Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L 1₹24.3 LAccepted-AOC 172 SHANIWAR PETH TRIMBAKESHWAR SOCIETY OFF SHANIWAR WADA PUNE 411030 PUNE CITY MAHARASHTRA 411030 INDIA | PUNE | MAHARASHTRA | 411030 | L 1 | Accepted-AOC L 1 | |
| 2 | L 2₹24.5 L+₹14,448 (0.59%)Rejected-Finance | L 2 | Rejected-Finance L 2 |
Tender Value
₹27 L
Closing Date
12 Oct 2021, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Chief Engineer (EMIT)
3rd Floor, V.S. Bhavan, Anushaktinagar, Mumbai - 400094
Design, supply, installation, testing and commissioning of Solar Water Heating System for Niyamak Bhavan C building at Anushaktinagar, Mumbai.
2021_DCSEM_649093_1
DCSEM/CQD/QSC/ AERB-C-Solar/NIT/15/21-22 dtd 20.0
Open Tender
Machineries/ Mechanical Engg Items
Works
180 days
Anushaktinagar
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
Exempted
12 Oct 2022
21 Sept 2021
14 Oct 2021
21 Sept 2021
12 Oct 2021
1 Oct 2021
21 Sept 2021 - 30 Sept 2021
150 days
Amount
GENERAL ABSTRACT
PART A : MECHANICAL WORKS
PART B : ELECTRICAL WORKS.
Description of Work / Item(s)
Amount
PART-A: Supplying, storing, handling, erecting, testing and commissioning of solar water heating system complete with collector (Flat plate collectors with storage tank) including collector support stands (MS structural supports for the collectors shall be hot dip galvanized sections), heat absorbers designed structure support, painting complete, SS valves with solar panels, pressure & temperature gauges, capable of specified heat transferring capacity copper thermic fluid pipe clamps, hanger etc. with suitable installation and expansion bellows of suitable temp /pressure rating (from heat storage tank to solar panels),testing of thermic fluid pipes clamps. Interlocked with mixing tank to ensure complete automatic control in all respects with control panel. System shall have built in air venting and anti-oxidant system as directed by Engineer-in-Charge. i)The storage tank shall be suitable for working pressure of 3.0 Kg/cm2. The storage tank shall be of 1000 litre capacity including all civil PCC support, structural supports for the tanks shall be hot dip galvanized sections etc. ii) The Solar water heater tank shall be provide suitable heating System with electric heater coil for hot water even on rainy/cloudy days as directed by Engineer-in-Charge.
Supplying & fixing on exposed surfaces the following sizes uv-stabilized Chlorinated Poly Vinyl Chloride (CPVC) pipes & Fittings of specified class consisting of following items of work: i) Supplying CPVC pipes and CPVC plain / brass threaded fittings, SDR - 11 having thermal stability for hot & cold water supply conforming to IS 15778 with ISI mark / equivalent approvals as per relevant standards as directed by Engineer-in-Charge. ii) Laying and fixing the pipe and specials on exposed surfaces / underground, to correct line, level and plumbfor water supply line, using metal straps (on wall surfaces) at 1.0 mtr interval or as directed by the EIC. iii) Jointing the pipes and specials using solvent cement conforming to IS 15225 & Teflon tape ( For threaded joins ) of approved makes including cutting the pipe to required size, preperation of surfaces, necessary tools etc. all complete as directed by Engineer-in-Charge. iv) Cutting or making hole or chases in RCC or brick work structure such as wall, column, beam, slab, chajja,dado etc. for passing the pipe line and reinstating all the damage to its original condition and as directed by Engineer-in-Charge. v) Testing the pipe line to a hydraulic pressure of 10 Kg / Sq.cm for leak proof joints. vi) Nipples, specials.
Providing and fixing Pipe thermal insulation for exposed hot water CPVC pipes of following dia, insulation tubing thickness of 9 mm with lamination of Aluminium foil / UV barrrier film of INSUshield brand of Supreme using tubing manufactured using UV resistant materials of folowing Make and dia of pipe on which it is to be provided. All pipe joints are to be isulated properly using same material in the appropriate form and as directed by Engineer-in-Charge.
Providing and Fixing CPVC- Ball valve with SS ball of Approved make suitable for pipe pressure class of approved make with material and labour, making water proof joints, including cost of jointing material and PPR specials if required & testing the joints. etc complete as per directions of engineer-in-charge.
Providing and Fixing Ball Valve as per relavent IS suitable for pipe pressure class with body of bronze and ball & stem of Stainless Steel of approved make with fittings & material for conectivity and labour, making water proof joints, including cost of jointing material and CPVC specials if required & testing the joints. etc complete as per directions of engineer-in-charge.
50 mm for CPVC pipe
Providing and fixing of CI wafer type check valve with flanges,Nut,bolts & washers,painting etc complete as directed by Engineer-in-Charge.
Providing fixing dial type (100 mm) pressure gauge with isolation valve suitable for working pressure of 250 psi cost shall be inclusive of providing any short piece,nipples,elbows etc as directed by Engineer-in-Charge.
Providing and fixing temprature Gauges with isolation valve suitable for system temperature as directed by Engineer-in-Charge.
Supplying and fixing of 25 mm dia Air release valve etc. complete as directed by Engineer-in-Charge.
G.I. Pipe for hot Water with insulation: Supply, Installation, testing & commissioing of galvanised Iron Heavy Class G.I. pipe conforming to IS 1239 (part-I) with galvanised mild steel fittings conforming to IS 1239 (part-II), laying pipes in proper level and gradient. i) The piping installation has to be put to hydraulic test to 1.5 times Working pressure before applying paint or pipe coating and wrapping etc. ii) Making threaded / flanged joints including providing flanges, nut bolts, gaskets shall be considered in the scope of the bidder. iii) MS Supports, clamps, anchor, fastners etc. required for installation GI-pipes, is inclusive in this item's rate. No separate measurement shall be made for these. iv) PCC Blocks required for GI-pipes supports shall be measured as per SOQ item no. 10 v) GI Pipe insualtion : To protect the external piping of solar hot water system is to use an aluminum jacketing over either fiberglass or iso foam insulation. bottom.
80 dia GI Pipe (Heavy Class as per IS-1239)
65 dia GI Pipe (Heavy Class as per IS-1239)
50 dia GI Pipe (Heavy Class as per IS-1239)
32 dia GI Pipe (Heavy Class as per IS-1239)
NIPPLES: Providing and fixing Nipples of required size to be connected from exisitng GI pipes to GI / CPVC pipes after making holes at appropriate places wherever required and welding the nipples to the GI pipes and the other end with threaded portion to be connected to the GI / CPVC pipes, complete in all respects as per drawings, specifications and the instruction of EIC.
GATE VALVES: Supply, installation, testing and commissioning of double flanged CI gate (sluice) valves of required sizes of ratings PN 1.6 with non rising stem conforming to IS-14846 with all necessary fittings like flanges, neoprene gaskets, nut bolts, hardware, flange joint etc. as per drawings, specifications and as directed by E-I-C.
80 mm dia.
40 mm dia.
MS Supports: Fabrication, supply and installation of MS support as required but not covered under specific items as per drawings, specifications and as instructed by E-I-C. Material shall conform to IS-2062.
PCC Work: Providing PCC supports for headers and underground pipelines of required sizes with cement morter 1:2:4 with curing etc, all complete as per specifications, drawings and as directed by E-I-C.
Description of Work / Item(s)
Amount
PART-B: LT Cabling, Jointing, Termination & Earthing and connected works: L.T Cables : Supply, installation, testing & commissioning of 1.1 KV gradealuminium/ Cu stranded circular/ sectorshape core conductor with PVC/XLPEinsulation, extruded PVC innersheathed, G.I flat strip/wire armoured,extruded FRLS grade antirodent & antitermite PVC (ST-2)outer sheathedcable conforming to IS : 1554 Part I / IS7098 Part-I with latest amendments, fixed on wall/column/slab/false ceiling/ existing cable tray /existing humepipe/trench/ shaft/pit/ on 5mm thickM.S. flat /GI spacer/angle/ support fixed with coach screws/grouted inwall/anchor fasteners 2mm. thick G.I.fabricated saddle, all fixingaccessories, etc complete including painting of M.S spacers/angles and saddles or in ground at a - depth of 900 mm below ground level (cost of excavation shall be measured seperately under item no. 4.0 of Section-XXIII ) , sand bedding, laying of baked bricks on side & top, temporary reinstatement, back filling, dewatering, consolidation, disposal of excess earth within the radius of 500 m and making good to the original finir venting and anti-oxidant system as directed by Engineer-in-Charge. Note: 1) Colour shade for DB's shall be as follows : DB's fed from normal/DG power supply - RAL 7032, 2) MCBs (Type -C) shall be minimum 10 KA/25 KA breaking capacity, as specified, 3) Blanking plates shall be included inscope of work, 4) DB shall be of standard ready made type from approved manufacturers as indicated in preferred makes of as directed by Engineer-in-Charge.
3.5C x 120 sq.mm Al conductor cable
4C x 6 Sq.mm Copper conductor cable
LT Cables End Joints :End jointing of following sizes of cable bycrimping with supply of all jointingmaterials like solderless tinned coppercable socket,double compression brasscable glands, gland earthing, insulationtape, flux, duplicate interconnectionbetween gland earthing strip & to thenearest earthing bus terminals as per thedrawings, specifications and as per theinstructions of the Engineer-in-charge.
3.5C x 120 sq.mm Al conductor cable
4C x 6 Sq.mm Copper conductor cable
Tinned copper/ GI earth wire/earth stripfixed on wall/side of trench/slab /column/beam/ shaft connection topanel/DBs/SFU's etc. with 5mm thick G.I.Spacers & 2mm thick G.I. Saddle inground at 750 mm below includingexcavation in ground with protectivebaked bricks, excavation in ground,refilling & removal of excess earth within aradius of 500 m, temporary instatement &back filling of trench, consolidation,interconnection of earth strip/wire withbrass bolt & nuts & washers & solderjointing, painting with two coats of black bituminous paint for earth wire/ strip inground & green enamel paint for earthwire /strip on surface etc. as directed by Engineer-in-Charge.
25 X 6 mm GI strip
10 SWG tinned Cu earth wire
MAIN DISTRIBUTION BOARDS : Supply, installation, testing &commissioning of following readymadedistribution boards, double door, IP-55 degree protection complete withnecessary, MCCB , MCBs, earthleakage circuit breaker (ELCB) etc. including interconnections with appropriate capacity size of PVC insulated copper conductor wires (ISImarked),suitable for concealed mounting/wall mounting with MS frame work of 40 x40 x 5 mm MS angle iron, with M.S.enclosure fabricated out of min 18 SWG/20SWG thick M.S. CRCA sheet as per manufacturers standard, with concealedhinged door, locking arrangement etc.including earthing clamps for both incoming & outgoing circuits,interconnections, per phase isolation kitas required,cable end box & wire way box if required, continuous copper earth wire in the wire way box with single/duplicate brass earthing terminals, danger board, name plate, flexible earthing for the door,metal treatment & powder coated painting, Phase Distribution drawing etc. all as per drawings (G.A. & fabrication drawing venting and anti-oxidant system as required by Clint/Consultant with following capacity as directed by Engineer-in-charge. Colour shade forDB's shall be as follows: 1. DB's fed from normal power supply - RAL 7032Note:1.MCBs (Type –C) shall be minimum 10 KA /25 KA breaking capacity, as specified. 2. Blanking Plates shall be included inscope of work. 3. DB shall be of standard readymade type from approved manufacturers as indicated in preferred makes of material. 4. Routine tests will be conducted atfactory as per relevant IS. 5. The DB shall be complete withnecessary tinned Copper busbars, interconnections, separate earth bus & separate neutral bus for each phases. 6. All Distribution boards doors are lockable with master sets of key each separate block as directed by Engineer-in-Charge.
VTPN DB - 8 Way :The double door type 8 Way VTPN MCCBDB comprising of the following :a) 160 A FP, 16 kA MCCB -- 1 No.b) 16-32 A FP MCB -- 8 nos
16 A, FP RCBO-300mA
GREENSENSE ENERGY SYSTEM PVT.LTD
GREENSENSE ENERGY SYSTEM PVT.LTD
skylark thermal energy systems
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .