Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹75.4 LAccepted-AOC | ₹75.4 L | l1 | Accepted-AOC L1 |
| 2 | Rejected-Technical | - | - | Rejected-Technical REJECTED |
Tender Value
₹76.1 L
EMD Value
₹1.5 L
Closing Date
9 Jul 2024, 3:00 pmClosed
UNIVERSITY ENGINEER
GOA UNIVERSITY TALEIGAO PLATEAU GOA
Annual operation and maintenance of Electric sub stations and distribution of power supply within University campus during year 2024- 2025
2024_GU_15804_1
GU/9/2024-2025/Engg and Tech Div/ 48
Open Tender
Electrical Works
Item Rate
365 days
GOA UNIVERSITY TALEIGAO PLATEAU GOA
PLEASE REFER TENDER DOCUMENTS
5 documents required · 5 mandatory
₹8,000
₹1.5 L
5 Aug 2024
10 Jun 2024
10 Jul 2024
10 Jun 2024
9 Jul 2024
11 Jun 2024
Amount
Operation and maintenance of electric substation including four pole structure yard
Operation of diesel generators as and when required ( diesel shall be provided by the University free of cost). The scope of work includes providing manpower and minor materials such as insulation tape, fuse wire, screws etc. and maintenance. Other material needed for day to day maintenance shall be provided by University free of cost.
a) 11KV/440 Volts sub station-1 Job
b) 33KV/440 Volts sub station-1 Job
Operation and maintenance of external electrical installation including street lights, feeder pillars, distribution boards, underground cables, earthings etc. The scope of work includes providing required manpower needed for day to day operation and maintenance. Minor materials such as insulation tape, fuse wire, screw etc. and all other materials like fittings, fixtures will be supplied by the University free of cost-1 Job
Repairs and maintenance of external/internal electrical installation for all non-residential/ residential buildings temporary and permanent. The scope of the work includes providing required manpower needed for day to day operations and maintenance. Minor materials such as insulation tape, fuse wire, screw etc. and all other materials like fittings, fixtures will be supplied by the University free of cost-1 Job
Operation of A.C systems and audio video systems such as moving cordless mikes, operation of projectors, UPS systems, lights etc. inside the senate hall/ conference hall in main Administration building/ Seminar hall in Arts and Humanities building/ Silver Jubilee hall/ Auditorium halls in New Science Faculty building or any other location in the campus as instructed by Engineer-in-charge in the Goa University.
Filtration of transformer oil using suitable filtration machine at site.
Testing oil samples and issue the test certificate before and after TRF filtration.
Top up of new oil in transformer/OCB unit, make of oil (power oil)
Transport charges towards transportation of filtration machine to and from site and back.
Supply of silica gel
Supply of PVC container for silica gel
Supply and fixing of L.T cable jointing kit complete with all accessories including aluminium ferrules as required on site 3M make as per the following sizes of cable.
(a) 3 1/2 x 185 sq.mm (Cat No.SLA-9) Code No: 3MSCOTCHCAST450-9
(b) 3 1/2 x 240 sq.mm (Cat No.SLA-11) Code No: 3MSCOTCHCAST450-11
(c) 3 1/2 x 150 sq.mm or 3 1/2 x 120 sq.mm (Cat No.SLA-8) Code No: 3MSCOTCHCAST450-8
(d) 3 1/2 x 25 sq.mm to 3 1/2 x 35 sq.mm (Cat No.SLA-4) Code No: 3MSCOTCHCAST450-4
(e) 3 1/2 x 50 sq.mm (Cat No.SLA-5) Code No: 3MSCOTCHCAST450-5
(f) 4 x 16 sq.mm or 4 x 10 sq.mm (Cat No.SLA-3) Code No: 3MSCOTCHCAST450-3
(g) 4 x 6 sq.mm (Cat No.SLA-2) Code No: 3MSCOTCHCAST450-2
(h) 3 1/2 x 95 sq.mm (Cat No.SLA-7) Code No: 3MSCOTCHCAST450-7
(i) 3 1/2 x 400 sq.mm (Cat No.SLA-13) Code No: 3MSCOTCHCAST450-13
Earthwork in excavation by mechanical means ( hydraulic excavator manual means in foundation trenches drain ( not exceeding 1.5m in width or 10 sq.m on plan)) including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated sil as directed within a lead of 50 m. a. All kinds of soil.
b. All types of ordinary rock including all types of laterite rock, blasting prohibited.
Refilling the foundation trenches plinth sides, foundation etc. with available excavated earth in layers not exceeding 20 cm depth consolidating each layer ramming and watering lead upto 50 m and all lifts and disposal of surplus earth as directed by Engineer in charge.
Clearing jungle including rank vegetation grass bush wood trees and sapling of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish upto distance of 50 m, outside the periphery of the area cleared ( if however, only grass is met with the area will be measured and paid under item 4001)
Supply and fixing of heat shrink straight through cable jointing it complete with all accessories including aluminium ferrules and other related accessories complete as required on site 3M make as per the following sizes of cable
(A) 3 ½ x 6 Sq.mm to 3 ½ x 16 Sq. mm size
(B) 3 ½ x 25 Sq.mm to 3 ½ x 50 Sq. mm size
(C) 3 ½ x 70 Sq.mm to 3 ½ x 150 Sq. mm size
(D) 3 ½ x 185 Sq.mm to 3 ½ x 300 Sq. mm size
(E) 3 ½ x 400 Sq.mm to 500 Sq.mm
Servicing of L.T air circuit breakers including testing, calibrating and adjusting ACB release, pole assembly and FRCD mechanisms in breaker overhauling and cleaning various operating mechanisms/ contacted/ linkages complete as required for following rated and type of breakers of L&T make through the technicians of L&T service dealer ( test certificate to be submitted from the L&T service dealer after testing)
(i) 1000A/ 1600A, S/3PMDO/SR 18G
(ii) 2000 AS14PEDO/DN1
(iii) 1000 A/800 A, S14PEDO/DN1
(iv) 1000A CHPM DO/DN1, Schneider/ L&T make
Supply and fixing of 11KV indoor type end termination kit suitable for 3 core screened XLPE cable of size
(a) 95 sq.mm, 3M make Code no: MH1 x 22 KVE 3C
(b) 185 sq.mm, 3M make Code no: MH1 x 22 KVE 3C
Supply and fixing of 11KV outdoor type end termination it suitable for 3 core screened XLPE cable of size
(a) 185 sq.mm, 3M make Code no: MH1 x 22 KVE 3C
Supply and fixing 33K indoor type end termination kit suitable for 3 core screened XLPE cable of size
(a) 95 sq.mm to 150 sq.mm, 3M make Code no: MH1P33KVE3C
Supply and fixing 33KV outdoor type end termination kit suitable for 3 core screened XLPE cable of size
(a) 95 sq.mm to 150 sq.mm, 3M make Code no: MH1P33KVE3C
Servicing of H.T breakers including testing, calibrating and adjusting circuit breakers release, pole assembly and other mechanisms in breaker overhauling and cleaning various operating mechanisms/ contacts/ linkages complete as required for following rated and type of breaker Megavin MEI make through the technicians of Megavin or MEI service dealer (test certificate of the service dealer in original to be submitted from the dealer after testing)
(i) 800A, oil circuit breaker 11KV, 50Hz, MEI make type GUD
(ii) 800A, vacuum circuit breaker 11KV, 50Hz, MEI make type VCB
(iii) 1250A, vacuum circuit breaker 33KV, 50Hz, Megavin make type MHVCB
(iv) 630A, vacuum circuit breaker 33KV, 50Hz, Megavin make type MHVCB
Supply of 3 1/2 / 4 core armoured PVC/XLPE insulated PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS: 1554 (Part I), IS: 7098 (Part I) with latest amendments of following size
(i) 3 1/2 core 25 sq.mm
(ii) 3 1/2 core 35 sq.mm
(iii) 3 1/2 core 120 sq.mm
(iv) 3 1/2 core 150 sq.mm
(v) 3 1/2 core 185 sq.mm
(vi) 3 1/2 core 50 sq.mm
(vii) 3 1/2 core 95 sq.mm
(viii) 4 core 10 sq.mm
(ix) 3 1/2 core 240 sq.mm
(x) 3 1/2 core 400 sq.mm
Inspection and testing of earth electrode resistances with necessary earth megger tester and submission of reports of the resistance of the earthing electrodes complete as required.
Inspection, testing, repairing (excluding cost of spares, such as insulators, lightning arrestors, nuts and bolts etc.) of 11KV/33KV D.P switch including greasing and painting with suitable primer and enamel paint wherever required and submission of report regarding the condition of the D.P structure including A.B switch complete as required.
Inspection, cleaning with suitable air blower, testing of external L.T feeder pillars including greasing and painting with suitable primer and enamel paint of base metal stand and submission of reports as required
Vacuum cleaning of indoor L.T panels including cleaning the busbar chambers, switches and cleaning and tightening the contacts and submitting reports of the panel
Work of cable fault identification and pin pointing using precision cable fault finding equipment for all 1.1KV cables from 10 sq.mm - 400 sq.mm for a length of upto 100mts. For every meter above 100 mts Rs. 10 per meter will be charged extra.
Work of cable fault identification and pin pointing using precision cable fault finding equipment for all HT cables of 11KV and 33KV from 70 sq.mm - 400 sq.mm for a length of upto 100mts. For every meter above 100 mts Rs. 13 per meter will be charged extra.
Supply of Battery charger 24V 20A
Supply and fixing stainless steel rectangular type hinges on site, including drilling holes, providing SS nut bolts, washer of suitable size complete with labour charges as required for outdoor FRP feeder panels with following size hinges.
(1) 5" SS hinges
(2) 4" SS hinges
(3) Tower bolted door lock Aluminium 6" Size
Providing and fixing following rating and breaking capacity fixed type/adjustable 3 pole MCCB inside the existing cubicle panel board including drilling holes in cubicle panel making connections etc. as required
(j) 250 A Adjustable 35/40 KA, CAT B
(k) 400 A 35 KA/40KA, CAT B
(l) 630 A 35 KA/40KA, CAT B
Supply & fixing of Air Circuit Breaker motor , 240V, 50Hz A.C L&T make
Supply & fixing of ACB closing coil 240V 50Hz, A.C of L&T make
Supply & fixing of ACB General Industrial controls timer, Micon 17, L&T make
Dismantling of old existing switch fuse unit from L.T panel including trolley unit base busbar connections, C.T units as required
Supply and fixing of LED indicating lamp, 230 Volts, A.C, on L.T panel as required
Supply and fixing of external rotary handle mechanism suitable for
(a) 250A MCCB
(b) 400A MCCB
(c) 630A MCCB
Supply and fixing of digital type A.C Ammeter, 230V 500 A as required
Supply and fixing of pre-fabricated 145 WG M.S sheet front cover lid for MCCB enclosure complete with provision for fixing all accessories as per site requirement and hinged to main panel including powder coating etc., complete as required
Supply of power pack 230V AC/ 110V DC with battery backup of Megavin make in 33kV substation
Job of disconnecting, dismantling of old power pack and installation of power pack in the existing 33KV VCB panel by studying the existing circuitry
Supply and fitting of 24V power pack in 11kV substation
Replacement of all indicator etc. of 11KV / 33kV feeders
Supply and installation of 110V DC tripping coil assembly of MEGAWIN make for VCB in 33kV substation
Supply, Installation, testing of ACB undervoltage coil spares of L&T make through the technicians of L&T service dealer ( test certificate to be submitted from the L&T service dealer after testing)
(i) Undervoltage release 240 VAC
(ii) Arcing contacts fix - 800A
(iii) Arcing contacts Moving - 800A
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .