| Sl No | Description | Qty | Unit | POWER TECH ENTEPRISES L2 | MERKURY ELECTRICAL CORPORATION L1 |
|---|---|---|---|---|---|
| 1.00Clean Room Light Fitting | |||||
| 1.01 | Site visit, lighting layout design, lux calculation/simulation, and engineering consultancy for clean room LED fittings as per IS standards/Clean room standards. | 1 | Lot | 25,000 ₹25,000 Lowest | 1,00,000 ₹1,00,000 |
| 1.02 | Supply, installation, testing, and commissioning of bottom openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of min 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600x600mm approximate weight ≤6 kg, featuring LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), LED efficacy >100 Lm,/Watt, Ambient temperature (0-50 degre)CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC,Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification of (as per IS standards) for general areas, for IVF workstations (as per standards). | 211 | Nos | 6,500 ₹13,71,500 | 5,658.68 ₹11,93,981.48 Lowest |
| 1.03 | Supply, installation, testing, and commissioning of bottom openable, recess-mounted stainless steel cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cut out size of 600x600mm), approximate weight ≤6 kg, featuring LED engine in stainless steel (SS 304/316 grade) or equivalent corrosion-resistant housing with polyester powder-coated finish option, PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation. LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification (as per IS standards) | 24 | Nos | 9,800 ₹2,35,200 | 7,919.18 ₹1,90,060.32 Lowest |
| 1.04 | Supply, installation, testing, and commissioning of top openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 3-5 (equivalent to FS209E Class 100-100000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600 x 600 mm approximate weight ≤10 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 580-600mm x 580-600mm cutout (compatible with existing 600x600mm), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, and auto cut-off safety feature.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification | 371 | Nos | 9,300 ₹34,50,300 Lowest | 9,370.35 ₹34,76,399.85 |
| 1.05 | Supply, installation, testing, and commissioning of top openable, recess-mounted cleanroom LED luminaire (1 ft x 1 ft size) suitable for ISO Class 3-5 (equivalent to FS209E Class 100-100000), with system efficacy ≥100 lm/W and minimum luminous flux of 1800 lumens. Luminaire dimensions shall be Compatible for existing cut out size, approximate weight ≤4 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 300mm x 300mm cutout (1 ft x 1 ft compatible), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, auto cut-off safety feature.LEDs sh all be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification. | 46 | Nos | 5,400 ₹2,48,400 Lowest | 8,122.95 ₹3,73,655.7 |
| 1.06 | Supply of bottom openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of min 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600x600mm approximate weight ≤6 kg, featuring LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), LED efficacy >100 Lm,/Watt, Ambient temperature (0-50 degre)CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC,Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification of (as per IS standards) for general areas, for IVF workstations (as per standards). | 20 | Nos | 6,400 ₹1,28,000 | 5,658.68 ₹1,13,173.6 Lowest |
| 1.07 | Supply of bottom openable, recess-mounted stainless steel cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cut out size of 600x600mm), approximate weight ≤6 kg, featuring LED engine in stainless steel (SS 304/316 grade) or equivalent corrosion-resistant housing with polyester powder-coated finish option, PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation. LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification (as per IS standards) | 2 | Nos | 9,750 ₹19,500 | 7,919.18 ₹15,838.36 Lowest |
| 1.08 | Supply of top openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 3-5 (equivalent to FS209E Class 100-1000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600 x 600 mm approximate weight ≤10 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 580-600mm x 580-600mm cutout (compatible with existing 600x600mm), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, and auto cut-off safety feature.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification | 30 | Nos | 6,500 ₹1,95,000 Lowest | 9,370.35 ₹2,81,110.5 |
| 1.09 | Supply of top openable, recess-mounted cleanroom LED luminaire (1 ft x 1 ft size) suitable for ISO Class 3-5 (equivalent to FS209E Class 100-10000), with system efficacy ≥100 lm/W and minimum luminous flux of 1800 lumens. Luminaire dimensions shall be Compatible for existing cut out size, approximate weight ≤4 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 300mm x 300mm cutout (1 ft x 1 ft compatible), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, auto cut-off safety feature.LEDs sh all be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification. | 4 | Nos | 5,500 ₹22,000 Lowest | 8,122.95 ₹32,491.8 |
Tender Value
₹74.3 L
EMD Value
₹1.9 L
Closing Date
4 Feb 2026, 12:00 pmClosed
Deputy General Manager
Integrated vaccine complex, Survey no 192 195, Meleripakkam village, Chengalpattu - 603003
Supply, Installation, Testing and Commissioning of clean room LED lighting fixtures at the IVC facility, Chengalpattu
2026_HBL_263748_1
HBL/LED/CR/IVC/CPT/25-26
Open Tender
Electrical Works
EPC Contract
45 days
HLL Biotech Limited
Please refer Tender documents.
19 documents required · 19 mandatory
₹2,950
Yes
HLL Biotech Limited
₹1.9 L
Yes
Online
17 Feb 2026
20 Jan 2026
5 Feb 2026
20 Jan 2026
4 Feb 2026
20 Jan 2026
23 Jan 2026
Clean Room Light Fitting
Site visit, lighting layout design, lux calculation/simulation, and engineering consultancy for clean room LED fittings as per IS standards/Clean room standards.
Supply, installation, testing, and commissioning of bottom openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of min 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600x600mm approximate weight ≤6 kg, featuring LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), LED efficacy >100 Lm,/Watt, Ambient temperature (0-50 degre)CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC,Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification of (as per IS standards) for general areas, for IVF workstations (as per standards).
Supply, installation, testing, and commissioning of bottom openable, recess-mounted stainless steel cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cut out size of 600x600mm), approximate weight ≤6 kg, featuring LED engine in stainless steel (SS 304/316 grade) or equivalent corrosion-resistant housing with polyester powder-coated finish option, PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation. LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification (as per IS standards)
Supply, installation, testing, and commissioning of top openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 3-5 (equivalent to FS209E Class 100-100000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600 x 600 mm approximate weight ≤10 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 580-600mm x 580-600mm cutout (compatible with existing 600x600mm), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, and auto cut-off safety feature.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification
Supply, installation, testing, and commissioning of top openable, recess-mounted cleanroom LED luminaire (1 ft x 1 ft size) suitable for ISO Class 3-5 (equivalent to FS209E Class 100-100000), with system efficacy ≥100 lm/W and minimum luminous flux of 1800 lumens. Luminaire dimensions shall be Compatible for existing cut out size, approximate weight ≤4 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 300mm x 300mm cutout (1 ft x 1 ft compatible), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, auto cut-off safety feature.LEDs sh all be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification.
Supply of bottom openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of min 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600x600mm approximate weight ≤6 kg, featuring LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), LED efficacy >100 Lm,/Watt, Ambient temperature (0-50 degre)CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC,Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification of (as per IS standards) for general areas, for IVF workstations (as per standards).
Supply of bottom openable, recess-mounted stainless steel cleanroom LED luminaire suitable for ISO Class 5-8 (equivalent to FS209E Class 100-100,000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cut out size of 600x600mm), approximate weight ≤6 kg, featuring LED engine in stainless steel (SS 304/316 grade) or equivalent corrosion-resistant housing with polyester powder-coated finish option, PMMA or polycarbonate diffuser, fully sealed with non-hygroscopic silicone/EPDM gasket achieving IP65 rating post-installation. LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80 and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing).Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults. Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification (as per IS standards)
Supply of top openable, recess-mounted cleanroom LED luminaire suitable for ISO Class 3-5 (equivalent to FS209E Class 100-1000), with system efficacy ≥100 lm/W and minimum luminous flux of 3600 lumens. Luminaire dimensions shall be compatible with existing cutout of 600 x 600 mm approximate weight ≤10 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 580-600mm x 580-600mm cutout (compatible with existing 600x600mm), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, and auto cut-off safety feature.LEDs shall be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification
Supply of top openable, recess-mounted cleanroom LED luminaire (1 ft x 1 ft size) suitable for ISO Class 3-5 (equivalent to FS209E Class 100-10000), with system efficacy ≥100 lm/W and minimum luminous flux of 1800 lumens. Luminaire dimensions shall be Compatible for existing cut out size, approximate weight ≤4 kg, featuring upgradable LED engine in polyester powder-coated CRCA or equivalent corrosion-resistant housing with high-efficiency translucent PMMA/polycarbonate diffuser, fully sealed with non-hygroscopic XLPE/silicone/EPDM gasket achieving IP65 rating post-installation, chamfered bottom edges for easy maintenance, designed for metallic walkable ceilings (50-80mm thick) via 300mm x 300mm cutout (1 ft x 1 ft compatible), flush top cover, frame load-bearing capacity ≥125 kg, loop-in-loop-out terminals, auto cut-off safety feature.LEDs sh all be LM-80 compliant from established manufacturers (e.g., Nichia, Cree, Bridgelux, Lumileds, Osram, Seoul or equivalent), with EN 62471 photobiological safety compliance (submit manufacturer certificate), CCT 5000-6500K, CRI ≥80, and L70 lifespan ≥50,000 hours at maximum drive current (submit full LM-80 report for ≥10,000 hours testing)Integrated isolated constant current LED driver shall support 150-280V AC, Constant Current - Constant Voltage LED Driver with APFC Construction, high voltage cutoff & auto restart @320V, phase to phase 440V protection upto 8hrs, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation, 50Hz input, with efficiency >85%, ≥3kV surge protection, power factor >0.95, THD <10%, and protections for short-circuit, open-circuit, and thermal faults.Compliance requirements include LM-79 (photometry/efficiency) and LM-80 reports from NABL/UL/ILAC accredited lab; manufacturer in-house testing lab accredited by NABL or equivalent Indian government body; standards IS 10322 Part 5/Sect 5, IS 16102/16105/16106/16108, IS 15885 Part 2/Sec 13, IEC 60598, RoHS; and post-installation lux verification.
Dismantling of existing light fittings with frame and arreange the same in Store room using mechanical means or physical means without disturbing the overall structure of proposed area. All items dismantled and shall be made a checklist for returning back to concerned Authorities. All items shall be verified by Electrical Engineer (HBL) before handing over. If any working product is damaged during transit, the same shall be replaced without any additional claim.
Refixing of rectified/verified fittings of existing light fittings using mechanical means or physical means without disturbing the overall structure of proposed area. All items dismantled and shall be made a checklist for returning back to concerned Authorities. All items shall be verified by Electrical Engineer (HBL) before handing over. If any working product is damaged during transit, the same shall be replaced without any additional claim.
Removal of damaged CFL bulb and refixing of conditioned CFL bulbs by mechanical means or physical means without structural disturbance; all dismantled items shall be checklist-inventoried for return to authorities, verified by Electrical Engineer (HBL) prior to handover, with replacement of any transit-damaged working items at no extra cost
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.51 MB
TEDOCLEANROOM.pdf
Tender Documents • 1.50 MB
BOQ_305972.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .