| 1 | L1₹36.9 LAccepted-AOC VILLAGE CHANNI POST OFFICE SATTANI DISTT UDHAMPUR UDHAMPUR UDHAMPUR JAMMU KASHMIR 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L1 | Accepted-AOC Being Lowest Bidder | |
| 2 | L2₹39.7 L+₹2.9 L (7.77%)Rejected-AOC NEAR INDUSTRIAL ESTATE THANDA PADDAR UDHAMPUR J K 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L2 | Rejected-AOC 2nd Lowest Bidder | |
| 3 | L3₹41.5 L+₹4.6 L (12.4%)Rejected-AOC WARD NO 16 HOUSE NO 66 SALLIAN TALAB UDHAMPUR 182 101 J K | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L3 | Rejected-AOC 3rd lowest bidder |
Tender Value
₹39.0 L
EMD Value
₹78,000
Closing Date
25 Dec 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE(Army) Dhar Road
GE(Army) Dhar Road
CERTAIN EM SANCTIONED WORKS AT DHAR ROAD UNDER GE ARMY DHAR ROAD
2023_MES_627202_1
8069/NIT-60/2023-24
Open Tender
Civil Works
Item Rate
270 days
GE(Army) Dhar Road
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE(Army) Dhar Road
₹78,000
Yes
12 Mar 2024
7 Nov 2023
27 Dec 2023
8 Nov 2023
25 Dec 2023
12 Dec 2023
Amount
Material and labour for Point wiring complete (for simple and modular type ) with 1.5 sqmm single core PVC insulated heavy duty ISI Marked,FRLS unsheathed cable 1100 volts grade with multistranded copper conductor drawn through and including PVC white non metalic PVC conduit heavy duty not less than 20mm dia with all accessories like tee, straight joint, L Bend etc.,concealed on walls, sufrace on ceiling/ floors etc., and including provision of PVC heavy duty Insulated FRLS copper conductor, 1.5 sqmm for earth continuity conductor and connected to common earth dolly, including suitable size of sheet metal modular sunken box 1.2mm thick fixed and flushed inside the walls, with 3mm thick laminated sheet top cover for housing the switches, socket outlets, fan regulators etc., for the following:-
One light / Exhaust Fan/Ceiling fan & One Bell/buzzer point controlled by one switch.
Material and labour for Point wiring complete with 2 run of 2.5 sqmm single core PVC insulated heavy duty ISI Marked , unsheathed cable 1100 volts grade with multistranded copper conductor drawn through and including suitable size of PVC white non metalic conduit with all accessories like tee, straight joint, L Bend etc., concealed on wall surface on ceiling / roofs etc., and including provision of PVC insulated heavy duty ISI Marked unsheathed copper conductor 1.5 sqmm for earth continuity conductor and connected to common earth dolly, including suitable size of sheet metal box 1.2mm thick fixed and flushed inside the walls, with 3mm thick laminated sheet top cover for housing the switches/socket outlets 15 Amps.
Material and labour for sub main wiring with two single core PVC insulated unsheathed copper conductor cable 6 sqmm drawing in and including rigid non metalic PVC heavy duty 25 mm dia conduit concealed on wall/surface on ceiling with one additional PVC wire of copper conductor of 6 sqmm for earth continuity conductor incl taking down old Unsv submain any type and size and making good the disturbed surface complete all as specified and directed by EIC.
Supply and fixing LED flood light not less than 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp
Material and labour for fixing or passing through pipe, laid in trenches or fixed to pole/wal or fixed to LT panel board, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape, armoured with galvanised steel wire or tape and overall PVC sheathed 16 Sqmm 2 core with required aluminium cable lugs all as specified and directed.
Supply and Fixing LED tube light not less than 20 Watt light fitting integral sleek design extruded polycarbonate LED Channel with white acrylic cover and including twin core twisted flexible copper conductor cable with suitble size complete with all accessories all as specified and directed by Engr-in-Charge.
Supply and fixing Ceiling Fan Brush lerss direct current (BLDC type)" min air delivery not less than 210 cubic meter per min, B star rating 5 power consumption not more than 35W, RPM not less than 340 an AC single phase 230 volts for size 1200 mm sweep, including fixing arrangement such as nut, bolts, washer etc, complete with Fan box & all other accessories compatible to fan regulator complete all as specified & directed by Engineer Incharge.
Supply and fixing of building security LED fitting not less than 30/35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection including GI pipe brackets all as directed by EIC
S & F ceiling rose Ceiling rose, 3 phase/PVC/polycarbonate, isolated body all as specified and directed.
Supply and fix fan speed regulator, electronic step type, suitable for single phase AC, 240 volts, 50 Hz, all as specified and as directed.
Supply and fixing Switch , single pole, one way 5 Amp 230 Volt ISI Mark complete all as specified and directed
Supply and fixing socket outlet 16 Amp 230 volt ISI Mark complete all as specified and directed
Supply and fixing switch , single pole, one way 16 Amp 230 volt ISI Mark complete all as specified and directed
Supply & Fixing SPN Distribution Box, double door of protection grade IP 42 in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 8 way, confirming to IS 13032 & 8623 complete all as specified and directed.
Supply & Fixing SPN Distribution Box, double door of protection grade IP 42 in fine powder coated, matt finish with best CRCA sheet, fitted with shrouded neutral, insulated pin type copper bus bar, Din rail, earth bar of 4 way, confirming to IS 13032 & 8623 complete all as specified and directed.
Supply & Fixing MCB SPN, 32 to 63 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed.
Supply & Fixing MCB SP, 06 to 40 Amps 240 volts, AC , 10 KA breaking capacity 'C' Series,"ISI marked and conforming to IS 8828/IEC 60898-1 complete all as specified and directed.
M&L as in repair for earthing as per IS:3043 with galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanized iron wire 4 mm dia (8 SWG) as earthing lead protected by GI pipe medium grade 15 mm bore for protection of GI earth wire and 20 mm dia GI pipe medium grade for watering with alternate layers of charcoal /coke and salt including all accessories like nut, bolts, reducer, nipple, wire meshed/screened funnel and making brick masonry finished chamber of internal size 300 mm x 300 mm x 300 mm with concrete base, covered with PCC cover which shall be embedded in the block masonry including excavation works, refilling, connected to main switch/MCB DB for feeding the electric supply to domestic quarters compete all as specified as shown in electricall plateNo. 3 of SSR Part-I and testing of earth resistance as required. Note : Earthing lead/G.I.Earth wire upto 7.5 metre length shall be deemed to be included in quoted unit rate
Supply and fixing LED security light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum housing ,impact and corrosion resistant complete with heat resistant glass/PVC cover , duly fitted with DC driver, LEDs,heat sink for thermal management , PVC Connector etc equipped with IP 65/66 protection complete all as specified & directed by Engr Incharge.
S&F Bracket made out of galvanised steel tubing light grade of size 40mm bore, not less than 1.2 mtr long, bent to shape at an angle of 120 degree as per requirement with 02 Nos mild steel clamps made out of 25mm x 4 mm flat iron complete with suitable size nuts, bolts and washers etc & painting with two coats of synthetic enamel aluminium paint over a coat of red oxide primer incl fixing on pole complete all as specified and directed by Engr Incharge.
S&F SMC junction box of size 250mm x 200mm x 105mm size outdoor type, weather proof, shock/rust proof,termite resistant, fire retardant,made out of PVC sheet not less than1.8 mm thick with front side hinged, having locking arrangement with nuts , bolts & washers complete having arrangement for entry & exit of incoming and out going cables/wires etc complete comprising of the followings complete all as specified & directed by Engr Incharge. :- (a) Bus bar with two aluminium strips, 100 Amps capacity mounted insulators, including PVC wires of suitable size from bus bar to MCB (b) MCB SPN 6 to 32 Amps - 01 No (c) Clamps made out of 25mm x 3mm flat iron duly fixed with nuts & bolts.
M&L for Supply/Erecting and fixing of steel tubular swaged pole 410SP31 (9.00 Mtr long in true vertical position) with base plate welded at bottom & finial plug welded at top including 2 coats of black bituminious paint up to planting depth and remaining exterior portion of pole with two coat of aluminium paint over a coat of red oxide primer all as specified and directed by Engr Incharge at site. NOTE - Excavation and Earth work and PCC in foundation shall be measured and paid seprately.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 2 core
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core
S&F sheet metal enclosure feeder panel made out of 3.15 mm thick CRCA sheet with powder coated paint (CPRI approved) double door outdoor type including solid aluminium bus bar of capacity 100 Amp 4 Nos strip with locking arrangements, enclosure box to be fixed on plinth foundation 1:2:4 and 900 mm above ground level including MS angle/ channel consisting of necessary fixing arrangements for incoming & out going cables with cable glands, lugs, nut, bolts, washers and fixing arrangement , PCC work including necessary flat iron clamps with nuts, bolts & washers and all as specified and directed.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed laid on pole from junction box to light fitting on pole one twin core cable flat or circular cables 1.0 Sqmm aluminium stranded conductor all as specified and directed
M&L for earthing as per IS:3043 with galvanized steel earth plate electrode 600 x 600 x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level welded to galvanized iron strip of size not less than 30mm X5 mm as earthing lead including tarring of welded area protected by GI pipe medium grade 50mm bore for protection of GI earth strip and 20 mm dia GI pipe medium grade for watering with alternate layers of charcoal /coke and salt including all accessories such as nut, bolts, washers , nipple, wire mesh/screen funnel etc and making brick masonry finished chamber of internal size 300 mm x 300 mm x 300 mm with concrete base, covered with PCC cover including excavation works, refilling, connected to main switch/MCB DB for feeding the electric supply to domestic quarters compete all as specified as shown in electrical plate No. 3 of SSR Part-I completeincluding testing of earth resistance complete all as specified & directed by engr-in-charge.
Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter in deep getting out in hard/dense soil for stay assembly/laying of cable/errection of poles etc complete all as specified and directed.
All as per item No. 11 above but depth exceeding 1.5 m and not exceeding 3 m complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25cm thick.
Removing of excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point.
PCC (1:4:8) type D-2 using 40mm graded aggregate as in foundation for filling in, mass concrete for foundation of Pole, Transformer, Panel board, stay, post top lantern, repairs to road cutting, drain, path etc complete all as specified and directed.
PCC (1:3:6) type C-2 using 40mm graded aggregate as in foundation for filling in, mass concrete for foundation of Pole, Transformer, Panel board, stay, post top lantern, repairs to road cutting, drain, path etc complete all as specified and directed.
PCC (1:2:4) type B-1 using 20mm graded aggregate as in coping of new pole / reconstruction old damaged copings etc, including necessary form work complete all as specified and directed
M & L for dry Sand cushioning in trenches for protection of cable including watering and consolidation all as specified and directed. Note: Punned thickness shall be considerd for measurment purpose
M & L for well burnt brick sub class 'B' old size laying in trenches perpendicular to axis of the cable complete all as specified and directed.
Supply and laying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 40 mm bore for protection of cable including dismantling existing pipe complete all as specified and directed by the Engineer-in-Charge.
M&L for cutting of PCC/Hard standing/WBM road not exceeding 20 cm in width not less than 30 cm in depth for passing of LT cable and making good of disturbed surfaces to match with the existing by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directedby the Engineer-in-Charge. .
S&F automatic street light controller using infrared sensor based switch for automatic switching of street lights. Switch operation should be based on natural light lux level. Required illuminance level for switching ON is ≤ 60 Lux and for switching OFF ≥ 10Lux. The sensor should also have part night operation facility of min 4 hrs to max 12hrs. The sensor along with suitable power contactor of rating 25 Amps .The enclosure shall be termite proof , FR grade SMC junction box conforming to IP66 protection.Circuit wiring min 10Sq mm stranded complete all as specefied and directed by Engr- in -charge. Make of components are as under:
S&F automatic street light controller using infrared sensor based switch for automatic switching of street lights. Switch operation should be based on natural light lux level. Required illuminance level for switching ON is ≤ 60 Lux and for switching OFF ≥ 10Lux. The sensor should also have part night operation facility of min 4 hrs to max 12hrs. The sensor along with suitable power contactor of rating 16 Amps per phase .The enclosure shall be termite proof , FR grade SMC junction box conforming to IP66 protection.Circuit wiring min 10Sq mm stranded complete all as specefied and directed by Engr- in -charge. Make of components are as under:
M & L for on surface Flame proof point wiring for One light /Fan/Bell point controlled one flame proof switch 5/6 Amp one way single pole, on wall and ceiling/ roof with necessary fixing arrangements with PVC insulated FRLS and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including rigid stove enameled steel metallic conduit not less than 20 mm dia including all MS conduit accessories/ fittings except flame proof bends, tees,junction boxes but including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.2 mm for fixing of switches / sockets, fittings,etc with MS screw and cup washers including PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing including cutting the chases and making good the surfaces by cement mortar (1:3) and for matching / finishing of new surfaces either by means of plaster of peris/ Putti or distemper / colour wash with same existing colour complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing flame proof LED light fitting not less than 16 Watt , CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable in flexible metalic conduit from fitting to junction box with suitable size complete all as specified and as directed by Engineer-in-Charge.
S&F submain wiring alongwith earth wire with 2x4.0 sq. mm + 1x4 sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed alonwith rigid steel conduit 20 mm dia complete all as specified and as directed by Engineer-in-Charge.
supply & fixing flame proof junction box 3 way made of stainless steel anti corrosive epoxy powder coated of size 100mm x50 mm IP 65 ,IS:2148-2004,Class T-6, complete all as specified and directed by Engineer-in-Charge
supply & fixing flame proof bend 20 mm dia IP 65 ,IS:2148-2004,Class T-6,complete all as specified and directed by Engineer-in-Charge
K S BUILDERS
LUXMI ELECTRONIC WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .