAR | CHHATRAPATI SAMBHAJINAGAR | MAHARASHTRA | 431007 | L1 | Accepted-AOC Accepting being lowest | |
| 2 | L2₹44.6 L−₹4.0 Cr (89.9%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest quoted rate |
Tender Value
₹46.5 L
EMD Value
₹93,000
Closing Date
15 Feb 2022, 6:00 pmClosed
Maj Pramod Kumar Tripathi
Shri Prakash G Kalekar AE QS and C and Shri D S Dhurpate JE QS and C
Repair / Maint of Gen Sets, Voltage Stabilizers, LT Panels, Repair of Street Light works and certain E/M misc works in the area of AGE E/M under GE (South) Ahmednagar
2022_MES_501409_1
8849/E8
Open Tender
Miscellaneous Works
Item Rate
334 days
Ahmednagar
Class D Cat b (i)
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahmednagar
₹93,000
Yes
4 Mar 2022
14 Jan 2022
17 Feb 2022
14 Jan 2022
15 Feb 2022
29 Jan 2022
14 Jan 2022 - 21 Jan 2022
Amount
M&L for monthly 'A' Check Inspection, maintenance and serviceing DG sets, 125 KVA Capacity, Make : kirloskar oil engines, Model 6R 1080TA, Location : AC Depot Pump House, including alternator, electric panel board connection to DG set etc for smooth functioning and carrying out following maintanance as required at site and directed by Engr-in Charge. Note: Items/ Spares required shall be measured and paid separately under respective item of BoQ (i) Checking engine oil level and topping up as and when required. (ii) Checking and adjusting the belt for tension and replacement of belt if required. (iii) Checking of oil bath air cleaner level (iv) Checking of exhaust system for leakage (v) Draining of sediment from fuel filter and fuel tank (vi) Cleaning of air cleaner elements (vii) Checking engine alternator coupling, mounting bolts and alignment (viii) Tighting all nuts, bolts, in altenator terminal block (ix) Checking of alternator carbon brushes and connections in alternator (x) Checking and tightening of all connection in DC control wiring. (xi) Checking of all radiator rubber hoses for leakage and replacement if required. (xii) Checking and recording oil pressure, water and oil temperarute for smooth functioning. (xiii) Checking anti vibration mounting pads for any deformation. (xiv) Checking throttle linkage for smooth operation. (xv) Checking battery for cell test, electrolyte level, gravity and topping up to required level (xvi) Routine check / repair work of panel, switches, MCCBs, main switch, all contactors, engine control unit etc. (xvii) Checking of AMF panel, all electrical connections etc. (xviii) Checking of earthing resistance (xix) Cleaning of vegitation around the DG set up to 1.5 mtr area.
All as per serial item No 1 but DG set 100 KVA Capacity, Make : kirloskar Green, Model KG-225L, Location : New KLP Pump house
All as per serial item No 1 but DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250MAL, Location : Dhobhighat pump house
All as per serial item No 1 but DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250M, Location : Dhobhighat pump house
All as per serial item No 1 but DG set 200 KVA Capacity, Make : Kirloskar, Modal KG 254M-1 Location :DAD complex
All as per serial item No 1 but DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhinghar pump house
All as per serial item No 1 but DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhingar pump house
M&L for 'B' Check once in Six month OR 250 Hrs running whichever is earlier for DG sets of 125 KVA Capacity, Make : kirloskar oil engines, Model 6R 1080TA, Location : AC Depot Pump House, Inspection, maintenance and serviceing including alternator, electric panel board connection to DG set etc for smooth functioning and carrying out following maintenance as per OEM instructions and as directed by Engr-in-Charge. Note: Items/ Spares including 'B' Check kit, coolent, lubricating oil required shall be measured and paid separately under respective item of BoQ (i) Repeat the activities of 'Á' Check services (ii) Replacment of lubricant oil. (iii) Replacing lubricant oil filters element with O rings (iv) Replacing fuel filters element with O rings (v) Replacing air filter elements with O rings (vi) Replacing coolant.
All as per serial item No 8 but for DG set 100 KVA Capacity, Make : kirloskar Green, Model KG-225L, Location : New KLP Pump house
All as per serial item No 8 but for DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250MAL, Location : Dhobhighat pump house
All as per serial item No 8 but for DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250M, Location : Dhobhighat pump house
All as per serial item No 8 but for DG set 200 KVA Capacity, Make : Kirloskar, Modal KG 254M-1 Location :DAD complex
All as per serial item No 8 but for DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhinghar pump house
All as per serial item No 8 but for DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhinghar pump house
Supply only 'B' check kit for DG set 125 KVA Capacity, Make : kirloskar oil engines, Model 6R 1080TA, Location : AC Depot Pump House. Note : Quoted rate includes oil filters (1.00 Ltr/0.5 ltr), Diesel filters and air filters inner and outer as recommended by OEM
All as per serial item No 15 but for DG set 100 KVA Capacity, Make : kirloskar Green, Model KG-225L, Location : New KLP Pump house
All as per serial item No 15 but for DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250MAL, Location : Dhobhighat pump house
All as per serial item No 15 but for DG set 160 KVA Capacity, Make : kirloskar oil engines, Model KG 160 SGIR250M, Location : Dhobhighat pump house
All as per serial item No 15 but for DG set 200 KVA Capacity, Make : Kirloskar, Modal KG 254M-1 Location :DAD complex
All as per serial item No 15 but for DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhinghar pump house
All as per serial item No 15 but for DG set 320 KVA Capacity, Make : Crompton Greaves Ltd, Model F-GIR 315 SB EKG-1049, Location : Bhinghar pump house
Supply & Refiling coolent, K cool super plus 50-50 Premix all as specified and as directed.
Supply & Refiling Battery water with electrolyte mix all as specified and as directed.
Supply & Refiling Engine oil 20 W 40 turbo synthetic superior quality engine oil all as specified and as directed.
S&F radiator hose pipe set with clamps suitable for DG set of capacity 100 /125 KVA all as specified and as directed.
S&F radiator hose pipe set with clamps suitable for DG set of capacity 160/200 KVA all as specified and as directed.
S&F radiator hose pipe set with clamps suitable for DG set of capacity 320 KVA all as specified and as directed.
S&F fan belt set suitable for 100/125 KVA all as specified and as directed.
S&F fan belt set suitable for 160/200 KVA all as specified and as directed.
S&F fan belt set suitable for 320 KVA all as specified and as directed.
S&F in replacement of battery lead with Negative & Positive brass terminals of suitable size and length of each lead all as specified and as directed.
Servicing & repair to self starter of DG set of 100 KVA to 320 KVA including replacement of parts such as washer, nut, bolts, bush, solonoid, rotor etc. assembling and testing complete all as directed by Engr-in-Charge.
S&F in replacement of battery 12 V, 180 AH, maintenance free battery, 12 Volt initially charged with suitable size of copper leads and brass terminals complete as directed by Engr-in-Charge. Make: Excide/ Amron/ Luminous
M&L for complete checking of AMF panel, finding the fault, servicing complete including replacement of unserviceable spares with necessary wiring and testing complete for manual & Auto operations all as directed. (Note:- Items required for replacement will be measured & paid seperately under respective item of BoQ)
S&F in replacement of AMF panel under and over voltage timing relay as per existing type, make and capacity all as specified and as directed.
S&F in replacement of AMF panel timer relay for circuit 230 V AC supply as per existing type, make and capacity all as specified and as directed.
S&F in replacement of AMF panel relay card 12 V DC supply for change over as per existing type, make and capacity all as specified and as directed.
S&F in replacement of AMF panel relay single with batch 8 pin 230 V AC supply as per existing type, make and capacity all as specified and as directed.
M&L in replacement of unserviceable contactor 220 V AC supply, 4 pole suitable for DG set 200 KVA AMF panel all as specified and as directed.
M&L in replacement of unserviceable contactor 220 V AC supply, 4 pole suitable for DG set 100/125 KVA AMF panel all as specified and as directed.
M&L in replacement of Start/ Stop switch with elements of AMF panel of any make and capacity all as specified and as directed.
M&L in replacement of solenoid switch for use of engine stop of AMF panel of any make and capacity all as specified and as directed.
M&L in replacement of Volt meter digital type of range 0-500 volts of AMF panel all as specified and as directed.
M&L in replacement of Amp meter digital type of existing make,model and capacity of AMF panel all as specified and as directed.
M&L in replacement of Indicator lamp 230 V AC Supply of AMF panel all as specified and as directed.
S&F in replacement of AMF panel MCCB, 3 pole, 25-100 Amp, 16 KA all as specified and as directed.
S&F in replacement of AMF panel MCCB, 3 pole, 125 Amp, 16 KA all as specified and as directed.
M&L in repairs and replacement of broken conopy door hinges of DG set of any capacity and make. Setting of conopy door, properly locking arrengement complete all as directed by Engr-in Charge
M&L in repairs and replacement for earthing complete with GI earth plate electrode of size 60cm x 60cm x 6mm buried directly in ground vertically at a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level sorrounded from all sides by 15cm thick and packed layer of charcoal dust and common salt filling in alternate layers etc and connected to and including galvanized earth strip 25mmx4mm upto 7.5 m by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 32mm dia GI pipe connected to main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, charcoal,salt etc RCC pit cover flush to earth pit 50mm thick reinforced with 8mm TMT bar 100mmC/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20mm graded aggregate) including excavation and earthwork disposal of surplus soil to distance not exceeding 50 metre) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as specified and as directed.
S&F in replacement of fuel level gauge of DG set as per existing make, model complete all as directed by Engineer-in-Charge.
M&L for dismantling, transportation to workshop and back, opening, rewinding main winding assembly and refixing 100 to 320 KVA DG set alternater, three phase, 415 V, 50 Hz with super enameled copper wire of existing gauge and existing class insulation including superior quality varnishing, heating / drying coils, making connections from coil to terminal box, spray painting with two coats of synthetic enamel paint including repair/replacement of diode plates for neutral & phase and repair / replacement of AVR, connecting, testing and commissioning at site for satisfactorily operation as required and directed by Engr-in-Charge..
S&F in replacement of Alternator connection terminal block suitable for 100 to 320 KVA DG Set alternetor as per existing sample complete all as directed by Engr-in Charge.
M&L in replacement of battery stand frame of size 4 feet x 1.5 feet with height of 1 feet made of 50mm x 50mm x 6mm angle iron and support with flat iron of size 40mm x 6mm, duly painted with two coats of synthetic enamel paint over one coat of red oxide primer, 20 mm wooden plank on top to place 02 Nos batteries complete all as specified and as directed by Engr-in-Charge.
M&L for taking the Diesel Generating set from Bhingar PH to civil workshop where repair to be carried out safely, dismantling the engine completery for repair and top over hauling of Diesel Generating set 320 KVA capacity of Make: Crompton Greaves , as per manufacture instuction, replacement of all defective parts as required for smooth functioning of the DG set complete all as specified and as directed by Engr-in-Charge. Note : (i) S&F in replacement of spare parts and certain repair work will be measured and paid separately under item Nos 56 to 88 here-in-after. (ii) Repair work shall be carried out through authorised dealer/ persons of Crompton Greaves only.
Supply & Replacement of liner FO D41V12 with Modified Honing all as specified and as directed.
Supply & Replacement of piston assembly complete with gudgeon pin and ring set with 'O' rings all as specified and as directed.
Supply & Replacement of sleeve for cylinder head, brass all as specified and as directed.
Supply & Replacement of Cylinder Head Sealing all as specified and as directed.
Supply & Replacement of O ring Viton 9mm x 4.5mm all as specified and as directed.
Supply & Replacement of O ring Viton 18mm x 5mm all as specified and as directed.
Supply & Replacement of Gasket cylinder head cover all as specified and as directed.
Supply & Replacement of Flexible Fule pipe all as specified and as directed.
Supply & Replacement of V12 F.I.pipe set-A type-E all as specified and as directed.
Supply & Replacement of gasket-Exhaust manifold all as specified and as directed.
Supply & Replacement of gasket-Air intake manifold all as specified and as directed.
Supply & Replacement of Inserts V S Inlet & exhaust all as specified and as directed.
Supply & Replacement of valve EX D2 KV 2994 all as specified and as directed.
Supply & Replacement of FILT Element with O ring all as specified and as directed.
Supply & Replacement of FLTR INSRT with O ring all as specified and as directed.
Supply & Replacement of Valve steam seal all as specified and as directed.
Supply & Replacement of valve Guide D2 all as specified and as directed.
Supply & Replacement of Set of Hoses TBDV12 MK2 all as specified and as directed.
Supply & Replacement of Set of Hose Clip TBDV12 MK-II all as specified and as directed.
Supply & Replacement of set of Flex pipe TBDV12 MK-II all as specified and as directed.
Supply & Replacement of Radiator AVM all as specified and as directed.
Supply & Replacement of set of LLOP sensor all as specified and as directed.
Supply & Replacement of Push rod all as specified and as directed.
Supply & Replacement of Piston cooling Nozzel all as specified and as directed.
Supply & Replacement of High Pressure Hose all as specified and as directed.
M&L for repair to charging alternator assembly including replacement of carbon brushes and bushes complete and refixing all the components in position with necessary screws, nuts & bolts complete all as directed.
M&L for repair to self starter 12 Volts including replacement of armature, union, carbon bushes complete and refixing all the components in position with necessary screws, nuts & Bolts complete all as directed.
M&L for servicing / cleaning of air intake manifold assy with requsite tools and air pressure to remove dirt & foreign pairtcle completetly including replacement / repair to fiexible coupling of silencer / exhaust manifold to ensure no leakage of exhaust inside the canopy complete all as directed.
M&L for cleaning / derusting for inner cushion foam (insulation) of all inside canopy to achieve neat & cleanliness of gererating cabin with requisite air blower / dust sucker suitable for the job complete all as directed.
M&L for replacment of dioade, DE and NDE bearing of AC generator and warnishing field coil and armature assy complete all as directed.
M & L for painting of outer surface only of canoply of generating set inculding cleaning and de-rusting and preperation and painting with requisite tools and painting with white bright super enamel / synthetic paint including rewriting of machine no complete all as specified and as directed.
M & L for leakage rectification of radiator, cleaning, pressure testing complete as required and as directed.
Testing and tunning of DG set with load test complete all as directed by Engr-in-Charge.
Dismantling of fuel injection pump assembly complete from the engine of 200 KVA DG set Make KIRLOSKAR Model 6 SL 9088T , replacement of valve , washers etc assembling, calibiration , setting for proper function ,refixing and testing complete all as specified and as directed.
All as per serial item No 89 but for 160 KVA DG set Make : KIRLOSKAR Model 6 SL 1500TA.
All as per serial item No 89 but for 125 KVA DG set Make KIRLOSKAR Model 6 SL 9088T
All as per serial item No 89 but for 100 KVA DG set Make KIRLOSKAR Model 6 SL 9088T/Model no. KG100W52
Dismaintling, radiator assembly from the engine of 200 KVA DG set Make KIRLOSKAR Model 6 SL 9088T by disconnecting inlet and out let connections , overhauling/ servicing the radiator , clearing, removing blockages arresting leakages, assembling back incl necessary welding brazing as required , refixing , reconnecting and testing for proper functioning :
All as per serial item No 93 but for 160 KVA DG set Make : KIRLOSKAR Model 6 SL 1500TA.
All as per serial item No 93 but for 125 KVA DG set Make KIRLOSKAR Model 6 SL 9088T
All as per serial item No 93 but for 100 KVA DG set Make KIRLOSKAR Model 6 SL 9088T/Model no. KG100W52
S&F in repairs, fuel level indicator pipe white transparent including two jublee clamps, marking level with radiem paint/ tape complete all as specified and as directed
S&F in repairs, exhaust pipe white asbestos rope including removing old unservicable rope all as specified and as directed
S&F in repairs, MCCB, 3 Pole,400 Amps, capacity 50 Hz, 415 volts with rating 36 KA and connection with proper Lugs all as specified and as directed
S&F in repairs, MCCB, 3 Pole 250 Amps, capacity 50 Hz, 415 volts with rating 36KA and connection with proper Lugs all as specified and as directed
S&F in repairs, MCCB, 3 Pole 200 Amps, capacity 50 Hz, 415 volts with rating 36 KA and connection with proper Lugs all as specified and as directed
S&F in repairs, MCCB, 3 Pole 160 Amps, capacity 50 Hz, 415 volts with rating 36 KA and connection with proper Lugs all as specified and as directed
S&F in repairs, automatic voltage regulator Kit suitable for 100/125 KVA alternator including incoming and out going cable connection and tesring on completion all as specified and as directed Make : Kirlokar / Minilec/ Keltron
M&L for Graphite Gland packing rope of size 10mm/ 12mm/14mm all as specified and as directed
M&L for Bearing grease HP/BP type servo Gem Natra-3/Lithon-3. in 5 kg pack all as specified and as directed
S&F in repairs, flexible love-joy coupling set with Nut/ Bolt and rubber bushes suitable for existing DG set including metal filling grinding, finishing to suit the site installation alinging for noise free function all as specified and as directed
S&F in repairs, rubber bushing/rubber spider of DG set coupling complete with Nut , bolt and washer all as per site requirement and as directed by Engineer - in - charge .
M&L in replacement of battery charger 12 V DC SMPS 10 Amp for AMF panel all as specified and as directed
Supply and topping up / replacement of insulating oil of stabilizer chamber with new insulating / transformer oil upto the required level in any type and capacity of the voltage stabilizer all as directed by Engineer-in-Charge. Note : Insulating / transforemer oil brought by the contractor at site must be in seal packed in drum having ISI mark as per IS-335 / 1983. Make : Savita / Asian.
Repair / Servicing to voltage stabilizers 3 phase 4 wire system, 160 to 300 KVA by at site by opening carefully from top, taking out coils / connections, cleanig coils checking defective joints / soldering / jointing, re- assembling and testing on full load and making fully servicable including spray painting with supper enamelled paint of colour as directed by EIC, complete all as specified and directed.
S&F in repairs, off load change over switch - Disconnectors in sheet metal enclosure, 400Amps, 4P, 415 V all as specified and as directed
M&L for disconnecting and taking down unserviceable street light fittings of any type/rating from pole or wall, dismantling the same for necessary repair or replacment of unserviceable spars complete and refixing, connecting and testing the same all as specified and directed by Engineer-in-Charge. Notes:- (i) Spares/accessories required for replacement shall be measured and paid sepratley as supply only under respective items of BOQ. (ii) T&P required for repair/ maintenance such as ladder, vehicle, manpower etc, shall be included in the quoted rate of this item.
Supply & replacement surge protection device compatible with industrial & outdoor LED fixtures as per existing make and model, suitable for 20/25 Watt LED fitting all as specified and as directed
All as per serial item No 113 but suitable for 30-45 Watt LED fitting
All as per serial item No 113 but suitable for 60-70 Watt LED fitting
All as per serial item No 113 but suitable for 90 Watt LED fitting
Supply & replacement LED drivers compatible with industrial & outdoor LED fixtures of IS 15885 (Part 2/ Sec 13) or as per existing make and model suitable for 20/25 Watt LED fitting all as specified and as directed
All as per serial item No 117 but suitable for 30-45 Watt LED fitting
All as per serial item No 117 but suitable for 60-70 Watt LED fitting
All as per serial item No 117 but suitable for 90 Watt LED fitting
S&F GI pipe bracket, light grade of 40mm bore dia, 1.5mtr long, ISI marked duly bent to shape with an angle including mild steel clamps, nuts, bolts, washers etc compltete including dismantling of existing old brackets all as specified and as directed.
M&L for disconnecting jumpers of street light fittings from OH LT line and remove carbon and replace the damaged jumpers refixing, connecting and testing the same complete all as required at site and as directed.
M&L for 2 sqmm 2 core, 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections twin core cable flat stranded conductor including taking down old unserviceable cable all as specified and as directed.
All as per serial item No 123 but 4 sqmm 2 core
All as per serial item No 123 but 10 sqmm, 2 core
S&F in repairs, HDPE junction box of size 32 cm x 23 cm with bus bar mounted on insulators, 10 Amp MCB SP and fixing on poles with MS Clamps and connecting with existing cable all as specified and as directed.
M&L for repair and replacment of unserviceable time switch accessories/ spares including reconnecting and testing complete all as specified and as directed. Note : - Spares/accessories required for replacement shall be measured and paid sepratley under respective items of BoQ.
S&f in repairs, time switch analog type, single phase, 230 Volts of rating 20 Amps all as specified and as directed.
S&F in repairs, contactor, 40 amps, 4 pole, 415 volts fixing with existing box by suitable size of copper cable with suitable size of lugs all as specified and as directed.
S&F in repairs, contactor, 63 amps, 4 pole, 415 volts fixing with existing box by suitable size of copper cable with suitable size of lugs all as specified and as directed.
S&F in repairs, MCB TPN 16-32 Amps, 415 Volts, 50 Hz AC supply system all as specified and as directed.
S&F in repairs, MCB TPN 40-100 Amps, 415 Volts, 50 Hz AC supply system all as specified and as directed.
Supply, install, testing and commissioning in replacement of factory made and tested (including CPRI type test certified) LT Panel box Indoor type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated copper bus bars installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement comprises of following items. (Location- Dhobhighat Pump house) including taking down existing panel box with framework all as specified and as directed. Incoming (a) On load changeover switch 415V ,4pole,400 Amps (b) MCCB 400 amps, 4 pole, 35 KA, 415 volts grade, with thermal magnetic - 01 No (c) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, mounted on insulators for incomming supply - 01 Set. (d) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -01 set. (e) Neon indicating lamps (R, Y & B) -01 Set. Outgoing (a) MCCB 200 amps, 3 pole, 25 KA, 415 volts grade, with thermal magnetic - 04 No (b) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -04 set. (c) Neon indicating lamps (R, Y & B) -04 Set. (d) MCB TPN 63 amps, 4 pole, 10 KA , 415 volts, 50 Hz - 01 No. (e) MCB SPN 40 amps, 10 KA , 230 volts- 03 No. Note : Panel design will be approved by GE.
Supply, install, testing and commissioning in replacement of factory made and tested (including CPRI type test certified) LT Panel box Indoor type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated copper bus bars installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement comprises of following items. (Location- Dhobhighat Pump house) including taking down existing pannel box with framework all as specified and as directed. Incoming (a) On load changeover switch 415V ,4pole,200 Amps (b) MCCB 200 amps, 4 pole, 36 KA, 415 volts grade, with thermal magnetic - 01 No (c) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 300 Amp, 4 pole, mounted on insulators for incomming supply - 01 Set. (d) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -01 set. (e) Neon indicating lamps (R, Y & B) -01 Set. Outgoing (a) MCCB 160 amps, 3 pole, 36 KA, 415 volts grade, with thermal magnetic - 03 No (b) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -03 set. (c) Neon indicating lamps (R, Y & B) -04 Set. (d) MCB TPN 63 amps, 4 pole, 10 KA , 415 volts, 50 Hz - 01 No. (e) MCB SPN 40 amps, 10 KA , 230 volts- 03 No. (f) ML 4 ,75HP FASD Fully automatic star delta starter ,Make - L&T,-02 set Note : Panel design will be approved by GE.
Supply, install, testing and commissioning in replacement of factory made and tested (including CPRI type test certified) LT Panel box Indoor type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated copper bus bars installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement comprises of following items. (Location- Dhobhighat Pump house) including taking down existing pannel box with framework all as specified and as directed. Incoming (a) On load changeover switch 415V ,4pole,250 Amps (b) MCCB 250 amps, 4 pole, 36 KA, 415 volts grade, with thermal magnetic - 01 No (c) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 400 Amp, 4 pole, mounted on insulators for incomming supply - 01 Set. (d) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -01 set. (e) Neon indicating lamps (R, Y & B) -01 Set. Outgoing (a) MCCB 200 amps, 3 pole, 36 KA, 415 volts grade, with thermal magnetic - 03 No (b) Volt meter and Amp meter with selctor switch ,415 volts, 50 Hz AC supply -03 set. (c) Neon indicating lamps (R, Y & B) -04 Set. (d) MCB TPN 63 amps, 4 pole, 10 KA , 415 volts, 50 Hz - 01 No. (e) MCB SPN 40 amps, 10 KA , 230 volts- 03 No. (f) ML 4 ,75HP FASD Fully automatic star delta starter ,Make - L&T,-02 set Note : Panel design will be approved by GE.
S&F in repairs/replacement, XLPE insulated screened PVC bedded galvanised steel strip or wire armoured UG heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area of 10 sqmm 2 core size laid in trenches under floor/roads/hard standing along poles etc all as specified and as directed.
All as per serial item No 136 but 16 sqmm 4.0 core
All as per serial item No 136 but 25 sqmm 3.5 core
All as per serial item No 136 but 50 sqmm 3.5 core
All as per serial item No 136 but 95 sqmm 3.5 core
All as per serial item No 136 but 185 sqmm 3.5 core
All as per serial item No 136 but 240 sqmm 3.5 core
M&L for GI pipe 40 mm bore dia light grade fixing to wall or laying in floors for protection of cable complete all as specified and as directed.
M&L in repairs/replacement for earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting to the GI wire 4 mm dia , by means of nut bolts, check nuts and washer of the GI . Earth wire connected upto main earth point/DBs alongwith 15mm dia GI pipe, medium grade, including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion.
Excavation in trenches in soft/loose soil, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying pipes, cables etc or pits not exceeding 10 sqm area, and getting out and forming botton surface to required gradient all as specified and as directed.
Returning, filling in trenches including spreading levelling watering and well ramming in layer not exceeding 25 cm thick in soft/loose soil all as specified and as directed.
Removing excaveted soil to a distance n,exc 50 m and depositing where directed at a level n,exc.1.5 m above the starting point complete all as specified and as directed.
M&L for dry river sand in trenches for cushioning of underground cable with a layer of fine sand 8 cms thick before laying of cables and 15 cms thick after laying of cable including spreading, levelling, hand punning complete all as specified and as directed. Note:Punned thickness will be measured and paid.
Supply and laying well burnt, old size, sub class ‘B’ bricks locally available best quality, laid dry in trenches for protection of underground cable, laid flat with length for brick perpendicular to length of cable complete all as specified and as directed.
M&L for 70 sqmm, single core, 1100 volts grade, heavy duty cable, PVC insulated, copper conductor, served with inner sheathing of PVC tape and overall PVC sheathed including taking down old unserviceable cable and protection covers all as specified and as directed.
M&L for disconnect carefully incoming, out going electric connection, taking down existing ACB from MS Sheet steel encloser, supply and fix new ACB, 4 Pole, C power draw out 800 Amps rating braking capacity Icu = Icw 1 sec EDO Version as per L&T Cat Part No SL 95321 including Fabrication of new panel to suit fixing arrangement connect in coming out going cable connection with proper Lugs washer nuts bolts complete all as specified and as directed.
M&L in repairs, three core, 4 sqmm, 1100 volts, PVC Insulated & PVC sheated Industrial flat copper cable for submersible pump motors including water proof joint all as specified and as directed. Make- Havells Cat no.WHPNDSKG34X0 or equivalent from list of makes.
M&L for construction of valve pit/chamber of Internal dimensions 1500 mm x 1500 mm x 1500 mm, using PCC 1:4:8, type D-2, using 40mm graded stone aggregates for foundation, 23 cm thick, brick wall built in cement mortar (1:4) ,15 mm thick rendering all around the brick work in cement mortar (1:6), 75 mm thick PCC (1:2:4) type B-1 using 20mm graded stone aggregates in coping including necessary form work, 3 coats of white wash on rendered surfaces and on coping, 2 mm thick mild steel top sheet cover with frame made out of 40x40x6 mm angle iron, locking arrangement, including painting of steel surface with two coats of synthetic enamel paint over a coat of red oxide primer including demolition of existing valve chamber and clearing the debris complete all as specified and as directed.
M&L for preparation of surface of steel tubuler poles including connected cross arms, channels, clamps, street light brackets and GI protection pipes etc which are fitted on pole, by scrapping and applying two coats of aluminium paint and marking pole Nos on each pole with red and black colour radium paint alternate strips, 15 cm in width of each strip upto 1 m from bottom of the pole all as specified and as directed.
M&L for CI /DI fittings and specials such as bends (any type, radius and angle), tapers any type (straight, bend, increasing, decreasing or double socket etc.), Tee pieces single branch, "Y" junction, double branch, cross (all sockets or socket and spigot), Collars, Caps, Plugs, Connecting pieces one end flanged and other end socketed or spigot ends or all socketed / spigot ends etc for 200mm to 600mm bore dia including taking down existing CI/DI fittings and specials all as specified and as directed.
M&L for cutting existing 600 mm dia DI main pipe and inserting/fixing water meter 600mm dia size and stainer flanged including fittings, excavation and earthwork, jointing material such nut, bolts, washers etc complete all as specifed and as directed. Location : Dhobighat pump house Notes:- (i) Weight of fittings shall be included in the quoted rate. . (ii) T&P required for fixing such as ladder, Hydra vehicle, JCB, manpower etc, shall be included in the quoted rate of this item.(iii) Water meter will be issued under Sch'B' "FREE FOR FIXING iv) . The rates include for all jointing materials such as rubber/gaskets,bolts and nuts.(v) Excavation & earthwork shall be included in the quoted rate of this item
S&F in repairs, LED security light for buildings with single piece new generation energy saving and environmental friendly long life LED, 35 W, 230 volts, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete aluminium housing with acrylic covers as diffuser with IP 65/66 protection and impact resistance of IK07 and all acessories including one bracket made of light grade GI Pipe 32 mm dia, 1.5 mtr long fixed to wall/ pole with two clamps made out of mild steel flat iron 40 mm x 5 mm and connected to nearest electric supply with and including three core 1.5 sqmm aluminium conductor cable of suitable length complete all as specified and as directed. Make of LED : Havells Professional luminaries Cat Part No ENDURACITYLITEPLATPLUSSL35W LED757SASYBOPC or equivalent model of make Philips / GE/ Crompton/ Century LED/ Halonix/ SYSKA
S&F in repairs, LED security light for buildings with single piece new generation energy saving and environmental friendly long life LED, 60 W, 230 volts, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete aluminium housing with acrylic covers as diffuser with IP 65/66 protection and impact resistance of IK07 and all acessories including one bracket made of light grade GI Pipe 32 mm dia, 1.5 mtr long fixed to wall/ pole with two clamps made out of mild steel flat iron 40 mm x 5 mm and connected to nearest electric supply with and including three core 1.5 sqmm aluminium conductor cable of suitable length complete all as specified and as directed. Make of LED : Havells Professional luminaries Cat Part No ENDURAPEARLNEOSL60WLED 757PASYTOPC or equivalent model of make Philips / GE/ Crompton/ Century LED/ Halonix/ SYSKA
S&F in repairs, LED security light for buildings with single piece new generation energy saving and environmental friendly long life LED, 70 W, 230 volts, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete aluminium housing with acrylic covers as diffuser with IP 65/66 protection and impact resistance of IK07 and all acessories including one bracket made of light grade GI Pipe 32 mm dia, 1.5 mtr long fixed to wall/ pole with two clamps made out of mild steel flat iron 40 mm x 5 mm and connected to nearest electric supply with and including three core 1.5 sqmm aluminium conductor cable of suitable length complete all as specified and as directed. Make of LED : Havells Professional luminaries Cat Part No ENDURACITYLINERNEOSL70WLED 757PASYBOTG or equivalent model of make Philips / GE/ Crompton/ Century LED/ Halonix/ SYSKA
S&F in repairs, LED flood light, 70watt, 230v, AC outdoor type with thermal management in multiple optics and equipped with IP 66 protection,with impact and corrosion resistant complete with driver and lamp all as specified and as directed. Make of LED : Havells Professional luminaries Cat Part No JETAPROFL70WLED757LTG or equivalent model of make Philips / GE/ Crompton/ Century LED/Halonix/SYSKA
S&F in repairs, LED flood light, 100watt, 230v, AC outdoor type with thermal management in multiple optics and equipped with IP 66 protection,with impact and corrosion resistant complete with driver and lamp all as specified and as directed. Make of LED : Havells Professional luminaries Cat Part No JETAIRISFLS100WLED757APWBLTG or equivalent model of make Philips / GE/ Crompton/ Century LED/Halonix/SYSKA
S&F in repairs, LED solar street light fitting, 20 watt including galvanised steel pole 100mm bore dia 5m long, embedded in PCC 1:2:4, type B2 concrete, in built,lithium ion battery,solar panel,charge controller with disk down sensor, excavation and earthwork complete all as specified and as directed. Make of LED solar street light fitting : Havells Professional luminaries Cat Part No LHSTAKU7CBAF020 or equivalent model of make Philips / GE/ Crompton/ Century LED/ Halonix/ SYSKA
M&L in repairs/replacement of battery charger, 24 V DC SMPS 10 Amp for AMF panel all as specified and as directed.
BHAVIN INFRA
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .