Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 CrAccepted-AOC | ₹4.4 Cr Quoted ₹3.7 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹3.7 Cr+₹2.3 L (0.63%)Rejected-AOC | ₹3.7 Cr+₹2.3 L (0.63%) | L2 | Rejected-AOC L2 |
| 3 | L3₹3.8 Cr+₹8.0 L (2.16%)Rejected-AOC | ₹3.8 Cr+₹8.0 L (2.16%) | L3 | Rejected-AOC L3 |
Tender Value
Refer Docs
EMD Value
₹4.5 L
Closing Date
31 Mar 2025, 4:00 pmClosed
Ex.Eng.Mech.Ref
Municipal Workshop, 103, R.S.Nimkar Marg, Byculla , Mumbai
The work of Replacement / Providing of AHU at various locations at HBT Trauma Care Hospital, Jogeshwari (E) and Bharatratna Dr. Babasaheb AmbedkarMunicipal General Hospital, Kandivali (W).
2025_MCGM_1156486_1
DyChEng/mandE/3851/City
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
BDBA Hospital Kandivali anHBT Hospital Jogeshwari
Please refer Tender documents.
3 documents required · 3 mandatory
₹19,470
₹4.5 L
Municipal Workshop, 103, R.S.Nimkar Marg, Byculla
31 Jul 2025
11 Mar 2025
1 Apr 2025
11 Mar 2025
31 Mar 2025
11 Mar 2025
19 Mar 2025
Amount
Dismantling old Air Handling Unit and its accessories
Removing/ Dismantling of old 1.0/ 1.5 TR/ 2.0 window/ split AC/ FCU/ Cassette unit.
SITC of floor mounted chilled water double skin air handling unit construction, 25 mm thick insualted PUF panels, IP 55 TEFC IE2 motors, DIDW fan or PLUG Fan with VFD, chilled water cooling coil, Insulated drain pan, Pre-filter section, vibration isolators, canvas connections, with Frame Work etc of following capacity : 6000 - 7000 CFM 8Rows
SITC of floor mounted chilled water double skin air handling unit construction, 25 mm thick insualted PUF panels, IP 55 TEFC IE2 motors, DIDW fan or PLUG Fan with VFD, chilled water cooling coil, Insulated drain pan, Pre-filter section, vibration isolators, canvas connections, with Frame Work etc of following capacity 7000 - 8000 CFM 6Rows
SITC of floor mounted chilled water double skin air handling unit construction, 25 mm thick insualted PUF panels, IP 55 TEFC IE2 motors, DIDW fan or PLUG Fan with VFD, chilled water cooling coil, Insulated drain pan, Pre-filter section, vibration isolators, canvas connections, with Frame Work etc of following capacity 3000 - 4000 CFM 6Rows
SITC of Ceiling Suspended Chilled water double skin Air Handling Unit of mentioned capacities below: Specifications : 3000 - 4000 CFM Unit shall have Double Skin wall panels, 40 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD/8RD water cooled coil. Cooling oil shall have 12.5 to 15 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) ilters. Filter bank framework shall be fully sealed and constructed from GSS.
SITC of Ceiling Suspended Chilled water double skin Air Handling Unit of mentioned capacities below: Specifications : 1000 - 2000 CFM Unit shall have Double Skin wall panels, 40 mm thick sandwich PUF injected panels. Outer skin shall be 0.6 mm pre painted sheet with 275 GSM Zn coating. Inner sheet shall be 0.6 mm GSS, Complete with Glass view panel, marine light, limit switch, cable entry, GSS base frame. Screw less construction with zero leakage in the panel joints. Chilled water Coil - 6RD/8RD water cooled coil. Cooling oil shall have 12.5 to 15 mm dia (O.D) tubes minimum 0.35 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with SS Drain tray. Direct Driven Backward / Forward Curved Plug Fans with VFD, with Squirrel cage IE2 induction motor, Motor shall be suitable for operation of Variable Frequency Drive operation with 415±10% volts, 3 phase AC supply included with VFD. Each unit shall be provided with a factory assembled filter section containing pre filters( EU-4) ilters. Filter bank framework shall be fully sealed and constructed from GSS.
Nominal Capacity 2.0 TR (6050 Kcal / Hr. ( 1 indoor unit of 2.0 TR & 1 outdoor unit of 2.0 TR )
Nominal Capacity 3.0 TR Mega Split AC ( 1 indoor unit of 3 TR each & 1 outdoor unit of 3 TR.)
Providing & fixing of M.S.Cage / encloser for 2.0 TR Split A.C Units..
Providing & fixing of M.S.Cage / encloser for 3.0 TR Split A.C Units..
Providing & fixing of Refrigerant piping including electrical cabling & earthing as per specification.
GSS Ducting:- Supplying fabrication installation testing and commissioning of GI. Sheet metal ducting. Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive elastomeric foam gasket, Support etc as per SMACNA specification. GSS Ducting:- 24 SWG
GSS Ducting:- Supplying fabrication installation testing and commissioning of GI. Sheet metal ducting. Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive elastomeric foam gasket, Support etc as per SMACNA specification. GSS Ducting 22 SWG
Providing thermal insulation to supply air ducting with 19mm.thickness nitrile rubber
Providing & fixing of Canvas Connections for units.
Supply and installation of volume control dampers, bypass dampers.
SITC of the Vertical laminar air distribution ceiling (surgical module) suitable for Operating Theaters rooms
S & I of G.I. Powder Coated Rectangular Riser (Wall riser)
Providing fresh air damper with crowl piece,bird screen and removable type prefilters
Supply & fixing acoustic partition in the Plant room/AHU room
Providing aluminium supply air diffusers & return air grills with volume control dampers
75 mm diameter M.S. C class chilled water pipe line/drain line along with accessories and thermal insulation of nitrile rubber of 19 mm thk with glass cloth.
65 mm diameter M.S. C class chilled water pipe line/drain line along with accessories and thermal insulation of nitrile rubber of 19 mm thk with glass cloth.
50 mm diameter M.S. C class chilled water pipe line/drain line along with accessories and thermal insulation of nitrile rubber of 19 mm thk with glass cloth.
40 mm diameter M.S. C class chilled water pipe line/drain line along with accessories and thermal insulation of nitrile rubber of 19 mm thk with glass cloth.
25 mm diameter M.S. C class chilled water pipe line/drain line along with accessories and thermal insulation of nitrile rubber of 19 mm thk with glass cloth.
Providing & fixing of Drain piping as per specification.
Butterfly valves – 75 mm diameter
Butterfly valves – 65 mm diameter
Butterfly valves – 50 mm diameter
Butterfly valves – 150 mm diameter
Ball valves 40 mm diameter
Ball valves 25 mm diameter
Providing,fixing. testing & commissioning of 2- way mixing valve of-65 mm diameter
Providing,fixing. testing & commissioning of 2- way mixing valve of-50 mm diameter
Providing,fixing. testing & commissioning of 2- way mixing valve of-40 mm diameter
Providing,fixing. testing & commissioning of 2- way mixing valve of-32 mm diameter
Providing,fixing. testing & commissioning of 2- way mixing valve of-25 mm diameter
Y strainer-65 mm diameter
Y strainer-50 mm diameter
Y strainer-40 mm diameter
Y strainer-25 mm diameter
Supply and fixing of diaphragm type pressure gauges with necessary fitting and gate valve on chiller water inlet and outlet lines
Providing Digital temperature indicator with thermowell and senser on chiller water pipe line inlet, outlet and for return air
Auto air vents- 15 mm diameter auto air vents
S & I of Aluminium cladding for chilled water pipes
MS structure for AC works
Replacement of existing damaged false ceiling by new aluminum false ceiling sheets along with grid work
Supply and fixing 12 mm thick Marine Ply Plank
To make opening in the walls for laying of chilled water piping / drain piping, supply air duct, cable etc.& making them good as per original appearance
INDOOR LED FIXTURES - -LED Square Recessed Downlighter- 36W (600X600)
Light /Fan / Ex. fan Points Concealed Manner with Modular switches & FR wires
S & I of Cubical panel for chilled water AHU/ Refrigeration unit
1st category Cu armoured cables FRLS outer sheathed- 4C x 4 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 4C x 2.5 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 2.5 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 1.5 Sq.mm
Earthing Continuity Conductors -Bare G.I. Conductor size 8 SWG
SITC of fins type tube heater for 1 KW heater as per specifications
Rebate 2TR AC
Rebate for old AHU and its accessories CFM 2000 - CFM 7000
Vijay Traders (BID ID -6581622)
EMPAS ENGINEERING (BID ID -6574985)
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .