| Sl No | Description | Qty | Unit | M/S SHAKTI TRADERS L1 | M/S DURGA TRADERS L2 |
|---|---|---|---|---|---|
| 1.00 | Designing, providing, fixing, testing and commissioning of GASEOUS CHLORINATION SYSTEM having capacity upto 2000 grams/ hrs. as designed having the control of gas upto 20th part of max. dose.( Supreme Technology/ Enchlor/Grouptech Industries) The complete system consists of (a) Vacuum regulator (b) Measuring Glass Tube (c) Ejector (d) PF tubing (e) Spanner with cylinder opening key (f) Ammonia Gas (Liquid for leaking test) (g) 1` dia PVC pipe with PVC fitting, ball valves etc. (h) 2 Nos. chlorine gas cylinder capacity 100 Kg. duly certified and approved by BIS and Explosive Department Govt. of India (i) Electronic Chlorine gas leak detector with sensor and hooter (j) Full face mask with canister and all other works contingent thereto and make Grouptech industries, supreme technologies, enclor. | 4 | Each | 5,40,000 ₹21,60,000 Lowest | 5,61,600 ₹22,46,400 |
| 2.00 | Designing, providing, fixing, testing and commissioning of AUTO-SHUT OFF VALVE ( Make Deep Automation/Supreme Technology/ Grouptech Industries.) | 8 | Each | 90,000 ₹7,20,000 Lowest | 93,600 ₹7,48,800 |
| 3.00 | Designing, providing, fixing, testing and commissioning of VACUUM-OPERATED AUTOMATIC SWITCHOVER SYSTEM .(Supreme Technology/ Enchlor/ Grouptech Industries) | 4 | Each | 5,20,000 ₹20,80,000 Lowest | 5,40,800 ₹21,63,200 |
| 4.00 | SUPPLYING INSTALLATION TESTING and COMMISSIONING OF THE ALAKALI BASED/WET SCRUBBER MEDIA (LEAK ABSORPTION SYSTEM HAVING FOLLOWING SPECIFICATION:-
Application- Liquid chlorine gas (Wet Scrubber system) to neutralized Leakage of chlorine gas),
Leak Detection- Through leak detection sensor,
Flow- 450 CMH, Head- 300 Mm WC, Power Supply- 440 volt AC 50 Hz Three Phase) , Blower Internal (MOS)- MS plus FRP Lining, Moter Insulation- F, Moter Rating- 2830 RPM, Manual Override- Provided, Control Panel- 3 Phase/Single Phase, Chlorine Sensor- Single, Absorption tank- FRP, Pipe line- PVC/ UPVC/CPVC, Blower Coating- FRP, Hood Covering- FRP, Chemical reaction- Neutralization of chlorine gas by reaction of chlorine gas in alkali, Media- NAOH Media, System- Automated, Auto Detector- Auto, Hooter- Auto, Designed to absorb chlorine gas- 150 Kg liquid chlorine gas in the ovent of leakage from Cylinder, Special Engineered- Dry Media, Make- Supreme Technology/ Group Tech Industries (Including Contractor Profit) | 1 | Each | 9,00,000 ₹9,00,000 Lowest | 9,30,600 ₹9,30,600 |
| 5.00 | SUPPLYING INSTALLATION TESTING and COMMISSIONING OF ONLINE CHLORINE ANALYZER SYSTEM HAVING FOLLOWING
TECHNICAL SPECIFICATIONS:- Item Description- Chlorine
analyzer, Application- drinking water, Input- Through chlorine
content sensor, Material Specification- Sensor is placed in a
measurement cell (flow cell), Electrical Connection- Cable/Screw/Terminal/Connector, Ambient Temp-min 10 degree C max. and 55 Degree C, Storage Temp- 10 to 65 Degree C, Measuring rage- 0-20 PPM, Mounted- Wall mounted Glass flow cell, Cable length- As required at site, Screen- LCD Display, Data communication- RS 405 (Modbus plus RTU), Parameters- Multiple, Output type- 420 MA Rs. 485 (one no. relay output, 2 Nos. relay out put (optional), Working- Manual or Auto, Communication function Auto- Photo electric Isolation 4-20 A current output , Power off protection- Yes, Watch dog function- Yes, Simultaneous Display- Multiple Parameters, Sensor Type- Chlorine, Accuracy- 1 plus % or (0-01 Mg/liter Glass flow cell, Power- 5 V, 12, 24 volt/230 volt AC, Protection- IP 65 or 68, Components- High Quality, Mounting type- Panel mount, Make Cimcon/ Enchlor/ Supreme Technologies.
SUPPLYING INSTALLATION TESTING and COMMISSIONING OF ONLINE TURBIDITY METER AND CHLORINE ANALISER SYSTEM HAVING FOLLOWING TECHNICAL SPECIFICATIONS:- Item Description -
Turbidity Sensor, Application- analysis of drinking water, Input- Through chlorine content sensor, Material Specification- Sensor is placed in a measurement cell (flow cell), Electrical Connection- Cable/Screw/Terminal/Connector, Ambient Temp-min 10 degree C max. and 55 Degree C, Storage Temp- 10 to 65 Degree C, Measuring rage- 0-400 NTU, Mounted- Wall mounted Glass flow cell, Cable length- As required at site, Screen- LCD Display, Data communication- RS 405 (Modbus plus RTU), Parameters- Multiple, Output type- 420 MA Rs. 485 (one no. relay output, 2 Nos. relay out put (optional), Working- Manual or Auto, Communication function- Auto Photo electric Isolation 4-20 A current output, Power off protection- Yes, Watch dog function- Yes, Simultaneous Display- Multiple Parameters, Sensor Type Turbidity in water Accuracy- 1 plus % or (0-01 Mg/liter Glass flow cell, Power- 5 V, 12, 24 volt/230 volt AC, Protection - IP 65 or 68, Components- High Quality, Mounting type - Panel mount, Make Cimcon/ Supreme Technologies, | 1 | Each | 3,50,000 ₹3,50,000 Lowest | 3,60,400 ₹3,60,400 |
| 6.00 | Supply of empty chlorine gas cylinder/ tonner of specification are as under:- Code of Construction ASME section VIII Div. 1 2004
Including Addenda 2005 Type of Construction Fusion Welded
Welding process and Rod SAW-F6PO-EM12K and E7P2-EH14 SMAW – Electrode E7018 Design Pressure and 20.63 kgf/cm2 (g) Temperature 650 C Minimum nominal shell 12 mm Wall thickness Head 10.2 (crown portion), 9.5 (other portion) / 12 mm Material specification Shell/ SA 516 Grade 60
Head
W. Cap. 780 Kg
Cl2 Cap. 930 Kg.
Tare C9wt. 632 Kg.
Gross Weight 1562 Kg.
Size 760 mm inside Dia. meter and 2090 mm long
Water capacity 780 Kg.
Valve 2 Nos.
Safety Valve 1 No.
Cap 1 No.
Filling permission issued by exclusive deptt. Govt. of India at Nagpur | 6 | Each | 3,00,000 ₹18,00,000 Lowest | 3,10,200 ₹18,61,200 |
| 7.00 | Breathing apparatus with PP Kit with mask etc. complete in all respect | 1 | Each | 1,00,000 ₹1,00,000 Lowest | 1,00,400 ₹1,00,400 |
| 8.00 | Supply of liquid chlorine gas filled in 900 kg. tonner for a period of one year | 10,800 | Kg. | 65 ₹7,02,000 Lowest | 68 ₹7,34,400 |
| 9.00 | Supply and installation of 5 KVA inverter for emergency work i.e. chlorine gas leak and necessary fittings complete in all respect. | 1 | Each | 3,00,000 ₹3,00,000 Lowest | 3,10,200 ₹3,10,200 |
Tender Value
₹80.6 L
EMD Value
₹1.6 L
Closing Date
28 Feb 2026, 5:00 pmClosed
Sandeep Dahiya
DIV Faridabad
Providing and fixing of gaseous Chlorination system Designing, testing and commissioning of online analyzer for turbidity and chlorine, vacuum operatedautomatic switchover, chlorine gas dry media scrubber, etc in sec56-56A and sec62 fbd
2026_HBC_503517_1
202630356CB7 7835 436C 8CB5 CB519AC056F5248HSV
Open Tender
Civil Works
Works
90 days
Faridabad (MC)
as per dnit
2 documents required · 2 mandatory
₹2,000
₹1.6 L
Yes
25 Mar 2026
18 Feb 2026
2 Mar 2026
18 Feb 2026
28 Feb 2026
18 Feb 2026
18 Feb 2026 - 20 Feb 2026
Designing, providing, fixing, testing and commissioning of GASEOUS CHLORINATION SYSTEM having capacity upto 2000 grams/ hrs. as designed having the control of gas upto 20th part of max. dose.( Supreme Technology/ Enchlor/Grouptech Industries) The complete system consists of (a) Vacuum regulator (b) Measuring Glass Tube (c) Ejector (d) PF tubing (e) Spanner with cylinder opening key (f) Ammonia Gas (Liquid for leaking test) (g) 1` dia PVC pipe with PVC fitting, ball valves etc. (h) 2 Nos. chlorine gas cylinder capacity 100 Kg. duly certified and approved by BIS and Explosive Department Govt. of India (i) Electronic Chlorine gas leak detector with sensor and hooter (j) Full face mask with canister and all other works contingent thereto and make Grouptech industries, supreme technologies, enclor.
Designing, providing, fixing, testing and commissioning of AUTO-SHUT OFF VALVE ( Make Deep Automation/Supreme Technology/ Grouptech Industries.)
Designing, providing, fixing, testing and commissioning of VACUUM-OPERATED AUTOMATIC SWITCHOVER SYSTEM .(Supreme Technology/ Enchlor/ Grouptech Industries)
SUPPLYING INSTALLATION TESTING and COMMISSIONING OF THE ALAKALI BASED/WET SCRUBBER MEDIA (LEAK ABSORPTION SYSTEM HAVING FOLLOWING SPECIFICATION:- Application- Liquid chlorine gas (Wet Scrubber system) to neutralized Leakage of chlorine gas), Leak Detection- Through leak detection sensor, Flow- 450 CMH, Head- 300 Mm WC, Power Supply- 440 volt AC 50 Hz Three Phase) , Blower Internal (MOS)- MS plus FRP Lining, Moter Insulation- F, Moter Rating- 2830 RPM, Manual Override- Provided, Control Panel- 3 Phase/Single Phase, Chlorine Sensor- Single, Absorption tank- FRP, Pipe line- PVC/ UPVC/CPVC, Blower Coating- FRP, Hood Covering- FRP, Chemical reaction- Neutralization of chlorine gas by reaction of chlorine gas in alkali, Media- NAOH Media, System- Automated, Auto Detector- Auto, Hooter- Auto, Designed to absorb chlorine gas- 150 Kg liquid chlorine gas in the ovent of leakage from Cylinder, Special Engineered- Dry Media, Make- Supreme Technology/ Group Tech Industries (Including Contractor Profit)
SUPPLYING INSTALLATION TESTING and COMMISSIONING OF ONLINE CHLORINE ANALYZER SYSTEM HAVING FOLLOWING TECHNICAL SPECIFICATIONS:- Item Description- Chlorine analyzer, Application- drinking water, Input- Through chlorine content sensor, Material Specification- Sensor is placed in a measurement cell (flow cell), Electrical Connection- Cable/Screw/Terminal/Connector, Ambient Temp-min 10 degree C max. and 55 Degree C, Storage Temp- 10 to 65 Degree C, Measuring rage- 0-20 PPM, Mounted- Wall mounted Glass flow cell, Cable length- As required at site, Screen- LCD Display, Data communication- RS 405 (Modbus plus RTU), Parameters- Multiple, Output type- 420 MA Rs. 485 (one no. relay output, 2 Nos. relay out put (optional), Working- Manual or Auto, Communication function Auto- Photo electric Isolation 4-20 A current output , Power off protection- Yes, Watch dog function- Yes, Simultaneous Display- Multiple Parameters, Sensor Type- Chlorine, Accuracy- 1 plus % or (0-01 Mg/liter Glass flow cell, Power- 5 V, 12, 24 volt/230 volt AC, Protection- IP 65 or 68, Components- High Quality, Mounting type- Panel mount, Make Cimcon/ Enchlor/ Supreme Technologies. SUPPLYING INSTALLATION TESTING and COMMISSIONING OF ONLINE TURBIDITY METER AND CHLORINE ANALISER SYSTEM HAVING FOLLOWING TECHNICAL SPECIFICATIONS:- Item Description - Turbidity Sensor, Application- analysis of drinking water, Input- Through chlorine content sensor, Material Specification- Sensor is placed in a measurement cell (flow cell), Electrical Connection- Cable/Screw/Terminal/Connector, Ambient Temp-min 10 degree C max. and 55 Degree C, Storage Temp- 10 to 65 Degree C, Measuring rage- 0-400 NTU, Mounted- Wall mounted Glass flow cell, Cable length- As required at site, Screen- LCD Display, Data communication- RS 405 (Modbus plus RTU), Parameters- Multiple, Output type- 420 MA Rs. 485 (one no. relay output, 2 Nos. relay out put (optional), Working- Manual or Auto, Communication function- Auto Photo electric Isolation 4-20 A current output, Power off protection- Yes, Watch dog function- Yes, Simultaneous Display- Multiple Parameters, Sensor Type Turbidity in water Accuracy- 1 plus % or (0-01 Mg/liter Glass flow cell, Power- 5 V, 12, 24 volt/230 volt AC, Protection - IP 65 or 68, Components- High Quality, Mounting type - Panel mount, Make Cimcon/ Supreme Technologies,
Supply of empty chlorine gas cylinder/ tonner of specification are as under:- Code of Construction ASME section VIII Div. 1 2004 Including Addenda 2005 Type of Construction Fusion Welded Welding process and Rod SAW-F6PO-EM12K and E7P2-EH14 SMAW – Electrode E7018 Design Pressure and 20.63 kgf/cm2 (g) Temperature 650 C Minimum nominal shell 12 mm Wall thickness Head 10.2 (crown portion), 9.5 (other portion) / 12 mm Material specification Shell/ SA 516 Grade 60 Head W. Cap. 780 Kg Cl2 Cap. 930 Kg. Tare C9wt. 632 Kg. Gross Weight 1562 Kg. Size 760 mm inside Dia. meter and 2090 mm long Water capacity 780 Kg. Valve 2 Nos. Safety Valve 1 No. Cap 1 No. Filling permission issued by exclusive deptt. Govt. of India at Nagpur
Breathing apparatus with PP Kit with mask etc. complete in all respect
Supply of liquid chlorine gas filled in 900 kg. tonner for a period of one year
Supply and installation of 5 KVA inverter for emergency work i.e. chlorine gas leak and necessary fittings complete in all respect.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.91 MB
BOQ_582207.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .