| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.4 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹4.5 L+₹14,500 (3.33%)Rejected-Finance 702 A1 SHREE PRASAD TAWADEWADI SHREE DATTAGURU PARK KUMBHARWADA URAN DIST RAIGAD MAHARASHTRA 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | L2 | Rejected-Finance L2 Bidder | |
| 3 | L3₹4.7 L+₹29,301 (6.73%)Rejected-Finance | L3 | Rejected-Finance L3 Bidder | |
| 4 | L4₹4.7 L+₹37,600 (8.63%)Rejected-Finance | L4 | Rejected-Finance L4 Bidder | |
| 5 | L5₹4.8 L+₹43,850 (10.1%)Rejected-Finance FLAT NO 201 GREEN VALLEY CHS PLOT NO 26 SECTOR 19 NERUL EAST NAVI MUMBAI 400 706 | THANE | MAHARASHTRA | 400706 | L5 | Rejected-Finance L5 Bidder |
Tender Value
Refer Docs
Closing Date
1 Apr 2020, 6:00 pmClosed
CWE Karanja
CWE Karanja, Naval Station Karanja, Uran, Raigad, MH 400704.
Job Work for disconnection of Old LT Cable Panel and refixing New LT Panel at Sub Station K at INS Tunir at Naval Station Karanja
2020_MES_335257_1
30001/EQJO/19-20/45/E3
Open Tender
Job Works
Works
30 days
CWE Karanja
Please refer Tender documents.
3 documents required · 3 mandatory
₹0
Exempted
13 Apr 2020
19 Mar 2020
3 Apr 2020
19 Mar 2020
1 Apr 2020
19 Mar 2020
Amount
4. M&L for disconnecting connected cables, and supplying, installing, testing and commissioning of factory made LT cubical double door panel, Indoor type, of Suitable to accomodate the following accessories made out of CRCA sheet 2.15 MM thick duly powder coated with Seimens Grey Shade RAL 7032, totally enclosed, dust and vermin proof outer cubicle. CRCA sheet with working voltage of 415V, 50 Hz, 3 phase 4 wire fully compartmentalised with single door system for each compartment.. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. The cubicle incomer MCCB as well as outgoings shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders with Ics = 100% Icu in all MCCBs with extended Rotary Handle. The cubicle should be inclusive of following : The cubicle should be inclusive of following :
Location : Sub Station 'K' (A) INCOMING - (a) Air Circuit breaker with micropressor release 4 pole, 800 Amps, 50 kA, manual Drawn out type.Make Havells Cat Part No. IHAFE2E080**# with O/L, S/C & E/F protections or equivelent in Siemens/Havells/L&T/HPL - 01 No (B) OUTGOING - (a) Air Circuit breaker with micropressor release 4 pole, 600 Amps, 50 kA, manual Drawn out type.Make Legrand/L&T Cat Part No. 028734 + 028802 with O/L, S/C & E/F protections or equivelent in Siemens/ABB/L&T/HPL - 01 No (b) MCCB -DPX3 630 thermal & magnetic type 3 pole 415 volt 36 kA breaking cap. adjustable thermal release range 400 Amps Cat ref no. 4220 16 of make Legrand or equivalent in M/s Schenider/M/s L&T/HPL – 03 No.
Sagar Electricals
R A Electric Co.
D.N.PATIL
M.K Enterprises
CHINMAY ENTERPRISES
M/S NOBLE TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .