Completion of balance Electro-Mechanical works of Walidad SHP
128950
NIT/04/Elect./2025-26
Open Tender
ELECTRICAL
Gaya
• Name of the Firm/Agency
• Address of the Firm/Agency
• PAN (Permanent Account Number)
• GST registration No.
• Labour License No.
ELECTRICAL
ITEM RATE
L1
1
25 documents required · 25 mandatory
₹10,000
Processing Fee: 590
₹2.8 L
Yes
BSHPCL HQ, Sone Bhawan, Second Floor, Patna
12 May 2026
10 Apr 2026
15 May 2026
11 Apr 2026
12 May 2026
11 Apr 2026
24 Apr 2026
TECHNICAL BID SHEET
NIT No. & date 04/Elect/2025-26 dated 30.03.2026
Name of Work Completion of balance/ complete works of E&M – including Testing & Commissioning
Name of Project Walidad SHP (1 x 700 KW)
Sl. No. Particulars Information to be filled up / document to be uploaded (Lead/ Sole Partner) JV/ C Partner 2 (In case of JV/C) JV/ C Partner 3 (In case of JV/C)
1 Name of the Firm/Agency
2 Address of the Firm/Agency
3 Earnest Money Deposit Amount of Earnest Money (In INR)
Proof of Payment (Details of Online Payment)
MSME Certificate (for exemption of EMD) No.
4 Validity of offers 180 Days 180 Days 180 Days
5 EPF Registration No.
6 PAN (Permanent Account Number)
7 GST registration No.
8 Labour License No.
9 Proof of registration under the Indian Companies Act or under the law of Bihar State or equivalent legal frame work of State/Govt. of India. Registration No & date:
10 If Joint Venture/ Consortium then Share of each Partner
11 Joint Venture/Consortium (if any) Agreement
12 Self declaration about submission of EPF, GST, Labour license & JV registration under company act in prescribed format by each partner of JV/ C (Annexure-1)
13 Work experience (Annexure-2)
14 Present Commitments (Annexure-3)
15 Details of key employees (Annexure-4)
16 Annual Turnover during financial years: 2022-23
Annual Turnover during financial years: 2023-24
Annual Turnover during financial years: 2024-25
Average Annual Turnover
17 Balance sheet and Profit & Loss statement for the 3 years (audited) i.e. for financial years (2022-23, 2023-24 & 2024-25) (Annexure-5)
18 Details of dispute (Annexure-6)
19 GTP (Annexure-7)
20 Proforma for power of attorney in respect of tenderer signature as per Annexure-8
21 Proforma for power of attorney in respect of joint ventures as per Annexure-9
22 Proforma for qualification as per Annexure-10
23 Proforma of Bank Guarantee for Contract Performance (Annexure-11)
24 Have you ever been black listed/ debarred or are under any blacklisting process? (Annexure-12)
25 Bank solvency certificate
26 Any Additional Document / General Document
Note All above Supporting documents shall be attached (In case JV/ C, all partner must be attached their documents individually) and their hard copy must be sent to the office of the Chief Engineer (E), BHPC.
WORK EXPERIENCE – COMPLETED IN RESPECT OF HYDRO PROJECTS
Name of Agency Sl. No. Name of Work Name of Department Agreement No. Agreement Amount (Rs in Lakh) Date of Work Order Stipulated Period of Completion Payment made so far (Rs in Lakh) Actual period of completion Remarks explaining reasons of delay in work completion (if applicable)
Sole/ Lead Partner 1 3 4 5 6 7 8 9 10 11
Partner 2 (In case of JV) 1
Partner 3 (In case of JV) 1
Note Supporting documents such as Certified copies of the LOI/ Work Order/ Purchase Order/ Sale Invoice/ Certificate granted by the previous client(s) be attached.
DETAILS OF PRESENT COMMITMENT (WORK IN HAND)
Name of Agency Sl. No. Name of Work Name of Department and Place Agreement No. Date of Work Order Stipulated period of Completion Payment made so far (Rs in Lakh) Value of work remaining (Rs in Lakh) Anticipated date of completion
Sole/Lead Partner 1 2 3 4 5 6 7 8 9
Partner 2 (In case of JV)
Partner 3 (In case of JV)
Note Supporting documents such as Certified copies of the LOI/ Work Order/ Purchase Order/ Sale Invoice/ Certificate granted by the previous client(s) be attached.
DETAILS OF KEY EMPLOYEES Number and details of employees currently on company strength.
Name of Agency Levels Nos. Qualification Year of experience Years with firm
Min. Max. Min. Max. Min. Max.
Sole/ Lead Partner Managerial
Supervisory level (technical)
Supervisory level (finance/managerial)
Certified welders
Skilled workers
Semiskilled workers
Partner 2 (In case of JV) Managerial
Supervisory level (technical)
Supervisory level (finance/managerial)
Certified welders
Skilled workers
Semiskilled workers
Partner 3 (In case of JV) Managerial
Supervisory level (technical)
Supervisory level (finance/managerial)
Certified welders
Skilled workers
Semiskilled workers
Note Supporting documents such as Certified copies of the LOI/ Work Order/ Purchase Order/ Sale Invoice/ Certificate granted by the previous client(s) be attached.
AVERAGE ANNUAL TURNOVER STATEMENT
Name of Agency Sl.No. Financial Year *Amount ( in Lakh ) Remarks
Sole/Lead Partner 1 2 3 4
Partner 2 (In case of JV) 1 2022-23
Partner 3 (In case of JV) 1 2022-23
* Audited copies certified by CA shall be attached separately in support of the submitted figures online.
BALANCE SHEET STATEMENT
Name of Agency Sl.No. Financial Year *Amount ( in Lakh ) NET WORTH Remarks
Sole/Lead Partner 1 2 3 4
Partner 2 (In case of JV) 1 2022-23
Partner 3 (In case of JV) 1 2022-23
* Audited copies certified by CA shall be attached separately in support of the submitted figures online.
ANNUAL PROFIT/(LOSS) STATEMENT
Name of Agency Sl.No. Financial Year *Profit ( in Lakh ) Remarks
Sole/Lead Partner 1 2 3 4
Partner 2 (In case of JV) 1 2022-23
Partner 3 (In case of JV) 1 2022-23
* Audited copies certified by CA shall be attached separately in support of the submitted figures online. * The profit shall be the "Profit Before Tax" duly audited.
DETAILS OF DISPUTE
Is there any dispute with any other parties ? If yes then plese fill the following. YES / NO
Sl.No. Name of Agency Other parties name and address Causes of Disputes Amount Involved Present Status Remarks
GUARANTEED TECHNICAL PARTICULARS
Sl. No. Items Walidad HEP (1×700 kW)
1 MECHANICAL AUXILIARIES OF POWER HOUSE
(i) Ventilation
(a) Name of Manufacturer (Word equivalent not acceptable)
(b) Fan size (mm)
(c) Rated Speed (RPM)
(d) Rated Voltage
(e) Rated Current
(f) Rated Power Factor
(g) Power of Motor
(h) Volume of Air delivery at rated voltage (m3/hr)
(i) Volume of Air delivery at test voltage (m3/hr)
(j) No. of Blades
(k) Class of Insulation
(l) Type of bearing
(j) Instructions for lubrication of bearings
(ii) Air Conditioning
(a) No. of A/C units to be installed
(b) Type of A/C units
(c) Capacity of each unit
(d) Temperature to be maintained
(e) Humidity to be maintained
(f) Power requirement for each A/C unit
(iii) Fire Extinguishers
CO2 Type Wheel & Hand Portable Types
(a) Name of Manufacturer (Word equivalent not acceptable)
(b) Standard to which it conforms
(d) Pressure of CO2 when charged
(e) Weight of CO2
(f) Weight of Cylinders when full and empty
(g) Effective range max./min
(h) Discharge time
(i) Test pressure
Foam Type (Hand Operated)
(a) a. Name of manufacturer (Word equivalent not acceptable)
(b) Standard to which it conforms
(c) Base chemical and name of gas under pressure
(d) Body material
(e) Capacity in kg.
(f) Weight of cylinder when full and empty
(g) Base diameter
(h) Overall height
(i) Effective range
(j) Duration of discharge time
(k) Test pressure.
2 ELECTRICAL AUXILIARIES
(i) Power And Control Cables
A LT Power Cable
i. Name and address of the manufacturer
ii. Name and address of contractor's representativefrom whom technical as well as commercial clarifications can be obtained.
iii. Location of factory
iv. Validity of tender
i. Type and size of Cables
ii. Standard applicable
iii. Voltage rating
iv. Permissible variation in voltage, frequency and combined voltage and frequency.
v. Suitable for earthed/ unearthed system
i. Material copper/ aluminium/ grade
ii. Nominal cross-sectional area.
iii. Form of conductor-circular/ shaped
iv. No. of strands
v. Nominal dia. of each strand
d Conductor Screen
ii. Minimum thickness
iii. Whether extruded
i. Material (Mention type)
ii. Minimum average thickness
iii. Tolerance on the smallest of the measured values of thickness of insulation.
iv. Dia of core over insulation.
v. Specific insulation resistance at 27oC
vi. Colour scheme of identification of cores.
vii. Average dielectric strength
viii. Suitability with regard to moisture zone, acid, oil and alkaline cup-roundings.
f Insulation Screen
i. Whether extruded semi-conducting screen is supplied
ii. Material of the semi-conducting screen
iii. Thickness of the semi-conducting screen
iv. Whether copper tape screening is applied
v. Thickness of the copper tape.
vi. For braided screen, material and dia. of screen wire and minimum percentage coverage.
i. Material (mention type)
ii. Whether extruded
iii. Minimum thickness of inner sheath
iv. Calculated diameter over stranded cores of the cables.
v. Whether the inner sheath and the filling material are suitable for the operating temperature of the cable.
i. Type and material
ii. Nominal dimensions of steel strip or nominal dia. of round armour wire.
i Outer Sheath/ Overall Covering
i. Material (mention type, if any)
ii. Whether extruded
iii. Minimum average thickness
iv. Tolerance on the smallest of the measured values of thickness of outer sheath.
v. Calculated dia. under the sheath.
vi. Whether anti-termite treatment has been given in the outer sheath.
j Electrical Properties
i. Conductor resistance at 20oC per km.
ii. Maximum permissible conductor temp.
(a) Under continuous full load
(b) Under transient conditions
iii. Loss tangent at normal frequency
iv. Reactance at 50 C/s per km.
v. Capacitance at 50 C/s per km.
vi. Current rating.
(a) In air (continuous)
(b) In duct (continuous)
(c) Reference ambient temperature for the above
(d) Short circuit current rating for 1 sec. duration
vii. Derating factors.
(a) For ambient temperature of 50oC
(b) For grouping of 4 to 6 cables in racks and trays and in 4 to 6 tiers for different spacings and also touching each other.
k Mechanical Data (For each of the cable sizes of different voltage grade)
i. Overall dia. of the cable
ii. Dia. of the cable under the sheath
iii. Diameter under armouring
iv. Diameter over the stranded cores
v. Weight of cable per kg.
vi. Drum length
vii. Tolerance on drum length
viii. Total weight of the drum
ix. Dimensions of the drum
x. Recommended minimum installation radius Maximum safe pulling force.
B HT Power Cable
i. Name and address of the manufacturer
ii. Name and address of contractor's representativefrom whom technical as well as commercial clarifications can be obtained.
iii. Location of factory
iv. Validity of tender
i. Type and size of Cables
ii. Standard applicable
iii. Voltage rating
iv. Permissible variation in voltage, frequency and combined voltage and frequency.
v. Suitable for earthed/ unearthed system
i. Material copper/ aluminium/ grade
ii. Nominal cross-sectional area.
iii. Form of conductor-circular/ shaped
iv. No. of strands
v. Nominal dia. of each strand
d Conductor Screen
ii. Minimum thickness
iii. Whether extruded
i. Material (Mention type)
ii. Minimum average thickness
iii. Tolerance on the smallest of the measured values of thickness of insulation.
iv. Dia of core over insulation.
v. Specific insulation resistance at 27oC
vi. Colour scheme of identification of cores.
vii. Average dielectric strength
viii. Suitability with regard to moisture zone, acid, oil and alkaline cup-roundings.
f Insulation Screen
i. Whether extruded semi-conducting screen is supplied
ii. Material of the semi-conducting screen
iii. Thickness of the semi-conducting screen
iv. Whether copper tape screening is applied
v. Thickness of the copper tape.
vi. For braided screen, material and dia. of screen wire and minimum percentage coverage.
i. Material (mention type)
ii. Whether extruded
iii. Minimum thickness of inner sheath
iv. Calculated diameter over stranded cores of the cables.
v. Whether the inner sheath and the filling material are suitable for the operating temperature of the cable.
i. Type and material
ii. Nominal dimensions of steel strip or nominal dia. of round armour wire.
i Outer Sheath/ Overall Covering
i. Material (mention type, if any)
ii. Whether extruded
iii. Minimum average thickness
iv. Tolerance on the smallest of the measured values of thickness of outer sheath.
v. Calculated dia. under the sheath.
vi. Whether anti-termite treatment has been given in the outer sheath.
j Electrical Properties
i. Conductor resistance at 20oC per km.
ii. Maximum permissible conductor temp.
(a) Under continuous full load
(b) Under transient conditions
iii. Loss tangent at normal frequency
iv. Reactance at 50 C/s per km.
v. Capacitance at 50 C/s per km.
vi. Current rating.
(a) In air (continuous)
(b) In duct (continuous)
(c) Reference ambient temperature for the above
(d) Short circuit current rating for 1 sec. duration
vii. Derating factors.
(a) For ambient temperature of 50oC
(b) For grouping of 4 to 6 cables in racks and trays and in 4 to 6 tiers for different spacings and also touching each other.
k Mechanical Data (For each of the cable sizes of different voltage grade)
i. Overall dia. of the cable
ii. Dia. of the cable under the sheath
iii. Diameter under armouring
iv. Diameter over the stranded cores
v. Weight of cable per kg.
vi. Drum length
vii. Tolerance on drum length
viii. Total weight of the drum
ix. Dimensions of the drum
x. Recommended minimum installation radius Maximum safe pulling force.
C. LT Control Cable
i. Name and address of the manufacturer
ii. Name and address of contractor's representativefrom whom technical as well as commercial clarifications can be obtained.
iii. Location of factory
iv. Validity of tender
i. Type and size of Cables
ii. Standard applicable
iii. Voltage rating
iv. Permissible variation in voltage, frequency and combined voltage and frequency.
v. Suitable for earthed/ unearthed system
i. Material copper/ aluminium/ grade
ii. Nominal cross-sectional area.
iii. Form of conductor-circular/ shaped
iv. No. of strands
v. Nominal dia. of each strand
d Conductor Screen
ii. Minimum thickness
iii. Whether extruded
i. Material (Mention type)
ii. Minimum average thickness
iii. Tolerance on the smallest of the measured values of thickness of insulation.
iv. Dia of core over insulation.
v. Specific insulation resistance at 27oC
vi. Colour scheme of identification of cores.
vii. Average dielectric strength
viii. Suitability with regard to moisture zone, acid, oil and alkaline cup-roundings.
f Insulation Screen
i. Whether extruded semi-conducting screen is supplied
ii. Material of the semi-conducting screen
iii. Thickness of the semi-conducting screen
iv. Whether copper tape screening is applied
v. Thickness of the copper tape.
vi. For braided screen, material and dia. of screen wire and minimum percentage coverage.
i. Material (mention type)
ii. Whether extruded
iii. Minimum thickness of inner sheath
iv. Calculated diameter over stranded cores of the cables.
v. Whether the inner sheath and the filling material are suitable for the operating temperature of the cable.
i. Type and material
ii. Nominal dimensions of steel strip or nominal dia. of round armour wire.
i Outer Sheath/ Overall Covering
i. Material (mention type, if any)
ii. Whether extruded
iii. Minimum average thickness
iv. Tolerance on the smallest of the measured values of thickness of outer sheath.
v. Calculated dia. under the sheath.
vi. Whether anti-termite treatment has been given in the outer sheath.
j Electrical Properties
i. Conductor resistance at 20oC per km.
ii. Maximum permissible conductor temp.
(a) Under continuous full load
(b) Under transient conditions
iii. Loss tangent at normal frequency
iv. Reactance at 50 C/s per km.
v. Capacitance at 50 C/s per km.
vi. Current rating.
(a) In air (continuous)
(b) In duct (continuous)
(c) Reference ambient temperature for the above
(d) Short circuit current rating for 1 sec. duration
vii. Derating factors.
(a) For ambient temperature of 50oC
(b) For grouping of 4 to 6 cables in racks and trays and in 4 to 6 tiers for different spacings and also touching each other.
k Mechanical Data (For each of the cable sizes of different voltage grade)
i. Overall dia. of the cable
ii. Dia. of the cable under the sheath
iii. Diameter under armouring
iv. Diameter over the stranded cores
v. Weight of cable per kg.
vi. Drum length
vii. Tolerance on drum length
viii. Total weight of the drum
ix. Dimensions of the drum
x. Recommended minimum installation radius Maximum safe pulling force.
D HT Control Cable
i. Name and address of the manufacturer
ii. Name and address of contractor's representativefrom whom technical as well as commercial clarifications can be obtained.
iii. Location of factory
iv. Validity of tender
i. Type and size of Cables
ii. Standard applicable
iii. Voltage rating
iv. Permissible variation in voltage, frequency and combined voltage and frequency.
v. Suitable for earthed/ unearthed system
i. Material copper/ aluminium/ grade
ii. Nominal cross-sectional area.
iii. Form of conductor-circular/ shaped
iv. No. of strands
v. Nominal dia. of each strand
d Conductor Screen
ii. Minimum thickness
iii. Whether extruded
i. Material (Mention type)
ii. Minimum average thickness
iii. Tolerance on the smallest of the measured values of thickness of insulation.
iv. Dia of core over insulation.
v. Specific insulation resistance at 27oC
vi. Colour scheme of identification of cores.
vii. Average dielectric strength
viii. Suitability with regard to moisture zone, acid, oil and alkaline cup-roundings.
f Insulation Screen
i. Whether extruded semi-conducting screen is supplied
ii. Material of the semi-conducting screen
iii. Thickness of the semi-conducting screen
iv. Whether copper tape screening is applied
v. Thickness of the copper tape.
vi. For braided screen, material and dia. of screen wire and minimum percentage coverage.
i. Material (mention type)
ii. Whether extruded
iii. Minimum thickness of inner sheath
iv. Calculated diameter over stranded cores of the cables.
v. Whether the inner sheath and the filling material are suitable for the operating temperature of the cable.
i. Type and material
ii. Nominal dimensions of steel strip or nominal dia. of round armour wire.
i Outer Sheath/ Overall Covering
i. Material (mention type, if any)
ii. Whether extruded
iii. Minimum average thickness
iv. Tolerance on the smallest of the measured values of thickness of outer sheath.
v. Calculated dia. under the sheath.
vi. Whether anti-termite treatment has been given in the outer sheath.
j Electrical Properties
i. Conductor resistance at 20oC per km.
ii. Maximum permissible conductor temp.
(a) Under continuous full load
(b) Under transient conditions
iii. Loss tangent at normal frequency
iv. Reactance at 50 C/s per km.
v. Capacitance at 50 C/s per km.
vi. Current rating.
(a) In air (continuous)
(b) In duct (continuous)
(c) Reference ambient temperature for the above
(d) Short circuit current rating for 1 sec. duration
vii. Derating factors.
(a) For ambient temperature of 50oC
(b) For grouping of 4 to 6 cables in racks and trays and in 4 to 6 tiers for different spacings and also touching each other.
k Mechanical Data (For each of the cable sizes of different voltage grade)
i. Overall dia. of the cable
ii. Dia. of the cable under the sheath
iii. Diameter under armouring
iv. Diameter over the stranded cores
v. Weight of cable per kg.
vi. Drum length
vii. Tolerance on drum length
viii. Total weight of the drum
ix. Dimensions of the drum
x. Recommended minimum installation radius Maximum safe pulling force.
3 0.415 kV Switchgear
v. One minute power frequency withstand voltage
vi. Rated continuous current : at 400C A
vii. Rated service current : at 600C A
viii. No. of poles
ix. Breaking capacity kA rms
x. Making capacity kA rms
xi. Short Time with stand capacity 1 second kA rms
xii. Rated breaking capacity
xiii. Symmetrical
xiv. Asymmetrical
xv. Operating mechanism
xvi. Operating Duty
xvii. Test Certificate Report reference
xviii. Type of main contact
xix. Material of contact surfaces
xx. Weight of circuit breaker complete with all fittings as in service. Kg
xxi Overcurrent and earth fault protection
xxii Other protections
(b) Name of manufacturer
(c) Rated transformation ratio
(d) Output at rated current and accuracy
(e) Accuracy class
(f) Rated over current factor
(i) Times rated current
(ii) Time in seconds
(g) Knee point voltage
(h) Basic insulation level
(i) Winding temperature rise
(j) Secondary winding resistance
4 Control, Protection And Metering
A CONTROL SYSTEM
i. Control components and their parameters & makes
ii. No. of inputs
(c) Provision for spares
iii. No. of outputs
(c) Provision for spares
iv. Start/stop operation
(a) Local Manual
(b) Local Automatic
v. Mimic diagram display
(a) Electrical System
(b) Hydraulic System
vi. Mode of control
(a) Level control
(b) Speed control
(c) Flow control
(d) Sequence control
(e) Step by step control
vii. Temperature measurement
(a) Make of the scanner
(b) Holding capacity
(c) Time for scanning cycle
(d) Alarm setting range
(e) No. of setting levels
viii. Generator, transformer & feeder control panels
(e) Power factor meter
(f) Frequency meter
(g) DC ammeter for field current
(h) DC voltmeter for field voltage
ix. Transducers
(c) Accuracy class
B Alarm & Annunciation System
iii. Wattage of window indicating lamp
iv. Wattage of a set of windows
v. Interface with auto control system
vi. Adjustable range of cut-off time, if unacknowledged
vii. No. of active windows
viii. No. of spare windows
ix. Response time
x. UPS arrangement
xi. Dimension of each windows
xii. Dimensions of a set of window
xiii. Over all dimensions of annunciation panel
C PROTECTION SYSTEM
ii Type of numerical relays their functions
(a) For Generators
(b) For transformers
(c) For Feeders
iii. Built in testing facility
iv. Methodology to provide redundancy
v Type of back-up protection in case of failure of numerical relays
(a) For generators
(b) For transformers
(c) For Feeders
vi Parameter/command documentation
vii Maximum operating time
viii. Sensitivity in %age of rated current
ix. Analogue Input Variables
(a) Rated frequency
(b) Rated current
(c) Thermal rating of current circuits
(ii) For 10 seconds
(iii) For 1 second
x Rated Voltage
xi Thermal rating of voltage circuits (continuous)
xii Burden per phase
(a) At rated current
(b) At rated voltage
xiii Current Transformer Requirements
(a) Generator Protection
(ii) Saturation factor
(iii) Minimum knee point voltage
(iv) Maximum excitation current
(b) Transformer Protection
(ii) Saturation factor
(iii) Minimum knee point voltage
(iv) Maximum excitation current
(c) Feeder Protection
(ii) Saturation factor
(iii) Accuracy class
D ENERGY METERING SYSTEM
iii. CT/PT connection direct or through transducers
iv. Accuracy of meters
v. Accuracy of transducers, if any
vi. Parameters measured
vii. Maximum current rating for 1 second
viii. Service voltage range and tolerance
ix. Service frequency range and tolerance
x Service temperature range
xi Power consumption
a. Current circuit
b. Voltage circuit
xii Service life
xiii Protection against electromagnetic/radio interference
5 Station Service Board
a HT SITE CIRCUIT BREAKER
v. Rated Service Voltage
vi. One (1) minute power frequency withstand voltage.
vii. Rated continuous current at 50oC and within the cubicle.
viii. Short time current for one (1) Sec.
ix. Rated breaking capacity.
x Rated breaking current.
b) Asymmetrical
xi Rated making capacity
xii Operating mechanism
xiii Tempt. rise above 50oC
xiv. Operating duty
b AUXILIARY VOLTAGE
iii) Spring charging motor
iv) Space heater & lamp 240 VAC, 50 Hz
c CURRENT TRANSFORMER
iv. Rated voltage
vi. Power frequency withstand voltage.
viii. Rated short time current for one (1) Sec.
d POTENTIAL TRANSFORMER
iv. Rated voltage
vi. Power frequency withstand voltage.
viii. Rated short time current for one (1) Sec.
ix. Voltage Ratio
x Class of Accuracy
6 CONTROL AND RELAY PANELS
iii. Reference standard
iv. Construction
Degree of protection
Sheet metal thickness mm
Floor channel sills, vibration damping pads and kick plate furnished?
v Equipment mounting
All relays, meters and switches are flush mounted?
Relays furnished in draw out cases with built-in test facilities?
vii Internal illumination
Door switch controlled
viii. Space heater
Thermostat controlled?
ix. Plug socket
x Panel illumination, space heater and plug socket circuits provided with individual switch fuse units?
xi Internal wiring
Conductor material
Conductor size for
i. Current/control circuit
ii. Voltage circuit
Wires identified at both ends with ferrules?
xii Terminal block
Type/catalogue No.
20% spare terminals furnished?
xiii Ground bus
Colour shade Inside/Outside
Details of painting procedure furnished?
xv Breaker control switch
Reference standard
xvi Make & Continuous Amp
Break (inductive) Amp
xvii Meter selector switch
Reference standard
Make and continuous Amp
Break (inductive) Amp
xviii Push button
Reference standard
Make and continuous Amp
Break (inductive) Amp
No. and type of contacts per button
Reference standard
Series resistance
xx Indicating instruments
Reference standard
Type of movement
Scale in degrees
Overload capacity without loss in accuracy (%)
Burden on CT/PT
xxi Annunciator
Referred standard
No. of annunciator groups furnished?
No. of windows per group
Overall dimension of a group mm
Details write-up on scheme furnished?
xxii Illumination status indication for isolators
xxiii Semaphore indicators
Fuse bases provided with imprints of fuse rating and voltage
Catalogue of all relays submitted with bid
Whether tenderer agree to conduct all site tests as asked
If 'NO' indicated deviations
Whether quality assurance plan is acceptable
If 'NO' indicate deviations
Whether tenderer agree to provide No. of aux. Relays timers, range of relays/meters terminal blocks, control switches, wiring etc. as per approved drawings
Minimum clearance between relays/meter/casings HorizontalVertical
Deviation if any on technical design parameters for control protection metering and alarm system
Any additional protection, metering control; features, if necessary/desirable from tenderer's point of view
7 Earthing & Lightning Protection
i. Size of earth strip for the yard and power house
ii. Gap between earth mat conductors
iii. Size of main outer strip
iv. Galvanizing content on above
v. Value of earthing resistance (proposed to be achieved)
vi. Standard to be following for galvanizing
vii. Type of electrodes
viii. Construction of earthing pit as per IS
ix. Deviation if any on technical data sheet
x. Cable identification tag
xiii. Binding wire material
xiv. Buried cable/markers/covers
xv. Applicable standards
xvi. Material of protective covers 1.1 kV cables
xvii. LV Cables
xviii. Conduit & floor opening sealing compounds
xix Material & composition for:
i. Water proofing
ii. Fire proofing
xx Grounding for cable amount/sheaths
i. Material of conductor
xxi Structural steel
i. Painting of fabricated steel
a. Type of paint and no. of coats of primer
b. Type of paint no. of coats and colour of furnish
xxii Whether shield wires or lightning conductors have been envisaged for the lightning protection
xxiii Angle for protection
xxiv Numbers of electrodes provided
xxv Earthing resistance value
xxvi Size of down conductors
xxvii Standard followed
xxviii Deviations if any on technical data sheet
xxix Tools provided
a. All necessary tools, tackles, crimping tools
b. Welding equipment
c. HV cable testing equipment
8 Power House Lighting
i. Illumination levels of machine hall
ii. No. and type of fixtures
iii. Illumination levels of Switchgear room
iv. No. and type of fixtures
v. Illumination levels of Control room
vi. No. and type of fixtures
vii. Illumination levels of Office room
viii. No. and type of fixtures
ix. Illumination levels of Turbine floor
x. No. and type of fixtures
xi. Illumination levels of Switchyard
xii. No. and type of fixtures
xiii. Illumination levels of Compressor room/ pump house etc.
xiv. No. and type of fixtures
xv. Illumination levels of Turbine auxiliaries
xvi. No. and type of fixtures
xvii. Illumination levels of Cable basement
xviii. No. and type of fixtures
xix. Street lighting
xx. No. of posts
xxii. No. of Masts
xxiv Make of conduit pipes, type, size and thickness
xxv Make of Sockets
xxvi No. of sockets (20A)
No. of sockets (63A)
No. of sockets (5A)
xxvii No. of sockets (15A)
xxviii Method of automatic control (synchronous timer or photocell)
xxix Sub distribution boards
xxx Size of boards
xxxi No. of circuits in one board
xxxii Rating of MCCBs
Short time rating
No. of operations at breaking at 100% short circuit current
Location of sub distribution boards
xxxiii Environmental protection
xxxiv Thickness of sheet
xxxv Make of fixtures/fittings
xxxvii Size of wires
xxxviii Current carrying capacity
xxxix Fusing current and time
9 CONDUCTOR, INSULATORS & HARDWARES
ACSR Conductor 'Dog'
iv. Nominal current rating at maximum site ambient temperature
v. Short time rating for 3 sec. (in kA)
vi. Rated dynamic stability current kA (peak)
vii. Weight per mtr in kg
viii. Clearance Phase to phase Phase to earth
10 INSULATORS AND HARDWARES
iii. Material of insulator
v Insuations level
vi Creepage distance
vii Power freq. Puncture test
viii. Visible discharge test volt
ix. For support insulators minimum height of base from ground
x Number of disc in string insulators
xi Rated voltage for disc in kV
xii Deviation if any from the data sheet
iv. Clamps And Connectors
12 11 kV LIGHTNING ARRESTORS
i. Name of manufacture
ii. Manufacturer's type designation
iii. Standards applicable
iv. Arrestor class and type
v. Rated arrestor voltage kV (rms)
vi. Nominal system voltage kV (rms)
vii. Rated frequency Hz
viii. Nominal discharge current (8/20 micro sec wave) kA (peak)
ix. Max. 100% 12/50 micro sec. spark over voltage kV (peak)
x. Max. wave front spark over voltage kV (peak) & front steepness kV/sec.
xi. Max. residual voltage at rated nominal discharge current kV (peak)
xii. Impulse current withstand
High current short duration (4/10 micro sec. wave) kA (peak)
Low current long duration Amps. (peak)
xiii. Wet and dry power frequency withstand voltage for the housing kV (rms)
xiv. Impulse withstand strength of arrester housing with 1.2/50 micro-sec wave kV (peak)
xv. Total creepage distance of the arrester housing mm
xvi. Protected creepage distance of the arrestor housing mm
xvii. Total weight of material included for supporting structures
Thickness of galvanizing micron
Total height of structures in mm
xviii. Suitable for outdoor duty.
xix. Confirm that all particulars given in Tech. Particulars in GTP sheet are acceptable
xx. If answer is 'NO' in 19 indicate point-wise deviation
13 11 kV ISOLATORS
i. Name of manufacturer
ii. Manufacturer's type designation
iii. Standards applicable
v. Rated voltage (kV)
vi. Rated frequency
vii Current rating
Continuous (at design temp.) (A)
Current rating at site condition (A)
Dynamic through fault (A)
Second rating (kA)
Making current (A)
viii. Design ambient temperature (°C)
ix. Maximum temperature of current carrying parts with carrying rated current at specified ambient temperature, (°C)
x. Maximum temperature of current carrying parts with carrying short circuit current for 3 seconds at temperature, (°C)
xi. One minute power frequency dry & wet withstand voltage
xii 1.2/50 micro-second impulse withstand voltage
xiii Switch contact particulars
Type of main isolating contacts
Area & material of contacts
Thickness of silver facing
xiv. Number of auxiliary contacts on disconnecting switch
xv Rating of auxiliary contacts
Breaking current (A)
xvi Type of interlock between earthing blade and isolator
xvii Particulars of isolator operating mechanism
xix No. of operations the disconnecting switch can withstand without deterioration of contacts
between phases,
between live parts & earth mm
between fixed contacts and blade in open position mm
xxi a. Capacitive current that can safely be interrupted
by the switch (A)
b. Magnetizing current that can safely be
interrupted by the switch (A).
xxii Type and make of insulators
xxiii No. of insulators per stack
xxiv One minute dry & wet withstand voltage per stack, kV (rms)
xxv Impulse voltage of insulator stack at 1.2/50 micro seconds positive full wave kV (peak)
xxvi Creepage distance
xxvii Total weight (kg)
xxviii Dimensions of switch L x B x H (mm x mm x mm)
xxix Shipping dimension of largest package
xxx Provision of earthing switch
xxxi GA drg. of disconnect switch along-with support structure
xxxii Supporting structures
Total weight/isolator (kg)
Thickness of galvanizing micron
Total height of structure in mm
xxxiii Power and control power supply voltage
xxxiv Confirm that all particulars given in technical particulars are acceptable to tenderer
xxxv If answer is 'NO' in above then indicate point wise deviation
TO BE FILLED IN BY BIDDER
NIT No. :- 04/ Elect/ 2025-26 Dated 30.03.2026
Name of work :- Completion of Balance E&M works on turnkey basis
Project Name :- Walidad SHP (1 x 700 KW)
1 Name of the Bidder :-
2 Address of the Bidder :-
3 Quoted Amount :- Amount (in Rs.) With GST
a **In Figure :- 0
** Grand Total in word to be filled by bidders.
Schedule of quantities and prices of Walidad SHP (1×700 kW)
Sl. No. Items Unit Qty. ** GST (%)
*Rate (in Rs.) ***Amount (in Rs.)
Without GST With GST
1 Item to be supplied
A Turbine and Auxiliaries
i Piping, Valves , 1 HP Booster pump & hardware for Cooling Water System No. 1 0 0
ii Guide bearing No. 1 0 0 0 0
iii Vacuum valve No. 1 0 0 0 0
iv Oil purification machine (1000 LPH) No. 1 0 0 0 0
v Control cards No. 1 0 0 0 0
B Station Auxiliaries 0 0 0
i Earthing & Lightning Equipment Lot 1 0 0 0 0
ii All types of Power Cables, Control Cables, Cable Accessories Lot 1 0 0 0 0
iii Lighting system of power house including fittings Lot 1 0 0 0 0
iv Fire Fighting system Co2 Lot 6 0 0 0 0
v Fire Fighting system Foam Lot 4 0 0 0 0
vi Air conditioning System for Control Room (2 Nos. 2 ton Windows AC) Rating 5 Star Nos. 2 0 0 0 0
vii Air conditioning System for Office (1 No. 1.5 ton Split/Windows AC) Rating 5 Star No. 1 0 0 0 0
viii Ventilation system Nos. 6 0 0 0 0
ix. Drainage & dewatering pump (5 HP 3 phase) No. 1 0 0 0 0
x. 1 HP motor for 10 Ton EOT crane for long & cross travel Nos. 2 0 0 0 0
xi. 24 V 200 Ah battery bank for power house No. 1 0 0 0 0
xii 24 V 200 Ah battery for DG set No. 1 0 0 0 0
xiii 20 W solar street light with 125 W PV module & 6 m 4" pipe 54 Ah LFP battery Nos. 5 0 0 0 0
C Power Evacuation System at Walidad HEP 0 0 0
a Control Relay panel for transformer cum feeder including control, protections and metering systems Nos. 1 0 0 0 0
b 11 kV, 630A, 18.4 kA VCB suitable for indoor installation Nos. 1 0 0 0 0
c 11 kV CTs, 100/1A, 3 Core, 0.2/5P10/PS 20VA cast resin Nos. 3 0 0 0 0
d 11 kV, PT 11 kV/√3/110V/√3/110V/ √3, 50 VA, CLASS 0.2/3P cast resin (3 phase) Nos. 3 0 0 0 0
e Lightning Arrestors 9KV, 10KA station type metal oxide Nos. 3 0 0 0 0
f Isolator 11 kV, 630 A three phase gang operated with earth switch No. 1 0 0 0 0
g All types of Power and Control Cable with accessories Lot 1 0 0 0 0
h Conductor ACSR ‘WEASEL’ for Jumpering of switchyard equipment. Lot 1 0 0 0 0
i Hardware, clamps & connectors, insulators etc. Lot 1 0 0 0 0
j Terminal structure, supporting structure of equipment and cable racks etc. Lot 1 0 0 0 0
k Earthing Material Lot 1 0 0 0 0
l Pale Fencing Lot 1 0 0 0 0
D 11 kV Works at Pahleja PSS 0 0 0 0
a Control Relay panel for feeder including control, protections and metering systems (including ABT meter) Nos. 1 0 0 0 0
b 11 kV, 630A, 18.4 kA VCB suitable for indoor installation Nos. 1 0 0 0 0
c 11 kV CTs, 100/1A, 3 Core, 0.2/5P10/PS 20VA cast resin Nos. 3 0 0 0 0
d 11 kV, PT 11 kV/√3/110V/√3/110V/ √3, 50 VA, CLASS 0.2/3P cast resin (3 phase) Nos. 3 0 0 0 0
e Lightning Arrestors 9 KV, 10 KA station type metal oxide Nos. 3 0 0 0 0
f Isolator 11 kV, 630 A three phase gang operated with earth switch Nos. 1 0 0 0 0
g Isolator 11 kV, 630 A three phase gang operated without earth switch Nos. 1 0 0 0 0
h All types of Power and Control Cable Lot 1 0 0 0 0
i Conductor ACSR ‘WEASEL’ for Jumpering of switchyard equipment. Lot 1 0 0 0 0
j Hardware, clamps & connectors, insulators etc. Lot 1 0 0 0 0
k Terminal structure, supporting structure of equipment and cable racks etc. Lot 1 0 0 0 0
l Earthing and Lightning Lot 1 0 0 0 0
m 11 KV metering system Lot 1 0 0 0 0
Sub Total (1) 0 0
2 Servicing of the Already Supplied and Erected Equipments Servicing of already supplied and erected equipment, including dismantling, cleaning, polishing, replacement of grease and other lubricants, replacement of all seals and re-assembly alignment. Refurbishing, Rewinding & refilling with marchaling box instruments of transformer & its testing.
i. Turbine and Auxiliaries and control panels Nos 1 0 0 0 0
ii. Gear Box Nos 1 0 0 0 0
iii. Generator and Auxiliaries and control cables Nos 1 0 0 0 0
iv. Station Auxiliaries including DG set Lot 1 0 0 0 0
v. Switchyard Equipment (Main transformer & Auxiliary transformer) Lot 1 0 0 0 0
Sub Total (2) 0 0
3 Erection Works Erection, Testing and commisiioning of above item to be supplied
A Turbine and Auxiliaries
i Piping, Valves , 1 HP Booster pump & hardware for Cooling Water System No. 1 0 0 0 0
ii Guide bearing No. 1 0 0 0 0
iii Vacuum valve No. 1 0 0 0 0
iv Oil purification machine (1000 LPH) No. 1 0 0 0 0
v Control cards No. 1 0 0 0 0
B Station Auxiliaries 0
i Earthing & Lightning Equipment Lot 1 0 0 0 0
ii All types of Power Cables, Control Cables, Cable Accessories Lot 1 0 0 0 0
iii Lighting system of power house including fittings Lot 1 0 0 0 0
iv Fire Fighting system Co2 Lot 6 0 0 0 0
v Fire Fighting system Foam Lot 4 0 0 0 0
vi Air conditioning System for Control Room (2 Nos. 2 ton Windows AC) Rating 5 Star Nos. 2 0 0 0 0
vii Air conditioning System for Office (1 No. 1.5 ton Split/Windows AC) Rating 5 Star No. 1 0 0 0 0
viii Ventilation system Nos. 6 0 0 0 0
ix. Drainage & dewatering pump (5 HP 3 phase) No. 1 0 0 0 0
x. 1 HP motor for 10 Ton EOT crane for long & cross travel Nos. 2 0 0 0 0
xi. 24 V 200 Ah battery bank for power house No. 1 0 0 0 0
xii 24 V 200 Ah battery for DG set No. 1 0 0 0 0
xiii 20 W solar street light with 125 W PV module & 6 m 4" pipe 54 Ah LFP battery Nos. 5 0 0 0 0
C Power Evacuation System at Walidad HEP
a Control Relay panel for transformer cum feeder including control, protections and metering systems Nos. 1 0 0 0 0
b 11 kV, 630A, 18.4 kA VCB suitable for indoor installation Nos. 1 0 0 0 0
c 11 kV CTs, 100/1A, 3 Core, 0.2/5P10/PS 20VA cast resin Nos. 3 0 0 0 0
d 11 kV, PT 11 kV/√3/110V/√3/110V/ √3, 50 VA, CLASS 0.2/3P cast resin (3 phase) Nos. 3 0 0 0 0
e Lightning Arrestors 9KV, 10KA station type metal oxide Nos. 3 0 0 0 0
f Isolator 11 kV, 630 A three phase gang operated with earth switch No. 1 0 0 0 0
g All types of Power and Control Cable with accessories Lot 1 0 0 0 0
h Conductor ACSR ‘WEASEL’ for Jumpering of switchyard equipment. Lot 1 0 0 0 0
i Hardware, clamps & connectors, insulators etc. Lot 1 0 0 0 0
j Terminal structure, supporting structure of equipment and cable racks etc. Lot 1 0 0 0 0
k Earthing Material Lot 1 0 0 0 0
l Pale Fencing Lot 1 0 0 0 0
D 11 kV Works at Pahleja PSS 0
a Control Relay panel for feeder including control, protections and metering systems (including ABT meter) Nos. 1 0 0 0 0
b 11 kV, 630A, 18.4 kA VCB suitable for indoor installation Nos. 1 0 0 0 0
c 11 kV CTs, 100/1A, 3 Core, 0.2/5P10/PS 20VA cast resin Nos. 3 0 0 0 0
d 11 kV, PT 11 kV/√3/110V/√3/110V/ √3, 50 VA, CLASS 0.2/3P cast resin (3 phase) Nos. 3 0 0 0 0
e Lightning Arrestors 9 KV, 10 KA station type metal oxide Nos. 3 0 0 0 0
f Isolator 11 kV, 630 A three phase gang operated with earth switch Nos. 1 0 0 0 0
g Isolator 11 kV, 630 A three phase gang operated without earth switch Nos. 1 0 0 0 0
h All types of Power and Control Cable Lot 1 0 0 0 0
i Conductor ACSR ‘WEASEL’ for Jumpering of switchyard equipment. Lot 1 0 0 0 0
j Hardware, clamps & connectors, insulators etc. Lot 1 0 0 0 0
k Terminal structure, supporting structure of equipment and cable racks etc. Lot 1 0 0 0 0
l Earthing and Lightning Lot 1 0 0 0 0
m 11 KV metering system Lot 1 0 0 0 0
Sub Total (3) 0 0
4 Testing & commissioning Testing and commissioning of complete Unit, Auxiliaries, Station Auxiliaries and Power Evacuation System (Inculuding already supplied items) No 1 0 0 0 0
5 O&M of plant (90 Operational Days) Month 3 0 0 0 0
6 Construction of 11 kV line, including survey, alignment, peg marking, excavation, erection of poles, fixing of cross arms, 11 kV isolators (2 Nos.) hoisting of insulators, paying of conductor, stringing and final sagging with earthing etc. KM 5 0 0 0 0
7 2 Nos 16 inch Bore Hole (250 feet deep) complete with casing, PVC pipes, filter etc. and commissioning of cooling water system with complete foundation and structutre with platform and railing for the 12m (above the machine hall level) over head storage PVC tank (Triple layer) 5000 Ltr. including Level switch for the Automatic operation of pump Lot 1 0 0 0 0
9 Mandatory Spares
i. Turbine Lot 1 0 0 0 0
ii. Cooling Water system Lot 1 0 0 0 0
iii. Gear Box Lot 1 0 0 0 0
iv. Generators Lot 1 0 0 0 0
v. EOT Crane Lot 1 0 0 0 0
vi. DG Set Lot 1 0 0 0 0
vii. Switchgear, Control Panel Lot 1 0 0 0 0
viii. Battery and Battery Charger Lot 1 0 0 0 0
ix. OPU Lot 1 0 0 0 0
x. Bulbs & Fuses Lot 1 0 0 0 0
xi. Miniature relay, Contractor Auxiliary switch Lot 1 0 0 0 0
xii. Governor Spares Lot 1 0 0 0 0
xiii. Station Transformer Lot. 1 0 0 0 0
xiv. Main Transformer Lot. 1 0 0 0 0
xv. 11 kV Circuit Breaker Lot. 1 0 0 0 0
xvi. Isolators Lot. 1 0 0 0 0
xvii. Lightning Arrestors Lot. 1 0 0 0 0
xviii. Current Transformer Lot. 1 0 0 0 0
xix. Potential Transformer Lot. 1 0 0 0 0
Sub Total (9) 0 0
Grand Total (8+9+10) 0 0
Total price without GST - Rs. 0
Total price with GST - Rs. 0
Note :- This is an EPC contract . Bidder to ensure the supply of items , so as to complete the system and to ensure the operation with safety and efficiency
* Rates are to be filled up by the bidder and taken excluding GST.
** GST (%) is to be filled up by the bidders.
*** The amount will come automatically after filling the rate of respective item. At present this amount is being shown.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
DetailedNIT.pdf
NIT • 0.31 MB
DetailedNIT.pdf
NIT • 0.31 MB
TD-WALIDAD-VOL1.pdf
NIT • 0.82 MB
TD-WALIDAD-VOL2.pdf
NIT • 0.85 MB
TD-WALIDAD-VOL3.pdf
NIT • 0.82 MB
SLD -Walidad.pdf
NIT • 0.24 MB
Technical Bid Sheet.xlsx
NIT • 0.06 MB
Price Bid Sheet.xlsx
NIT • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .