Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹93.9 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹96.8 L+₹2.4 L (2.52%)Rejected-Finance RAILWAY ROAD 9 10 KC MARKET 132001 2021R66 | KARNAL | HARYANA | 132001 | L2 | Rejected-Finance L2 |
Tender Value
₹79.9 L
EMD Value
₹1.6 L
Closing Date
20 Jul 2020, 5:00 pmClosed
Raja Nagender Singh
NIRMAN SADAN , 4TH FLOOR, CIVIL LINES , PWD B and R (Elect.)GURUGRAM
Recall-Special repair of Govt. Medical College Chhainsa (Erstwhile Gold Field Institute of Medical Science and Research Faridabad) For Establishment of Exclusive of Exclusive COVID 19 Hospital in Faridabad District (Pdg. 1000 KVA Oil Type Transforme
2020_HRY_134801_1
PWD (Elect.) 2020
Open Tender
Electrical Works
Works
365 days
XEN(E) Gurugram
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Yes
Public Work (B and R) Department
₹1.6 L
Yes
24 Dec 2020
9 Jul 2020
21 Jul 2020
9 Jul 2020
20 Jul 2020
9 Jul 2020
Amount
Cement Concerete Platform:- Earth work in excavation in fundations, trenches, etc in all kinds of soils, not exceeding 2 Meter depth including dressing of bottom and sides of trenches, stacking the excavated soil, clear from the edge of excavation and subsquent filling around masonry in 15 cm layers with compaction, including disposal of all surplus soil as directed with a lead of 30 metes.
Cement lime concrete 1:8:16 with brick blast 40mm nominal size in foundation and plinth.
Cement concrete 1:2:4 with slone aggregate 20mm nominal size in foundation and plinth.
First Class bricks work laid in cement sand mortar 1:6 in foundation and plinth
11:43 cm thick bricks wall laid in cement sand mortar 1:4 without rainforecement, in foundation and plinth.
Conglomerte floor 50 mm thick CC topping 1:2:4
12 mm thick cement plaster 1:6
(I) Steel Rainforcement Mild steel reinforcement for RCC works where not included in the complete rate of RCC, including bending, binding and placing in position complete
Pipe Laying. Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. (vii) Galvanised iron pipe 65 mm dia on surface.
Earthing (iii) Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc.(but without charcoal or coke and salt) complete as equired.
Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode.
Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required .
Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required .
Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material.
Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material.
(R) Lightning conductor Copper. Supply and erection of copper tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with suitable copper stapples of same size.
(b) Lightning conductor Galvanised iron. Supply and erection of G.I. tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with G.I. stapples of same size.
Under Ground Cables. Supply and erection of under ground cable 1 metre below ground level covered with sand and bricks including necessary connections,digging and refiling of trenches. 300 Sq. mm 3.5 Core Ard. Cable .
Supply and erection of under ground cable, loose in existing pipe or trenches complete with necessary connections . 300 Sq. mm 3.5 Core Ard. Cable .
Supply and erection of suitable compression type brass cable glands for underground Cable. 300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core .
Street Light. Supply and erection of prestressed cement concrete pole as per IS : 1678-1960. 9 metres long 105 mm x 115 mm at top and 105 mm x 315 mm at bottom with working load of 200 Kg. burried 1.80 m in ground.
Supply , erection, testing and commissioning of wall / free standing floor mounting dust and vermin proof compartmentalized cubical Panel made out of 2.0 mm thick CRCA sheet, required hardware, 3mm thick bakelite sheet provided all along the bus bar and cable alley separating switches compartment and supporting suitable channel, dully painted by 2 coat of zinc / Red oxide primer followed by 2 coats of powder coating in grey or required shade after rinsing. The panel having PU/ Neoprene ruBus Barer gasket of not less than 3 mm thickness, separate detachable gland plate MS base channel, hinged door with inter locking arrangement for equipment / switch gear, Transparent acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bars. Extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. The panel will be complete with control wiring ( copper) and fuse protection. ( only outer area on all sides shall be measured).
Supply and erection of copper bus bar duly tinned by means of SMC/DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending, cutting in required size and shape and insulation with colour coading heat shrinkable PVC sleeves complete in all respect upto entire satisfaction of Engineer-in-charge of work.
Supply & fixing of rotary handle for on / off operation of existing MCCB in the LT panel including fixing the same in position with all labour and material required to complete the job in all respect Rotary handle up to 125 A, MCCB
Rotary handle above 125 A, MCCB
Supply and erection of moulded case circuit brecaker single pole/ 4 pole on wall/ on existing pedestal including bounding to earth and making necessary connection required to complete the job the job in all respect up to the entire satisfaction of the Engineer -in - Charge of the work. 4 pole MCCB 6 to 63 amp.
4 pole MCCB 100 amp.
Supply and erection of XLPE (E) 11 KV HT aluminum conductors armoured cable ISI mark laid in 1 meter below grund level with sand and bricks with all labour and material including digging and refilling of trench required to complete the job in all respect upto the entire satisfaction of the Engineer - In - Chage of the work. 120 sqmm 3 core XLPE cable
Supply and erection of XLPE (E) 11 KV HT aluminum conductors armoured cable ISI mark laid in existing pipe/ trenches/ surface with all labour and material including digging and refilling of trench required to complete the job in all respect upto the entire satisfaction of the Engineer - In - Chage of the work.120 sqmm 3 core XLPE cable
Supply and erection of heat shrinkage type end termination jointing kit indoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cble/ ABC cable complete with all the kit contents including earth continuing connection along with 3 nos. crimpling type aluminum lugs of suitable capacity including makiing joining etc. complete in all respect. Suitable for 70 to 120 sqmm 3 core XLPE cable
Supply and erection of heat shrinkage type end termination jointing kit outdoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cble/ ABC cable complete with all the kit contents including earth continuing connection along with 3 nos. crimpling type aluminum lugs of suitable capacity including makiing joining etc. complee in all respect. Suitable for 70 to 120 sqmm 3 core XLPE cable
Supply & erection of cable tray made out of 2 mm thick galvanised perforated sheet steel including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect upto the entire satisfaction of Engineer - in - Chage of the work. 50 x 300 mm
Supply & erection of factory manufactured cable tray cover made of the G.I. sheet complete with fastoner nuts bolts and in position including the petty material required to complete the job in all respect upto the entire satisfaction of Engineer - in - Chage of the work. Suitable for 50 x 300 mm
Supply, installation, testing and commissioning of 1000KVA 11kV/433 Volts oil cooled transformer with OLTC +5% to - 15% steps of 1.25% with HV/LV cable box as per IS 1180 (Energy Efficiency level 2) as under :- No. load voltage ratio 11/ 0.43KV No. of phase 3 Frequency cycles = 50 Hz Type = Double wound core type copper wound. Cooling = ONAN , Vector group - DYN 11 Tapping on HV compensation + 5 % to - 5% in steps of 2.5% , Tap changer = Off load Tap changer , Temperature rise ( oil / winding) = 40 / 45 C, Termination HV/LV/ orientation = Cable box/ cable/ 180 deg. , Percentage Impedance (IS Tol) = 4.50% (IS Tol) , Total Loss @ 50% load = 1.86 KW (Max.) as per energy energy efficiency level-2, Total Loss @ 100% load = 5.30 KW (Max.) as per energy energy efficiency level-2, Duty = Outdoor, Insulation level = (KVp/KVrms), HV = 75/28, LV = --/03 Fitting /accesories Provides:3 Phase, 50 Hz, copper wound, two winding, core type transformer, cnfirming to IS : 2026 - latest, with an active part mounted on top cover/ Tank mounted and having the following fittings & accessories - 1 no. - Rating & diagram plate, 2 nos. - Earthing terminals, 4 nos. - Lifting Lugs, 1 no. - Oil level indicator with minimum level marking, 2 Nos. - Thermometer pockets, 1 no. - Conventional Conservator ,1 no. - Air release plug, 1 no. - Off circuit tap changer, 4 nos. - Bi - directional rollers, Jacking Pads, Radiators, Windging temprature indicator, Oil temp. indicator, Cable end box on HV side and LV side, Marshel box,Explosion vent,Bottom drain - cum filter valve, Top filter valve
Supply & erection of lightning arestor of W.S./ G.E. make SDU suitable for 11KV 3 Phase 50cycle grounded neutral system comprising of spark gap type quench gap types in series with non lineer register element housed in horizental seals porcelin bushing with line ground terminal alongwith mounting clamp conforming to ISS-3070 part-II of 1985 with latest ammendments with all labour and meterial required up to the entire satisfaction of Engineer -in-charge of work
Supply & erection of fire existinguishers ISI mark(AJAY Make) CO2 type 4.5 kg. Capacity as per IS:7285 duly erected/ hang on wall with hooks with all labour and material required to complete the job in all respect to the entire satisfaction of Engineer-in-charge of work.
Supply and erection of 11 K.V gang operated switch Jayshree make conforming ot IS and latest ammendment including suitable size of copper blade erection of same on existing H-pole with the help of 3 Nos. Channels of size 75x 40 x 6 mm thick 1.8 M long fixed with suitable size of M.S. Clamp, nuts and bolts including cost of 6 Nos 11K.V. Pin insulator with G.I. Pin, RD Fuses and painting with 2 coat of approved paint and one coat of red oxide including all labour and material required to complete the job in all respect to the entire satisfaction of Engineer-in-charge of work.
Supply and erection of stay wire suitable for 9M long PCC pole made out of 7/3 SWG GI wire with U type M.S. Rod 5/8" dia duly threaded by means of angle iron of size 50 x 50 x 6 mm x 30 cm 6 feet long M.S. Rod burried in ground after fixing with cross channel size 75 x 40 x 6 mm x 60 cm long the stay wire will be binded on the top of the pole with help of suitable size of double U type M.S. Clamps and stay fixed with nuts and bolts the stay wire shall be insulated in the middle piont with the help of egg insulator including all labour and material required to complete the job in all respect to the entire satisfaction of Engineer-in-charge of work.
S/E of MS bucket stand suitable for six Nos. fire buckets (but without buckets) including the cost of welding & painting with all cost of red oxide adn two coat of enamelled paint of red colour completion all respect.
Supply and erection of fire bucket of G.I. sheet of 24 gauge written with " FIRE" as per fire specifications.
Supply and erection of Rubber Mat 1mx2mmx 3mm thick suitable for 11/33 KV as per IS No.15652C/M/L 3017739 as approved by Chief Electrical inspector, Govt. of Haryana.
S/E of 11KV disc insulator (jayshree make) with pin with labour and material required to complete the job including fixing the same on existing chanel complete in all respect
S/E of M.S. channel, MS angle, MS flat & nuts & bolts of required size including painting and cutting etc. with labour and material required to complete the job including fixing the same on existing pole complete in all repspect
Supply installation testing and commissioning of 800 Amp. 4 pole 50KA microprocesser based manual drawout type ACB including cost of under voltage release, rotary handle, shunt trip and closing coil including making necessary connection with all labour and material required to complete the job in all respect upto entire satisfaction of Engineer -in- charge of the work.
Supply, installation, testing and commissioning of 500 KVA, D.G. set comprising of : radiator cooled, developing 608.0 BHP at 1500 RPM, complete with Electronic Governor, standard accessories coupled to alternator rated at 400 KW/ 500 KVA at 415 Volts, mounted on channel iron base framed complete with fuel tank & batteries and standard accessories alongwith AMF panel in liu of STD panel with all labour & material to complete the job in all respect upto the Entire satisfaction of Engineer - in - Charge of the work.
EXHAUST SYSTEM Designing, supplying, erecting, testing & commissioning of exhaust piping of the following sizes conforming to IS:3589 suitable for above 500 kVA and 1010 KVA DG Sets with all required flexible bellow connections, bends, thermal insulated 50 mm thick LRB lagging with chicken wire mesh and 24 gauge aluminimum sheet wrapping over the exhaust pipes including all necessary fastening accessories for fixing the pipes to MS support as specified and as required: NOTES: (i) The Contractor should furnish calculations and detailed drawing for exhaust piping sizing for approval by the Consultant prior to installation. The system should meet the performance of the engine without exceeding the back pressure limit prescribed by engine supplier without exceeding the back pressure limit prescribed by the Engine supplier. 250mm dia exhaust pipe-5.2 mm
Designing, supplying, erecting and commissioning MS structural support with suitably sized angles/channels etc. to carry the 200 mm dia, 250 mm dia,300 m dia & 350 mm dia exhaust pipes at a suitable height above the building ( to exhaust gases 30 m above ground level ), along with 125/100 mm dia cooling water pipes and associated cabling etc. including all cutting, welding and painting with two coats of red-oxide primer and two coats of silver paint as per approved drawing and design data.
POMERA AND CO LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .