Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.9 LAccepted-AOC NAMBLABAL PAMPORE DISTRICT PULWAMA JAMMU KASHMIR 192121 | PAMPORE | PULWAMA | JAMMU KASHMIR | 192121 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹42.6 L+₹2.6 L (6.63%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹43.2 L+₹3.2 L (8.09%)Rejected-Finance RAWALPORA WANABAL PATI YAYIL POST OFFICE SANAT NAGAR SRINAGAR 190005 J K | SRINAGAR | JAMMU AND KASHMIR | 190005 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹43.6 L+₹3.6 L (9.14%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹46.7 L+₹6.7 L (16.8%)Rejected-Finance 201 GANAPATI SANKUL AGASHIVNAGAR MALKAPUR KARAD SATARA MAHARASHTRA 415539 | SATARA | MAHARASHTRA | 415539 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹46.8 L
EMD Value
₹93,500
Closing Date
31 Oct 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE, HQ 134 Works Engineers
HQ 134 Works Engineers PIN - 914134 C/o 56 APO
PROVN OF 125 KVA DG SET FOR SERVER ROOM AND BLDG NO. P-246 AT JAK LI RC UNDER GE 970 EWS
2024_MES_677859_1
134WE-48(T)/2024-25
Open Tender
Civil Works - Others
Item Rate
180 days
GE 970 EWS
As per tender documents
9 documents required · 9 mandatory
₹500
GE 970 EWS
₹93,500
Yes
30 Nov 2024
3 Oct 2024
2 Nov 2024
3 Oct 2024
31 Oct 2024
18 Oct 2024
4 Oct 2024 - 10 Oct 2024
Amount
Supply, installing, testing and commissioning of diesel engine driven generating set, 415 Volts, 3 Phase, 4 wire as per BS-5514/ IS-10002 complete including automatic on main failure (AMF) panel complete with relay for automatic operation on failure of capacity 125 KVA 100 KW at after considering derating factor confirming to IS-1601 at an altitude of 5500 feet (approx) above MSL and capable of operating between temperature range (-)20 degree centigrade to (+)40 degree centigrade (at Srinagasr, J&K) conditions with acoustic enclosure as per latest CPCB-IV norms and including anti vibration pads of required size as recommended by the manufacturer & comprising of the followings :-
(A) ENGINE :- Inline engine 4 cylinder, heavy duty, turbocharged and water cooled diesel engine, water cooled with standard integral set, mounted radiator system, suitable for operation at 50 degree celsius ambient temperature, G2 class mechanical governing mechanism all as per BS-5514, IS-3046, 1500 RPM complete with all safety accessories and suitable for generating set application and capable to produce and output of 125 KVA 100 KW at 5500 feet (Approx) altitude above MSL and capable of operating between temperature range (-)20 degree centigrade to (+)40 degree centigrade (at Srinagar, J&K) conditions and sump pre heaters, cold start kit etc., complete all as specified and directed with the followings :- (i) Starting System - 12 volts DC electric starter with required 12 Volt 150 AH batteries and charging alternator, engine wiring harness and sensors as required. (ii) Fuel System - Combined unit injectors, mechanical governor & as per IS-1460 replaceable fuel filter elements with primary filter and fuel piping complete with integral fuel tank of minimum capacity suitable for 8 hours running of DG set at full load, providing with drain plug, air vent, inlet & outlet connection, level indicator and provision for cleaning.
(iii) Lube Oil System - Lube oil circulation pump with safety valve, lube oil filter, lube oil cooler, oil filler neck and oil dipstick for measurement, open crankcase venting system etc. (iv) Combusion Air System - Exhaust turbocharger, charge air cooler mounted on engine, exhaust flexible bellows, residential type exhaust silencers and extended silencer pipe of same size upto 1.0 mtr duly insulated and aluminium cladded as directed. (v) Cooling System - Gear driven coolant pump required for both jacket and intercooler along with necessary pipings on the engine. Water pump should have suitable capacity to circulate cooling water to radiator mounted on the DG acoustic enclosure. (vi) Engine Mounting - Engine mounting bracket with AVM pads mounted below base frame housing engine and alternator. (vii) Alignment and Fuel tank - Alternator and engine alinged on a common 14 SWG CRCA MS base frame complete with MS fuel tank, fabricated out of 14 SWG CRCA MS sheet and is part of base frame.
(B) ALTERNATOR :- Self regulated self exited brushless alternator, 415 V, 3 Phase, 4 wire, 50 Hz, 125 KVA 100 KW at 0.8 PF, 1500 RPM with voltage variation plus or minus 10% of rated voltage from no-load to full load, foot mounted, screen protected drip proof type with class `H' insulation with IP-23 ingress protection, ball/ roller bearings at both ends of the alternator shaft with necessary controls as recommended by the manufacturers with the followings :- (i) Engine Control Panel - Electronic controller for indicating engine parameters, emergency stop push button, genset monitoring and display of engine alternator parameters and alarms, genset protection against critical operating parameters, automatic start sequence control, acquisition and display of plant related measuring data. Features : Auto and Manual Start / Stop, Easy accessible. Display Engine Parameters - RPM, oil pressure coolant, temperature, hour meter, battery volts, battery charging voltage, running status, event recording, fault code display. Electrical Parameters - Voltage, Current, Hz, KW, KVA, PF, KWH and KVAR, Breaker status. Engine Protection - High/ low coolent temperature, low lube oil pressure, engine over speed shutdown. Electrical Protection - Overcurrent, short circuit, under/over frequency, under/over voltage.
(ii) AMF Panel - Floor mounted, vertical, totally enclosed cubical with canopy, indoor type dust and vermin proof, standard industrial pattern, factory fabricated out of 2mm thick CRCA steel sheet painted with one coat of red oxide primer and two coats of powder coating of approved colour complete with all mounting stuctures, insulators, bolts, nuts, washers etc. with necessary control wiring/ internal connections with proper size of copper conductor cables/ strips, suitable for 3 phase, 4 wire, 50 Hz, 415 Volts AC system, comprising of micrprocessor based AMF relay unit with sensing on mains and DG with necessary protection, suitable rating HRC Fuses, suitable 4 pole power contactor of suitable amps for mains and DG supply auto load charger, frequency meter, push button for start/ stop/ reset, LED type indicating lamps as required, SMPS based battery charger with automatic float & boost changeover facility, control circuit fuses, reverse power relay, alarm for high water lube oil temp and low lub oil pressure, any control devices/ measuring instruments recommended required as per latest engineering practices complete with cable glands with gland plate for cable entry, control cabling with copper conductor armoured multi-core cables of required cross sectional area from DG set to control panel all prewired and suitable for 125 KVA/ 100 KW DG Set, complete all as specified and directed.
(iii) Acoustic Enclosure - The engine and alternator will be coupled aligned and mounted on a specially designed common base frame fabricated from 16 SWG CRCA MS sheets / channels of suitable cross sectional area and length with bottom, drilled holes suitable for and including supplying and fixing anti vibration pads. Outdoor acoustic enclosure to be provided as per CPCB-IV norms. Acoustic base frame shall be fabricated using sheet/ ISMC channels with adequate stiffeners for strength. Should be fabricated with specially formed CRCA sheet with adequate stiffeners for strength. Door construction should be prefabricated CRCA sheet with double stepped formation. Doors to be fixed to main frame by hinges. Suitable sealing given at all the panel joints to avoid the sound & water leakage. The acoustic enclosure panels shall be powder coated using minimum of 9 tank process which should include intermediate rinsing modes between each step. (iv) First fill of premix corrosion inhibitor coolant. (v) First fill of lube oil should be supplied alongwith DG set. (vi) First set of fuel filter, air filter, lube oil filters etc. and consumables should be part of DG Set supply. (vii) Any other devices/ accessories required as per latest engineering practices as recommended/ supplied by the manufacturers as standard equipment.
(viii) Documents - Two sets of following documents :- (aa) Maintenance and Operation manuals for engine and alternator, Spare parts catalogue, Warranty/ Test certificates, Wiring Schematic diagrams of control panels. (ix) DG Sets shall be tested for duration of 12 & half Hrs at site using load bank. Cost of load bank, diesel control cables the length between DG AMF panel and DG set can be taken as max fo 30 mtrs and all auxillaries required for testing at site shall deemed to be include in the quoted rates. (x) Maintenance Spares :- (aa) Fuel filter element - 02 Nos (ab) Oil filter element - 03 Nos (ac) Element air cleaner outer - 06 Nos (ad) Element air cleaner inner - 06 Nos (ae) `V' belt - 02 Nos (af) Filter lubricant oil by pass - 02 Nos. Notes :- (a) The technical details and drawings of DG Set with all control panels should be taken approvals from Accepting Officer before the procurements/ manufacturing from OEM
Supply, laying, commissioning & testing XLPE LT cable, 1100 volts grade, PVC insulated, heavy duty, armoured, multistranded aluminium conductor cable of size 95 Sqmm 3.5 Core, laid in trenches, fixing on wall/ poles, under road crossing etc, complete all as specified and directed. Note :- Earth work, sand cushioning and brick covering shall be measured and paid separately under respective items of this BOQ.
M&L for earthing complete with GI steel earth plate electrode of size 600mm x 600mm x 6mm thick, burried directly in ground, earth pit not less than 2.25 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to the galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised steel, connected to earthing test point with and including necessary excavation and earthwork and earth electrode, earthing lead from electrode to equipments, adequated quantity of charcoal dust and common salt, test point, PCC 1:3:6 type C-1 (using 20mm graded stone aggregate), 40mm thick RCC (type B-1) cover reinforced with 8mm dia TMT bar both ways with 12mm dia round bar handle and 20mm bore GI light grade watering pipe with funnel and wiremesh and 40mm bore GI pipe light grade for protection of earth lead upto equipments max length 7.5 mtr, complete all as shown on electrical plate No. 5 of MES SSR Part-I (2009) and directed by Engr-in-Charge. Note :- On testing after completion if the desired resistenance is not obtained, the contrator shall redo the earthing without any extra cost to the department.
Excavation in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of cables, erection of poles, stays etc. and getting out in soft/ loose soil, complete all as specified and directed.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25cm thick, complete all as specified and directed.
Removing excavated soil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
M&L for dry river sand, laid in trenches for cable protection, as 15cm thick below the cable and 8cm thick above the cable, complete all as specified and directed. Note :- Punned thickness of sand shall be measured and paid.
M&L for sub class 'B' brick, old size, as in coverings, protection to the eletric cable, laid dry, flat, transversally along the length of cable on sand cushioning with width equal to length of brick, complete all as specified and directed.
Supplying and Laying reinforced precast concrete cable cover, class HV, type-2, flat, of size 250x150x40mm, complete all as specified and directed.
M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded crushed stone aggregates) as foundation, filling in, mass concrete etc. including necessary formwork, complete all as specified and directed.
M&L for plain cement concrete 1:2:4 type B-2 (using 40mm graded crushed stone aggregates) as foundation, filling in, mass concrete etc. including necessary formwork, complete all as specified and directed.
M&L for 15mm thick rendering in cement mortar 1:6 on fair faces of brick wall or concrete surfaces, finished the surface even and smooth without using extra cement, complete all as specified and directed.
M&L for replacement GI tubing light grade 50mm bore with all fittings, laid in trenches/ under road or floor and fixed to walls/ alongwith pole with suitable MS clamps, complete for protection of electric cable, complete all as specified and directed.
Supply, installation, commissioning and testing LT panel , outdoor type, floor mounted, weather vermin proof factory made, CPRI approved, fabricated out of 3mm thick mild steel sheet mounted, on frame of mild steel angle iron 40mm x 40mm x 6mm, 45cm above the ground level duly supported with mild steel angle iron 50mm x 50mm x 6mm thick in PCC foundation (1:2:4) type B-1, using 20mm graded crushed stone aggregate, LT panel shall be totally enclosed with front double door and rear opening with IP-54 protection as per IS/8623 duly powder coated for 433 Volts, 3 Phase, 4 wire having TPN Aluminium bus bars suitable for 400 Amps load duly drilled holes for connecting, RYB insulated with different colour code and sleeved insulators complete prewired and cable protection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connection with suitable size of copper lugs and cable glands, complete all as specified and directed and also comprising of following :-
INCOMING :- (a) MCCB 250 Amp 04 pole - 36 KA 01 Nos, ICS = 100% = ICU. OUTGOING :- (b) MCCB 100 Amp 04 pole - 25 KA 02 Nos, ICS = 100% ICU. (c) MCCB 63 Amp 04 pole - 25 KA 02 Nos, ICS=100%=ICU. (d) Copper bus bar suitable of capacity 480 A - set of 4. (e) Digital Voltmeter - 01 No (f) Digital Ammeter - 01 No. (g) R-Y-B Neon indicator lamp panel mounting type (set of 03) = 01 Set. (h) CT as per suitable capacity (set of 3) (j) Control wiring of suitable 4/6 Sqmm copper wire for connecting above accessories - each job. (k) PCC work for panel foundation - each job.
M&L for covered shed with PGI sheets (pre-painted galvalume iron sheet) as in roof top on 02 Nos MS angle iron (size of angle 65x65x6mm) trussess of size 4.5 Mtr x 3.5 Mtr over the PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation of size 4.5 Mtr x 3.5 Mtr x 0.60 Mtr, finishing the surface even and smooth and erecting 04 Nos 80mm bore MS tubular pipe of heavy grade having minimum height 4.0 Mtr including well grouted in foundation with and including 06 Nos purlins and 04 Nos angle iron to hold the tubular pipes and PGI sheets fencing of required size over the trussess, purlins and paiting with two coats of sythetic enamel paint over a coat of red oxide primer on steel surfaces after preparation of surfaces, complete all as specified and directed.
M/S NEW ROYAL CONSTRUCTION CO (BID ID -3149101)
FIRDOUS AHMAD BABA (BID ID -3154663)
M/S Inder Pal Singh (BID ID -3149282)
Prakash Trading Corporation (BID ID -3154867)
CHINAR CONSTRUCTION TRADERS (BID ID -3154678)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .