Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.3 LAccepted-AOC | ₹12.3 L Quoted ₹13.1 L | L1 | Accepted-AOC L1 |
| 2 | L2₹14.1 LRejected-Finance 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA | HARYANA | 133001 | ₹14.1 L | L2 | Rejected-Finance L2 |
| 3 | L3₹14.9 LRejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | ₹14.9 L | L3 | Rejected-Finance L3 |
| 4 | L4₹15.9 LRejected-Finance H NO 597 SEONA ROAD RANJIT NAGAR PATIALA PB 147001 | PATIALA | PATIALA | PUNJAB | 147001 | ₹15.9 L | L4 | Rejected-Finance L4 |
| 5 | L5₹16.7 LRejected-Finance BOOTH NO 119 SECTOR 9 PANCHKULA 134109 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134109 | ₹16.7 L | L5 | Rejected-Finance L5 |
| Sl No | Description | Qty | Unit | Arun enterprises L1 | M/S Sonu Traders L3 | u and v engineers and consultants L7 | Jawandha Enterprises L4 | Esha Engineers L2 | HARISH SALES CORPORATION L6 | bharat contrectors L8 | SHARMA ELECTRICAL ENGINEERS L5 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Dismantling old unserviceable LT panel including disconnecting connected cables complete all as specified and as directed., | 2 | Each | 100 ₹200 | 1,000 ₹2,000 | 500 ₹1,000 | 1,000 ₹2,000 | 500 ₹1,000 | 500 ₹1,000 | 100 ₹200 | 1,000 ₹2,000 |
| 2.00 | Material and labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415 Volts 3 Phase 4 Wire, 3.15 mm thick factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, sheet Outdoor double door Partially Type Tested Assembly Type (PTTA) LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with TPN PVC sleeved aluminium bus bar of size 250 Amps incld. angle iron base frame of suitable size. Including Panel mounted/grouted on 150 mm thick PCC (1:4:8) type D2 1 Mtr above ground level and with 500 mm offsets on all 04 sides of the panel complete and including spiral HDPE pipes for all cables under the PCC of panel inclusive of following accessories :-
A. INCOMING - (I) MCCB 100 Amps ,415 V 3 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable , Microprocessor release type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01Nos
B. OUTGOING -
(i) MCCB 63 Amps ,415 V 3 pole 25 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01 Nos
(ii) MCB TPN 63 Amp - 01 No.
(iii) MCB TPN 32 Amp - 03 No.
(iv) Spare cubicles for expansion as per MCCB 4P Amps - 02 Nos.
(v) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing
(vi) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as and including suitable size CTs (set of 3) - 01 No. (for Incoming feeder)
(vii) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos.
(viii) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | 1 | Each Job | 90,001 ₹90,001 | 65,000 ₹65,000 | 95,000 ₹95,000 | 1,05,000 ₹1.1 L | 94,000 ₹94,000 | 1,50,000 ₹1.5 L | 3,00,000 ₹3 L | 1,20,000 ₹1.2 L |
| 3.00 | Material and labour for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415 Volts 3 Phase 4 Wire, 3.15 mm thick factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, sheet Outdoor double door Partially Type Tested Assembly Type (PTTA) LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with TPN PVC sleeved aluminium bus bar of size 250 Amps incld. angle iron base frame of suitable size. Including Panel mounted/grouted on 150 mm thick PCC (1:4:8) type D2 1 Mtr above ground level and with 500 mm offsets on all 04 sides of the panel complete and including spiral HDPE pipes for all cables under the PCC of panel should be inclusive of following fitted in accessories :-
A. INCOMING - (I) MCCB 63 Amps ,415 V 3 pole 36 KA 50 Hz with Ics =100% Icu & thermal magnetic adjustable , Microprocessor release type including spreader terminals - set of 04 and direct rotary handle -01No as per OEM specifications- 01Nos
D. OUTGOING -
(i) MCB TPN 32 Amp - 04 No.
(ii) Spare cubicles for expansion as per MCCB 4P Amps - 02 Nos.
(iii) LED indicators - R/Y/B 240 V AC - 03 Sets of 03 Nos. per incoming & outgoing
(iv) Multifunction meter with accuracy Class 1.0, Flush mounting 96 x 96 mm, CT/PT site programmable for measurement of V, A, PF, kW, kVA, Load hours all as and including suitable size CTs (set of 3) - 01 No. (for Incoming feeder)
(v) MCB SP 'C' series 10kA 60-32 Amps as protection for LED lamps (01 No. each for set of 03 Nos. LED lamps, multifunction and single function meters) and multifunction meter - 2 Nos.
(vi) Control wiring with suitable size PVC insulated single core copper conductor cable for LED lamps, MFMs, etc. | 1 | Each Job | 60,004 ₹60,004 | 60,000 ₹60,000 | 85,000 ₹85,000 | 85,000 ₹85,000 | 90,000 ₹90,000 | 1,20,000 ₹1.2 L | 3,00,000 ₹3 L | 90,000 ₹90,000 |
| 4.00 | Material and labour for trenchless boring in any strata of soil across road, pavement,hardstanding etc upto depth as directed but not n,less than 0.60 mtrs below GL/road, pavement,hardstanding etc for laying of LT cable under road, pavement,hadrstanding without damaging existing under ground material complete all as specified and as directed. Note:- GI pipe shall be measured and paid separately under respective items of this schedule. | 20 | RM | 100 ₹2,000 | 400 ₹8,000 | 380 ₹7,600 | 500 ₹10,000 | 200 ₹4,000 | 400 ₹8,000 | 300 ₹6,000 | 350 ₹7,000 |
| 5.00 | Material and labour for 50 mm bore galvanized steel tubing light garde (ISI marked) for protection of cable fixed to pole/walls or laid in floors, road and duct crossing with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and as directed | 20 | RM | 200.08 ₹4,001.60 | 300 ₹6,000 | 320 ₹6,400 | 450 ₹9,000 | 250 ₹5,000 | 300 ₹6,000 | 100 ₹2,000 | 310 ₹6,200 |
| 6.00 | Dismantling concrete poles/ struts, any size complete all as specified and as directed | 13 | Each | 50.05 ₹650.65 | 700 ₹9,100 | 500 ₹6,500 | 500 ₹6,500 | 500 ₹6,500 | 500 ₹6,500 | 1,000 ₹13,000 | 500 ₹6,500 |
| 7.00 | Dismantling of cross arms of MS channel or angle etc complete setting aside for reuse within 50 m or remove from site complete all as specified and as directed. | 0.5 | Qtl | 505 ₹252.50 | 500 ₹250 | 1,000 ₹500 | 1,000 ₹500 | 100 ₹50 | 500 ₹250 | 1,000 ₹500 | 250 ₹125 |
| 8.00 | Dismantling insulators any type any size complete all as specified and as directed. | 20 | Each | 1 ₹20 | 10 ₹200 | 50 ₹1,000 | 50 ₹1,000 | 20 ₹400 | 40 ₹800 | 100 ₹2,000 | 1 ₹20 |
| 9.00 | Dismantling stay assembly complete including demolition of concrete and excavation etc complete all as specified and as directed | 3 | set | 100 ₹300 | 400 ₹1,200 | 200 ₹600 | 250 ₹750 | 100 ₹300 | 60 ₹180 | 100 ₹300 | 100 ₹300 |
| 10.00 | Dismantling earth wire or copper conductor, service fedder or distribution span complete all as specified and as directed. | 0.3 | Per Qtl | 505 ₹151.50 | 70 ₹21 | 1,000 ₹300 | 1,000 ₹300 | 100 ₹30 | 200 ₹60 | 1,000 ₹300 | 250 ₹75 |
Updated dates
Tender Value
₹24.7 L
EMD Value
₹49,400
Closing Date
17 Jan 2026, 6:00 pmClosed
HQ CWE PATIALA
HQ COMMANDER WORKS ENGINEER BLDG No 26 NEW LALBAGH PATIALA 147001 Contact 01712200082
CONVERSION OF OH LINE TO UG CABLE AT DAPPAR UNDER AGE (I) DAPPAR
2025_MES_745519_1
CWE/PAT/T-76/2025-26
Open Tender
Civil Works
120 days
AGE I DAPPAR
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
₹49,400
7 Feb 2026
20 Dec 2025
19 Jan 2026
20 Dec 2025
17 Jan 2026
3 Jan 2026
20 Dec 2025 - 30 Dec 2025
Dismantling old unserviceable LT panel including disconnecting connected cables complete all as specified and as directed.,
Dismantling of cross arms of MS channel or angle etc complete setting aside for reuse within 50 m or remove from site complete all as specified and as directed.
Dismantling earth wire or copper conductor, service fedder or distribution span complete all as specified and as directed.
Dismantling of ACSR or AAC conductor any size and any type complete all as specified and as directed .
Taking down old unserviceable cables/ service cable of any size complete all as specified and as directed.
Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 sqmm 4 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed.
Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sqmm 4 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed.
Supply,laying/fixing, jointing,testing and commissioning XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5 core laid in trenches/ducts/pipes/fixed on wall/pole etc complete all as specified and as directed.
Excavation in trenches in soft/loose soil n exc 1.5m wide and not Exc1.5m deep and getting out including forming bottom surfaces to required level or slope for taking out old cables,brick/PCC tiles covers complete all specified and all as directed .
Material and labour filling, spreading dry sand in trenches in layers for cushioning to under ground cable for protection of cable, 8cm deep before laying and 15 cm after laying the cable and punned to provide required cover complete all as specified and as directed. Note :- For payment Punned depth shall only be measured.
Removal of surplus excavated soil to a distance exc 50 m but not exc in 100 m and deposited where directed at a level n'exc 50 m above the starting point complete all as specified and as directed.
Returning filling in soil in trenches including spreading, leveling watering and well ramming in 25mm thick layers complete all as specified and as directed.
Supply and fixing weather proof Copper conductor 1.5 sqmm 3 core, round cable for connection from looping box to street light fitting in side the existing pole complete all as specified and as directed by Engineer-in-Charge.
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
BOQ_834788.xls
BOQ • 0.40 MB
TENDER762526.pdf
Tender Documents • 0.64 MB
Download all tender documents and submit your bid