| Sl No | Description | Qty | Unit | Aruna Electricals L1 | Sathyanarayana Electricals L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, Erection, testing and commissioning of 11KV 25 KA 630Amps 3 Panel HT INDOOR RING MAIN GEAR Switch board suitable for Indoor installation comprising two incomer Load break switches panels and one outgoing 11 kv HT Vacuum Circuit Breaker complete as per TANGEDCO specification with Mechanical inter lock between incomers. 1.Supply and Erection of Draw out type 11KV 25KA 630Amps Horizontal draw out/Horizontal Isolation VACCUM CIRCUIT BREAKER filled with motor(230V AC) operated spring charged Mechanism, with ON and OFF mechanical Indicator Anti Pumping Device, 110V DC Shunt Trip and Closing Coils (DC source of supply to be derived from a power pack suitable for three Tripping and two closing operations incorporated on Incoming panel only) Mechanical Operation counter, 4NO + NC Spare Aux. Contact with contact multiplication Contactor for customer use. Automatic safety shutter, Mechanical close/Trip Knob, Mechanical ON/OFF Indication, Operating Handle, 230V AC to 110V DC Power pack operating Handle etc.-1No 2. Supply and erection of 11KV 630Amps 25KA HT Air Break/Load Break Switch with mechanically inter locked earth switch, front operated spring assisted manual closing mechanism, 2 NO+2NC Aux. Contact operating handle etc.- 1No 3. 11KV/Root 3/110V/Root3-Three Phase 3 Limb 50VA class 0.5 Resin cast Draw out type potential Transformer complete with HT and LT HRC fuses with sealing arrangement-3 Nos. | 1 | Set | 8,00,000 ₹8 L | 8,50,000 ₹8.5 L |
| 1.014. Current Transformer of Suitable Ratio/5-5A dual Core (Core 1- 5VA Class 0.5 for Metering & Core 15 VA 5P 20 for Protection - 3 Nos. 5. Meters: Analog ammeter with 5 position selector switch - 1No Analog Voltmeter with selector switch- 1No cut out provision to receive digital Trivector Meter L&T or secure to be provided. 6. Protection: MCDG 61 TP ND IDMT two over current and one earth fault Relay with higher set Instt. Elements 1.3 Seconds-1No Master Trip relay Mega win MVAJH 13 eqivalent-1 No 7.Breaker On/Off indication LED Type-2 No Auto Trip/ Healthy Trip and spring charges indication LED type-3 Nos phase indicating Lamps RYB - 3Nos 8.TNC Breaker Control Switch -1 No local Remote selector switch- 1 No Push button for trip Healthy- 1 No 9. Necessary Control wiring with Copper wire 10. 630Amps Copper Bus bar PVC sleeved & required panel Earthing 11. Common for Switch gear MCB's for AC/DC Control Heater ON/OFF switch with space Heater and thermostat, single phases switch socket, cubicle illumination TL lamp, Door switch fully covered Test Terminal block of IMP make (wherever applicable) 12.MS Sheet steel Enclosure for indoor Installations powder coated with siemens Grey paint finish 13. Provision through bottom entry to receive Incomer & Out going cable excluding cable glands and cable Termination Kit (Make: System Control/Siemens) | |||||
| 2.00 | Supply and providing cable end termination suitable for 3 core 300 sq.mm HT Cable outdoor Terminations 11KV (UE) - Belted PILC cables XLPE HTUG cable with necessary outdoor type heat / cold shinkable joint kit and accessories. (Make: RayChem) | 6 | Nos | 21,750 ₹1.3 L | 23,500 ₹1.4 L |
| 3.00 | Supply and installation of GI perforated cable tray with cover of the following sizes 300 mm width x Depth 50 mm thickness 14 SWG The cable tray shall be fabricated in standard length of 2.5 meter of size with suitable supporting arrangements shall be provided at equal intervals with suitable angle/ channel from the wall / ceiling while erecting the cable tray. Jointing of cable trays shall be GI Coupler plates to match the dimension of the cable tray. Fixing both for the jointing of the tray and fixing of the trays on the structure shall be with Thread Rod or approved type of corrosion resistant fixtures. | 215 | Mtrs | 2,830 ₹6.1 L | 3,100 ₹6.7 L |
| 4.00 | Preparation of electrical schematic diagram site plans physical layout 5 copies and payment of CEIG fees submission of completion report obtaining drawing approval safety certificate etc., complete including lamination copy fixed at panel room (Only HT Side) | 1 | Job | 49,500 ₹49,500 | 1,00,000 ₹1 L |
| 5.00 | Liasioning charges for MRT Testing, installation charges, packing, forwarding and Transporting complete etc., | 1 | Job | 63,300 ₹63,300 | 65,000 ₹65,000 |
| 6.00 | GST @ 18% | 1 | Nos | 2,97,315 ₹3.0 L | 3,28,050 ₹3.3 L |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
25 Feb 2026, 3:00 pmClosed
The Superintending Engineer, PWD.,
O/o. The Superintending Engineer, PWD., Buildings (C and M) Circle-1, Chepauk, Chennai-5
Sub Work. Provision of RMG and Cable tray arrangements to Tamil Nadu Government Dental College Hospital, Chennai-3. (Second Call)
2026_PWD_661533_1
PWD/BCMC1/128-1/2025-26
Open Tender
Electrical Works
60 days
Govt. Dental College and Hospital
Refer Tender Condition
8 documents required · 8 mandatory
₹0
₹20,000
1 Apr 2026
19 Feb 2026
25 Feb 2026
19 Feb 2026
25 Feb 2026
19 Feb 2026
Supply, Erection, testing and commissioning of 11KV 25 KA 630Amps 3 Panel HT INDOOR RING MAIN GEAR Switch board suitable for Indoor installation comprising two incomer Load break switches panels and one outgoing 11 kv HT Vacuum Circuit Breaker complete as per TANGEDCO specification with Mechanical inter lock between incomers. 1.Supply and Erection of Draw out type 11KV 25KA 630Amps Horizontal draw out/Horizontal Isolation VACCUM CIRCUIT BREAKER filled with motor(230V AC) operated spring charged Mechanism, with ON and OFF mechanical Indicator Anti Pumping Device, 110V DC Shunt Trip and Closing Coils (DC source of supply to be derived from a power pack suitable for three Tripping and two closing operations incorporated on Incoming panel only) Mechanical Operation counter, 4NO + NC Spare Aux. Contact with contact multiplication Contactor for customer use. Automatic safety shutter, Mechanical close/Trip Knob, Mechanical ON/OFF Indication, Operating Handle, 230V AC to 110V DC Power pack operating Handle etc.-1No 2. Supply and erection of 11KV 630Amps 25KA HT Air Break/Load Break Switch with mechanically inter locked earth switch, front operated spring assisted manual closing mechanism, 2 NO+2NC Aux. Contact operating handle etc.- 1No 3. 11KV/Root 3/110V/Root3-Three Phase 3 Limb 50VA class 0.5 Resin cast Draw out type potential Transformer complete with HT and LT HRC fuses with sealing arrangement-3 Nos.
Supply and providing cable end termination suitable for 3 core 300 sq.mm HT Cable outdoor Terminations 11KV (UE) - Belted PILC cables XLPE HTUG cable with necessary outdoor type heat / cold shinkable joint kit and accessories. (Make: RayChem)
Supply and installation of GI perforated cable tray with cover of the following sizes 300 mm width x Depth 50 mm thickness 14 SWG The cable tray shall be fabricated in standard length of 2.5 meter of size with suitable supporting arrangements shall be provided at equal intervals with suitable angle/ channel from the wall / ceiling while erecting the cable tray. Jointing of cable trays shall be GI Coupler plates to match the dimension of the cable tray. Fixing both for the jointing of the tray and fixing of the trays on the structure shall be with Thread Rod or approved type of corrosion resistant fixtures.
Preparation of electrical schematic diagram site plans physical layout 5 copies and payment of CEIG fees submission of completion report obtaining drawing approval safety certificate etc., complete including lamination copy fixed at panel room (Only HT Side)
Liasioning charges for MRT Testing, installation charges, packing, forwarding and Transporting complete etc.,
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_794456.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
RMGCableTrayDentalCollegeSchCondition.pdf
Tender Documents • 0.78 MB
BOQ_794456.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid