Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.9 CrAccepted-AOC 701 HEADQUARTERS SANT DNYANESHWAR MARG CHETANA COLLEGE ADJUNCT BANDRA EAST MUMBAI 400051 | MUMBAI SUBURBAN | MAHARASHTRA | 400051 | ₹16.9 Cr | L1 | Accepted-AOC Being lowest and reasonable tender |
| 2 | L2₹17.6 CrRejected-Finance | ₹17.6 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹19.8 CrRejected-Finance | ₹19.8 Cr | L3 | Rejected-Finance Not being the lowest |
Tender Value
₹16.5 Cr
EMD Value
₹11.5 L
Closing Date
14 Dec 2021, 6:00 pmClosed
Chief Engineer (Navy) Mumbai
HQ Chief Engineer (Navy) Mumbai, 26 Assaye Bldgs, SBS Rd, Colaba, Mumbai-05
PROVISION OF DEFICIENT STORE HOUSE, REPAIR WORKSHOPS, TECHNICAL ACCOMMODATION AND ASSOCIATED FACILITIES AT MO (MB), GHATKOPAR
2021_MES_483410_1
87894/E8
Open Tender
Civil Works
730 days
Ghatkopar
As per tender documents
8 documents required · 8 mandatory
₹3,000
GE (P) BHANDUP
₹11.5 L
Yes
HQ Chief Engineer (Navy) Mumbai
6 Apr 2022
23 Oct 2021
16 Dec 2021
23 Oct 2021
14 Dec 2021
30 Nov 2021
23 Oct 2021 - 1 Nov 2021
1 Nov 2021
Amount
SCHEDULE "A" Part - I (BUILDINGS & STRUCTURES WORKS) Total of Sch-'A' Part-I B/F
SCHEDULE "A" PART-II (SITE CLEARANCE, AREA DEVELOPMENT, EXCAVATION & EARTHWORK) Total of Sch-'A' Part-II B/F
SCHEDULE "A" PART-III (DEMOLITION/ DISMANTLING) Total of Sch-'A' Part-III B/F
SCHEDULE "A" PART-IV (INTERNAL WATER SUPPLY) Total of Sch-'A' Part-IV B/F
SCHEDULE "A" PART-V (INTERNAL ELECTRICFICATION) Total of Sch-'A' Part-V B/F
SCHEDULE "A" PART-VI (ROAD & HARDSTANDING) Total of Sch-'A' Part-VI B/F
SCHEDULE "A" PART-VII (SEWAGE DISPOSAL) Total of Sch-'A' Part-VII B/F
SCHEDULE "A" PART-VIII (AREA DRAINAGE) Total of Sch-'A' Part-VIII B/F
SCHEDULE "A" PART-IX (EXTERNAL ELECTRIFICATION) Total of Sch-'A' Part-IX B/F
SCHEDULE "A" PART-X (EXTERNAL WATER SUPPLY) Total of Sch-'A' Part-X B/F
SCHEDULE "A" PART-XI (FIREFIGHTING) Total of Sch-'A' Part-XI B/F
SCHEDULE "A" PART-XII ( LIFT / DG SET ) Total of Sch-'A' Part-XII B/F
SCHEDULE "A" PART-XIII ( LIGHTNING PROTECTION ) Total of Sch-'A' Part-XIII B/F
SCHEDULE "A" PART -XVI (MISCELLANEOUS ITEMS)
SITE CLEARANCE & EARTHWORK
Removing excavated material (any type) and depositing it outside Ministry of Defence Land. Note for 16.001 (i) Before quoting the tender, the bidders are advised to ascertain the distance outside MD and, at which the excavated material/ debris are to be disposed off. No extra claim what-so-ever shall be entertained on this account. (ii) This item shall be considered as per the requirement at site. (iii) All excavation earthwork covered under Sch'A' part III to part XIV shall be measured and paid under this item.
Removing debris obtained from demolition of buildings and depositing it outside Ministry of Defence Land. Note for 16.002 (i) Before quoting the tender, the bidders are advised to ascertain the distance outside MD and, at which the excavated material/ debris are to be disposed off. No extra claim what-so-ever shall be entertained on this account. (ii) This item shall be considered as per the requirement at site.
DEMOLITION / DISMANTLING
Taking down copper/Aluminium point wiring (Light, fan, socket or power) complete including fixture and fitting such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. Removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) complete all as specified and directed.
Taking down carefully by unscrewing from boards/ outlet boxes, fittings & fixture such as switches, sockets, ceiling roses, lamp holder, ceiling fans/Exhaust fan, geyser & regulators complete all as specified. (Ceiling fans/exhaust fans/geysers to be deposit in MES store for reuse)
Taking down all type of old unserviceable MCB/TPN DBs etc complete all as specified and directed.
Taking down all type of old unserviceable MCBs (SP/SPN/TPN/TP) etc complete all as specified and directed.
Taking down U/S Submain wiring of copper/ Aluminium twin core cable of various sizes complete.
Disconnecting the electric supply from the panel board and dismantling panel board.
Taking down carefully by unscrewing light fittings of any type (tube lights fittings) any wattage etc.
INTERNAL WATER SUPPLY
S & F two way bib cock with wall flange quarter turn (Low-flow) 16 mm dia , complete all as specified and directed by Engineer-in-Charge. Make Jaquar Model No KUP-35041PMGE or equivalent in Crab Tree/Kohler brand
S & F Pillar Cock (Low-flow) 16 mm dia. complete all as specified and directed by Engineer-in-Charge. Make- Jaquar Model No KUP-35001PMG or equivalent in Crab Tree/Kohler brand
S & F Angular Stop Cook 15 mm bore of pipe (16 mm outer dia) with Wall Flange chromium plated Stop valves complete all as specified and directed. Make- Jaquar Model No KUP-35053PM or equivalent
S & F Hand shower (Health faucet) with 1 meter long easy flex tube in chrome finish and wall hook with NRV (Back flow preventer) complete all as specified and directed. Make Jaquar Model No ALD-579
INTERNAL ELECTRIC SUPPLY
S & F modular type 25/32 A SP MCB, conforming to IS 60898- 1: 2002 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Mylinc Cat. Part No. 6759 74 or equivalent model of Anchor or L & T
S & F modular type 3 pin 25/32 A socket, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Ekinox³ Cat-Part No. 5734 66 or equivalent model Anchor Cat-Part No. Penta 65206 or L & T Cat-Part No. OC31W25
S & F factory made screwless, dust proof cover plates having superior finish, rounded corners, and solid strength supported by plastic frame behind with flexible wall alignment, horizontal adjustment facility complete all as specified and directed.
a) 12 module Make: Legrand Arteor Cat-Part No. 5757 70 or equivalent model of Havells or Anchor
b) 18 module Make: Legrand Arteor Cat-Part No. 5757 90 or equivalent model of Havells or Anchor
S & F factory made not less than 1.2 mm thick sunken, modular flush sheet galvanized metal enclosure having zinc coating not less than 120 GSM, , conforming to IS 14772: 2000, having top, bottom, side and back-wall knockouts for conduit entry from any direction, suitable modular cover-plates complete all as specified and directed by the engineer-in-charge.
a) 8 module Make: Legrand Arteor Cat-Part No. 6890 42 or equivalent model of Havells or Anchor
b) 12 module Make: Legrand Arteor Cat-Part No. 6890 11 or equivalent model of Havells or Anchor
c) 18 module Make: Legrand Arteor Cat-Part No. 6890 12 or equivalent model of Havells or Anchor
S & F vertical triple pole & neutral, double door, metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed by engineer-in-charge. Make: Legrand, Schneider, L & T NOTE: [i] FP MCCB & SP/TP MCBs shall be measured and paid separately.
a) Verticle triple pole & neutral double door DB, 6 way
b) Verticle triple pole & neutral double door DB, 8 way
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Schneider, Legrand, L & T
(a) 6- 32 A, 230 V, 50 Hz, SP MCB (C curve)
(b) 6- 32 A, 230 V, 50 Hz, SPN / DP MCB (C curve)
(c) 6- 32 A, 415 V, 50 Hz, TP MCB (C curve)
(d) 6- 32 A, 415 V, 50 Hz, FP MCB (C curve)
(e) 40-63 A, 415 V, 50 Hz, TP MCB (C curve)
(f) 40-63 A, 415 V, 50 Hz, FP MCB (C curve)
S & F moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instantaneous protection, earth fault leakage protection, etc. having Ics = 100% as per IEC 60947-2 complete all as specified and directed by Engineer-in-charge. Make: Schneider, Legrand, L & T
(a) 125 A, 25 kA, 415 V, 50 Hz, FP MCCB
(b) 100 A, 25 kA, 415 V, 50 Hz, FP MCCB
(c) 63 A, 25 kA, 415 V, 50 Hz, FP MCCB
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type WORKSHOP PANEL - 1 & 2 of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. (for lift & machine room DBs) Make: L & T, Schneider, Siemens, ABB The WORKSHOP PANEL - 1 shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 400 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 250 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos.
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING [i] 100 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 03 Nos. [ii] 63 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 08 Set [iv] Digital ammeter of suitable capacity with suitable CTs for each feeder- 05 Nos. NOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM) or their channel partner only and certificate to that effect before sample approval be placed on record. [ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (iii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class B, 2.5 mm thick as per IS-15652(2006).
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type BUILDING PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. (for lift & machine room DBs) Make: L & T, Schneider, Siemens, ABB The BUILDING PANEL shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 400 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 250 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos.
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING [i] 125 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] 40 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [iii] 32 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 04 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 08 Set [v] Digital ammeter of suitable capacity with suitable CTs for each feeder- 06 Nos. NOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM) only. [ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (iii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class A , 2.0 mm thick as per IS-15652(2006)
S & F 40 W surface / wall mounted LED batten capable of delivering 3600 lumen, having PC diffuser, luminous efficacy of > 100 lumen/W, CRI > 80, PF > 0.9, CCT 5700K, independent isolated SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips/Wipro/Surya
S & F 20 W surface / wall mounted LED batten capable of delivering 2000 lumen, having PC diffuser, luminous efficacy of > 100 lumen/W, CRI > 80, PF > 0.9, CCT 5700K, independent isolated SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips/Wipro/Surya
S & F 10 W surface / wall mounted LED batten capable of delivering 1150 lumen, having PC diffuser, luminous efficacy of > 100 lumen/W, CRI > 80, PF > 0.9, CCT 5700K, independent isolated SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips/Wipro/Surya
S & F 30 W recessed mounted square shape 2' X 2' LED panel capable of delivering 3000 lumen having high efficiency long life LED package in integral module with luminous efficacy of > 120 lumen/W with CCT 5700K, independent isolated SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high transmittance polystyrene opal diffuser, housed in white powder coated pressure die-cast aluminium heat sink having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: Philips/Wipro/Surya
S & F 12 W recessed mounted round shape LED downlight capable of delivering 1200 lumen. having minimum luminous efficiency > 100 lumen/W, CCT 5700K, CRI > 80 with THD< 10%, high quality polycarbonate diffuser, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection complete all as specified and directed by the engineer-in-charge. Make: Philips/Wipro/Surya
S & F 20 W surface mounted round shape LED downlight capable of delivering 2000 lumen. having minimum luminous efficiency > 100 lumen/W, CCT 5700K, CRI > 80 with THD<10%, high quality polycarbonate diffuser, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection complete all as specified and directed by the engineer-in-charge. Make: Philips/Wipro/Surya
S & F 118 W High bay light duranto mounted LED, LED capable of delivering 14300 lumen, extruded aluminium housing with PC diffuser and integrated electronic driver with high efficiency long life LED chips, CRI > 70 with THD<10% and CCT 5700K, power factor ≥ 0.95, system luminous efficacy > 120, having average life 50000 hrs, operating voltage 140- 270, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the LED fitting including hanging arrangements from ceiling with SS chain 2 meter height complete all as specified and directed. Make: Philips/Wipro/Surya
S & F 25 W street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 2600 lumen/W, integral SMPS based constant current electronic LED driver with THD < 10% with CCT 5700K, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high efficiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enamel paint over a coat of red oxide primer complete in all respect as specified and directed by engineer-in-charge. (for building) Make: Philips/Wipro/Surya
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. ENTRUST 50- 5 STAR or equivalent model of Havells Cat-Part No. ES - 50 Premium or BAJAJ Cat-Part No. Electra 50
S & F energy efficient non-metallic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. VENTILUS 10" or equivalent model of Havells Cat-Part No. Ventil Air - DX White or BAJAJ Cat-Part No. Maxima DX
S & F energy efficient metallic exhaust fan having blade sweep 300 mm, air delivery not less than 6000 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. (for lift machine room & substation) Make: Crompton Cat-Part No. EXHD300- 4-1 or equivalent model of Havells Cat-Part No. Ventil Air - DSP or BAJAJ Cat-Part No. Max Air
S & F wall fan having blade sweep 600 mm, air delivery not less than 125 m³/min, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. WM Fizzair or equivalent model of Havells Cat-Part No. Turbo Force or BAJAJ Cat-Part No. Esteem
S & F of 16’ sweep high volume low speed (HVLS) fan having 5 aerofoil blades, air movement >=185650 ft3/min, coverage diameter ≥ 100’ velocity ≤ 70 rpm and a motor suitable for 3-Phase, 415 V, 50 Hz electric supply and rating ≤ 1.5 HP, suitable for minimum installation height (blade distance from floor) of 16’ complete with accessories all as specified and directed by the engineer-in-charge. Make: M.G Engineers, Heli fan, Ecoair or GECPL
S & F 2.0 mm thick 50 mm X 200 mm perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittings viz. joints, bends, tees, etc. in convenient sections of length.
S & F 2.0 mm thick 50 mm X 150 mm perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittings viz. joints, bends, tees, etc. in convenient sections of length.
S & F 2.0 mm thick 50 mm X 100 mm perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittings viz. joints, bends, tees, etc. in convenient sections of length.
M & L of structural steel for cable tray support structure with painting as recommended by OEM.
EXTERNAL ELECTRIFICATION
Supply, installation, testing and commissioning of Indoor type 3-Ph, 630 A, 12 kV, 50 Hz dead front, floor-standing, fully compartmentalized metal clad dust, damp and vermin-proof HT Panel conforming to IEC 62271-200, having 26.3 kA short time withstand current (for 3 sec) & internal arc tested for 26.3 kA (1 sec) with provision of bolting to the floor, suitable for severe tropical climate conditions conforming to IEC 60068-2-30, having separately earthed IP 67 rated HV and busbar compartments and IP4X rated LV compartment made of 2.5 mm thick for load bearing and 2.0 mm thick for non load bearing high quality galvanised steel sheet, indoor type motor operated spring closing vacuum circuit breaker (VCB) conforming to IEC 62271-100 with suitable adaptor box / bus riser and copper conductor of suitable size for connecting to existing VCB having SCADA compatible facilities and complete with all accessories, short-circuit and earth fault protection for rupturing capacity of 350 MVA complete as specified and directed by the engineer-in-charge. Make: Schneider, ABB, Siemens, L & T
[vi] PT shall be 3-Phase 11000/110 Volts, 3-Limb type with 50 VA per phase of class 0.5/3P accuracy and shall be mounted on incomer breaker truck. The same shall be mounted in a separate withdrawable truck in a separate vertical panel for bus connected PT. [vii] Control supply for closing and tripping shall be 110 / 220 V DC through an external battery source. 230 V, 50 Hz 1-Ph AC supply shall be also be available for the operation of spring charging motor and cubical space heater. Wattage rating of closing and tripping coils shall be within 250 W. [viii] All other secondary wiring in the panel shall have high quality PVC insulation and the same shall have conductor size of not less than 1.5 m2 copper. NOTES: [i] The HT Panel shall be purchased from the original equipment manufacturer (OEM). [ii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. for approval of the Engineer-in-Charge. [iii] The bidder shall intimate the Engineer-in-Charge of the routine tests in accordance with IEC 62271-200 & IEC 62271-100 in the OEM factory in presence of a representative nominated by the Engineer-in-Charge. before dispatch. (iv) The VCB shall be with antipumping feature by default with no additional relay used. (v) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class B, 2.5 mm thick as per IS-15652(2006).
[v] 32 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. (for street light) [vi] LED phase indicators (Red, Yellow, Blue)- 06 Set [vii] Digital ammeter of suitable capacity with suitable CTs for each feeder- 06 Nos. NOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM)/ channel partner of OEM only and certificate to that effect shall be placed on record before sample approval. [ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (iii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class A, 2.0 mm thick as per IS-15652(2006).
Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type UTILITY PANEL of suitable size, conforming to IS/IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by Engineer-in-charge. (for lift & machine room DBs) Make: L & T, Schneider, Siemens, ABB The UTILITY PANEL shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 200 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos.
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING [i] 63 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 03 Nos. (for spare, & Lift- 02 nos.) [ii] 40 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. (for 10TON crane ) [ii] 32 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. (for 5TON crane ) [iii] LED phase indicators (Red, Yellow, Blue)- 07 Set [iv] Digital ammeter of suitable capacity with suitable CTs for each feeder- 07 Nos. NOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM)/ channel partner of OEM only and certificate to that effect shall be placed on record before sample approval. [ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (iii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class A, 2.0 mm thick as per IS-15652(2006).
[ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING [i] 250 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 03 Nos. (for Workshop panel-1 and 2 and 01 spare) [i] 125 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. ( Spare) [iv] LED phase indicators (Red, Yellow, Blue)- 06 Set [v] Digital ammeter of suitable capacity with suitable CTs for each feeder- 04 Nos. NOTES: [i] The Panel shall be purchased from the original equipment manufacturer (OEM)/ channel partner of OEM only and certificate to that effect shall be placed on record before sample approval. [ii] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (iii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class A, 2.0 mm thick as per IS-15652(2006).
M & L for GI octagonal poles complete with single armed brackets as specified all for 6.0 m long with 70 mm top diameter and 130 mm bottom diameter, made of 3 mm thick tensile sheet along with base plate of size 225 X 225 X 12 mm thick, including 04 Nos. of M24 X 750 long 'J' type foundation bolts, MCB 6 A with 4-way heavy duty connector 32 A, single arm bracket and RCC foundation as per manufacturer's drawing(s) complete as specified and directed by Engineer-in-charge.
S & F 35 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high efficiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size complete as all specified and directed by engineer- in- charge. Make : Bajaj cat No.-BRTFG 36W LED or equivalent model of Phillips and Crompton.
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing complete as all specified and directed by engineer- in- charge. (for street light and bollard light) Make: Havells, HPL, Insu
Supply and laying DWC HDPE pipe SN4 rating with suitable fittings for laying of cables complete of sizes as below:
a) 75 mm int dia
b) 100 mm int dia
c) 150 mm int dia
EXTERNAL WATER SUPPLY
Supply, installation, testing and commissioning of Pump set approx 2 HP capacity with 30 mtrs head and 1.8 LPS discharge with suitable IE2, 3 h, 415V, 50 Hz motor, Pump set model- KDS- 235+kirloskar or equivalent in Crompton/ Jyoti complete with GI medium grade Suction pipe 50 mm dia, synthetic metal ball Foot valve 50 mm and delivery pipe 40 mm dia med grade with 40 mm size NRV and sluice valve on delivery side incl pressure gauge complete upto common header incl foundation as per manufacturers recommendations.
Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed by the engineer-in-charge. Make: Sant, Leader, Venus
Supply, installation, testing and commissioning of factory made, indoor cubical compartmental type PUMP SET PANEL of suitable size, conforming to IS/IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. (for lift & machine room DBs) Make: L & T, Schneider, Siemens, ABB The PUMP SET PANEL PANEL shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection
Supply and lay Copper cable 3 core 2.5 sq mm unarmoured from DOL starter to Motor complete with suitable DWC HDPE pipe saddled on wall and embedded in ground.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised steel wire of diameter 4.0 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 15 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed. (Ext. Water Supply: 02, Ext Electric Supply: 03 )
FIREFIGHTING
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in photoelectric smoke detector, conforming to UL 268 7th Edition, sealed against back pressure, with sensitivity range 0.5 % to 4.0 % per foot obscuration, two-wire SLC connection, fixed-temperature setpoint 135°F (57°C), built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design providing 360° viewing angle, visible bi-colour LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with FlashScan® and CLIP protocol systems, Rotary, decimal addressing, etc. and having the ability to combine temperature thermal sensing with optical sensing, complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete all as specified and directed by the engineer-in-charge.
M & L for low smoke zero halogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Polycab, Havells
a) 2 core, 2.5 mm²
b) 2 core, 1.5 mm²
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as specified and directed by the engineer-in-charge. Make: Newage, AAAG, Minimax
S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge. Make: Safex, Agni, Ceasefire
S & F 9 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge. Make: Safex, Agni, Ceasefire
S & F of 9 litre mechanical foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge. Make: Safex, Agni, Ceasefire
S & F of 9 kg water pressure type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the Engineer-in-charge. Make: Safex, Agni, Ceasefire
S & F of 4 kg clean agent, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, mild steel, rechargeable, UL listed 1-A ,10-B:C, with wall hanger complete all as specified and directed by the Engineer-in-charge.
Supply, installation,testing & commissioning of UL listed tube based Panel Fire Supression System having 4 kg automatic fire cylinder of CO2, linear pneumatic detection tube, CO2 discharge tubing with nozzles for protected panel space, master control unit having LED flasher, electronic hooter, LED indicator, silent switch, etc. with a provision for integration with the FACP along with all necessary accessories complete all as specified and directed by the Engineer-in-charge. Make: Safex, Agni, Ceasefire
S & F Fire buckets (FILLED WITH SAND) round bottom type enamel painted, white inside & Red out side and Letter "FIRE" in black out side and handle with mounting bracket complete as specified and directed by the Engineer-in-charge.
Cutting 150 mm NB MS pipe and reducing to required length before laying in position for insertion of new tees, branches, etc. including bends, tapers, tee pieces (single & double branch) any type and angle/radius and straight connecting pieces but all ends flanged.
EOT CRANE
Material and labour for earthing complete with galvanised steel plate electrodes of size 600x600x6mm thick buried directly in ground with earth pit not less than 2.25 meter deep below normal ground level with top edge of plate not less than 1.5 meter below normal ground level connected to galvanised 32x 6 mm earth lead by means of nuts bolts check nuts GI washers earth wire protected by galvanised iron pipe 40 mm bore (Medium grade) all as directed including concrete pit in PCC (1:3:6) type CI, precast RCC cover slab of size 30x30x10 cm with one handle for lifting made out of 8 mm diameter MS bar,including funnel, wire mesh and 20 mm bore galvanised iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all as specified and directed. EOT Crane: 04, Lightning Protection: 06, DG Set: 06, External electrification: 12 Internal electrification: 08)
SPLIT AC
Supply and install high wall inverter type split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and EER 3.2.of capacity 2 TR. Carrier, Voltas, Daikin, Hitachi
DG SET
Supply installation, testing & commissioning of factory assembled Diesel Engine driven generating set coupled with alternator AC to give continuous output of 125 KVA at a power factor of 0.8 lagging, 415 volts, AC, 3 phase, 4 wire, 50 HZ, 1500 RPM, diesel engine liquid cooled, mounted on common base frame complete with in built fuel tank of adequate capacity with fuel line & accessories, PCC foundation work as per manufacturer's instructions, vibration damper pads, micro processor based relay panel for automatic starting on mains failure, control panel showing all parameters of engine & alternator, sound proof canopy & other accessories etc. and confirming to the under mentioned technical specifications as per specified & directed. Make: Kirloskar, Greaves Cotton , Cummins, Mahindra (A) DIESEL ENGINE : Water cooled, turbo charged,1500 RPM under NTP conditions conforming to IS -4722, BS-5000, IEC-34/1, ISO 8528, BS-5514, ISO-3046 with an overload capacity of 10% for 01 hr in total 12 Hrs of continuous operation complete with the following accessories. (a) Radiator with blower fan with guard (b) Pipe coupling for cooling system (c) Corrosion inhibitor coolant (d) Filters for fuel/lube oil (e) Fly wheel housing and fly wheel suitable for alternator (f) Engine bearing mechanism in fly wheel housing (g) Shut off coil protection with safety for LLOP /HWT/ Over speed/high and low DC voltage. (h) Dry type heavy duty replaceable paper element air cleaner with restriction indicator and vacuum indicators . (J) Residential silencers. (k) Stainless steel exhaust flexible bellows.
(l) Motor driven priming pump. (m) Electric starter motor (n) Battery charging alternator. (o) Exhaust piping made out of STIC "C" class MS Pipe inclusive of all accessories and hardware, necessary support as per manufacturer’s recommendations to sustain back pressure with rain cap and suitable stack height and noise reduction as per latest CPCB norms (p) Mineral wool insulation 2 inch thick suitable for 400 degree Celsius temperature cladded with aluminium sheets for the entire length of exhaust pipe as per manufacturer's recommendations. (q) First fill of oil, coolant and diesel during commissioning and testing for 12 hrs (r) Interconnecting copper cabling of adequate capacity between batteries and controller. (s) Fuel pipe. C class STIC 1"/1.5"/2" dia - 01 lot (t) Self starter 12/24 volts DC, Electric operated with suitable electronic governor (u) Metering equipments for recording (i) Battery voltage and charging rate (ii) Coolant temperature (iii) Lubricating oil pressure (iv) Engine speed (RPM) (v) Engine hours run (vi) Balance of fuel. (v) Safety as protection control (Trip and indication) (i) High water temperature (ii) Low Lube oil pressure (iii) Low and high speed trip (iv) High and low DC voltage (v) over speed Stop
(w) Base frame : Sturdy fabricated welded construction, channel iron base frame (duly painted ) for mounting engine and alternator as per manufacturer’s design alongwith AVM pads (x) Battery: 02 Nos , 12 Volt, 150 Ah maintenance free with leads and terminals (y) Fuel Tank : 12 hrs full load diesel storage capacity full tanks with mounting brackets factory made of 5mm thick HR. MS sheet with level indicator fuel inlet, fuel out let, air vent, drain plug, in let arrangement for diesel filling from exterior of canopy (without opening its panel ) etc. complete all as specified and directed (B) ALTRERNATOR : 125 KVA at 0.8 PF lagging, 415 volts, 3 Phase, 4 wire, 50 Hz at 1500 RPM self excited and self regulated with AVR brushless excitation band of voltage ± 1% of rated voltage from no load to full load insulation class H, self ventilated and conforming to IS4722, BS5000, IEC 60034/1, IS0 8528, BS5514, I503046, suitable for above mentioned diesel engine. (C) ACOUSTIC ENCLOSURE : M & L for acoustic enclosure for the above 125 KVA DG set to reduce noise level to 75 dB measured at 1.0 distance at 75% load for audible frequencies as per latest guidelines of Central pollution Control Board(CPCB-II) and manufacturer's specification with inside illumination : 1 no - 1 x 18 wat FTL fitting of make Philip/Bajaj/ Crompton (D) Suitable control panel as per manufacturers design (E) Automatic Main Failure (AMF) control panel:- Indoor type, factory fabricated cubical type, free standing, floor mounted, AMF control panel, provided with removable rear door & hinged front door for easy accessibility, fabricated out of not less than 2.0 mm thick CRCA Sheet powder coated CPRI approved comprising of following :-
Notes:- (i)The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipment like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department. (ii) The rate quoted for the item shall be inclusive of insulating mat of size 2x1 mtr class A, 2.0 mm thick as per IS-15652(2006).
LIFTS
Design supply, installation, testing & commissioning of Goods lift, having 0.5 m/s car speed, single speed motor suitable for 3- Ph, 415 V, 50 Hz electric power supply, conforming to IS-14665, suitable to serve G + 01 upper floors with AC Variable Voltage & Variable Frequency drive (VVVF drive), complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infrared sensor in full height of door & built in announcing system without hand set (03 Nos, one each in car, machine room & near ground floor landing door) complete all as specified and directed. Make: Otis, Schindler, Mitsubishi, Thyssenkrupp, Toshiba Johnson The lift shall conform to the following technical specifications. [i] Type of Lift: goods lift [ii] Load Capacity: 2000 kg [iii] Speed: 0.5 m/s with single speed motor [iv] Power Supply: 3-Ph, 4 Wire, 415 V, 50 Hz AC [v] Type of Drive: AC Variable Voltage & Variable Frequency [vi] Type of Machine: Gearless [vii] Car Size: Not less than 1.7 m X 2.5 m, i.e. 4.25 m2 [viii] Car & Landing Door at all floors: COPD with VVVF door drive, opening size not less than 1700 mm X 2000 mm, sliding type, fabricated by stainless steel not less than 16 gauge having hairline finish (N-304)
[ix] Car Enclosure: Manufactured with stainless steel frame not less than 16 gauge with hairline finish (N-304) having stainless steel false ceiling with hairline finish, internal lighting arrangement with LED light fittings operated on commercial supply and one LED light fitting operated on battery with invertor as emergency light, complete internal ventilation system provided with concealed axial / cross flow fan with auto cut-off system and stainless steel grill / wire-mesh for protection [x] Provision of standard thickness 40 mm diameter stainless steel hand-rail all around inside the car cabin [xi] Terminal Buffers: Metal special spring / PU / Oil buffers as per manufacturer's recommendation. The buffing stroke shall not be less than 200 mm. [xii] Door Opening (inside): Protected by COPD stainless steel door having hairline finish with opening not less than 1700 mm X 2000 mm [xiii] Car & Counter Weight Guide: As per OEM recommendations [xiv] Flooring: As per OEM recommendations [xv] Signals: (a) Combined luminous hall buttons with LED / LCD / TFT hall position indicators at all floors (b) LED / LCD / TFT car position indicator panel of stainless steel (c) Car operating panel of stainless steel with luminous buttons in car (d) Car direction indicator in car & landing (e) Battery operated alarm bell & emergency light (rechargeable) along with suitable maintenance free battery. (The system shall be separate from ARD batteries.) (f) Overload warning feature in car cabin (display / announcing type both) (g) One fireman's switch to be installed at ground floor near landing door.
(h) All signal fixtures & car operating panel on hairline stainless steel face plate with hairline finish (i) Infrared door sensor safety edge of door for entire height (j) Built in announcing system without handset 2 Nos., one for lift car & ground floor landing door and one announcing system with handset in machine room (k) The interior of the car shall be provided with a device that audibly announce the floor position of lift car has reached and announce that car entrance / exit door is open or closed [xvi] Stops & Opening: 2-2 with all openings being on the same side [xvii] Safety Device: (a) Automatic Rescue Device (ARD) / automatic landing device operating with maintenance-free batteries having suitable capacity. The batteries must have auto charging facilities. The charger input be connected with converter of regenerative drive. (b) The ARD actuation time shall be less than one second after failure of power supply and when ARD is operative the car shall stop at the nearest floor and then doors shall open. [xviii] Machine Room: Located above the hoist way, details as per building drawings [xix] Hoist way: Construction details as per building drawings [xx] Civil Work: Necessary civil work viz. making good disturbed surfaces, modification to landing space to suit car size, necessary foundation to machine(s), etc. [xxi] One number of wall mounted type telephone instrument installed inside of car cabin along with fixing arrangement and telephone cable of suitable size from car cabin to machine room run along with travelling cable. The telephone instrument shall be connected in the telephone DB installed in the machine room.
M & L for Earthing complete with copper plate 60 cm × 60 cm × 3.15mm thick electrode, buried directly in ground vertically (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5m below ground level, connected to 20×3.15 mm copper strip as earthing lead by means bolts and nuts check nuts and washers of galvanized iron and connected to main switch board including 20 mm bore medium grade GI Pipe with , MS funnel with wire mesh watering arrangement and 50 mm bore light grade GI pipe for earth lead protection from earth plate to test point or panel connecting point , PCC chamber ,CI cover with frame etc including necessary excavation in any type of strata, returning, filling , removal of soil outside MD land ,filling of charcoal and salt complete all as shown in electrical plate No. 3 of MES Sch Part - I, connected to Earthing test point all as specified and directed and testing on completion.
COMPREHENSIVE MAINTENANCE OF LIFTS
Comprehensive maintenance and repairs of fully automatic electrically operated Goods lift ( BOQ Item : 25.001) of any Make and installed capacity with a carrying capacity of 2000 Kg to serve (G+01 Floors) with AC variable voltage & variable frequency (VVVF drive) drive complete with all standard accessories, simplex collective automatic & manual dual controlled operation with/without attendant, automatic center opening doors with VVVF door drive (electric motor driven mechanism), sliding stainless steel doors, automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set (04 Nos, one each in car, Machine room & near Ground floor landing door) comprising of all devices and accessories through 36 months for all days including holidays etc after expiry of defects liability period as shown below and all as specified and directed to Engr-in-Charge for 02 Nos of lift Note : Contractor shall carryout comprehensive maintenance (routine, daily, weekly, monthly, quarterly, half yearly, yearly) through OEM as per MOU and maintain all the lifts in serviceable condition 24 hrs x 365 days with out any extra cost.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(a) 3rd year after expiry of defects liability period
DAS Offshore Engg. Pvt. Ltd.
Mukund Enterprises Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid