Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 CrAccepted-AOC | ₹3.8 Cr | L1 | Accepted-AOC AWARDED SINCE L1 |
| 2 | L2₹4.0 Cr+₹22.6 L (6.02%)Rejected-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | ₹4.0 Cr+₹22.6 L (6.02%) | L2 | Rejected-Finance REJECTED SINCE NOT L1 |
| 3 | L3₹4.5 Cr+₹71.2 L (18.9%)Rejected-Finance | ₹4.5 Cr+₹71.2 L (18.9%) | L3 | Rejected-Finance REJECTED SINCE NOT L1 |
| 4 | L4₹4.9 Cr+₹1.2 Cr (31.1%)Rejected-Finance 145H 2G AQAMA MODEL APARTMENT LUKERGANJ PRAYAGRAJ UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211001 | ₹4.9 Cr+₹1.2 Cr (31.1%) | L4 | Rejected-Finance REJECTED SINCE NOT L1 |
Tender Value
₹4.9 Cr
EMD Value
₹5.7 L
Closing Date
16 Dec 2019, 6:00 pmClosed
CE AF ALLAHABAD
HQ CE AF ALLAHABAD
CONSTRUCTION OF MAFI POWER SUB STATION AT AF STN BAKSHI KA TALAB
2019_MES_294426_1
958792/E8
Open Tender
Civil Works
Lump-sum
540 days
BAKSHI KA TALAB
AS MENTIONED IN TENDER DOCUMENTS
8 documents required · 8 mandatory
₹2,000
Yes
GE AF BKT
₹5.7 L
Yes
14 Jan 2020
2 Nov 2019
21 Dec 2019
2 Nov 2019
16 Dec 2019
30 Nov 2019
16 Nov 2019 - 23 Nov 2019
Amount
SCHEDULE A PART I (BUILDING WORKS)
Construction of Sub Station No. 1 with duty room and attached toilet with permanent specification complete all as specified and as shown on drawings.
Construction of Sub Station No. 2 with duty room and attached toilet with permanent specification complete all as specified and as shown on drawings.
Sch A Part II (INTERNAL WATER SUPPLY)
Lump sum price worked out by the contractor for Internal Water Supply as listed in Sch ‘A’ Part II .
Sch A Part III (INTERNAL ELECTRIFICATION)
Lump sum price worked out by the contractor for Internal Electrification as listed in Sch ‘A’ Part III .
Sch A Part IV (EXTERNAL WATER SUPPLY)
Lump sum price worked out by the contractor for External Water Supply as listed in Sch ‘A’ Part IV .
Sch A Part V (EXTERNAL ELECTRIFICATION)
Lump sum price worked out by the contractor for External Electrification as listed in Sch ‘A’ Part V.
Sch A Part VI ( SEWAGE DISPOSAL)
Lump sum price worked out by the contractor for sewage disposal as listed in Sch ‘A’ Part VI.
Sch A Part VII (PATH/HARDSTANDING)
Lump sum price worked out by the contractor for Path/ Hardstanding as listed in Sch ‘A’ Part VII
Sch A Part VIII (SECURITY WALL AND GATE)
Lump sum price worked out by the contractor for Security wall & gate as listed in Sch ‘A’ Part VIII
Sch A Part IX (GENERATER SHELTER)
Lump sum price worked out by the contractor for generator shelter as listed in Sch ‘A’ Part IX.
Sch A Part X (SITE CLEARANCE, EXCAVATION AND EARTH WORK)
Lump sum price worked out by the contractor for Site clearance, Excavation & Earth Work as listed in Sch ‘A’ Part X
Sch A Part XI (Miscellaneous Items of B/R and E/M)
S&F Ceiling fan 1200 mm sweep BEE 5 star rated with down rod and connecting up including provision of 3 core of 1.5 sq mm multi stranded copper conductor cable IS-694 marked from ceiling rose to fan connector and testing etc complete all as specified and directed.
S&F mettallic Exhaust fan of 300 mm sweep BEE 3 star rating (heavy duty) with double ball bearing single phase 230 V, AC, 900 RPM with louvered shutter including mounting frame, nut bolts, washers, fastners etc with suitable size hole and connecting up including provision of 3 core of 1.5 sq mm multi stranded copper conductor cable IS-694 marked from ceiling rose to exhaust fan connector and testing etc complete all as specified and directed.
S&F Exhaust fan of 450 mm sweep BEE 3 star rating (heavy duty with double ball bearing) single phase 230 V, AC, 900 RPM with louvered shutter including mounting frame, nut bolts, washers, fastners etc with suitable size hole and connecting up including provision of 3 core of 1.5 sq mm multi stranded copper conductor cable IS-694 marked from ceiling rose to exhaust fan connector and testing etc complete all as specified and directed.
M&L for cutting into existing main distribution G.I. pipe line and inserting 'Tee' of size 50 mm x 50mm x 25 mm with all connected accessories complete all as specified & directed.
M&L for Boring of holes under road,pavement hard standing by trenchless technology using ultra sound technique and necessary machine including double wall corrugated HDPE pipe of size 150mm dia suitable for 0.4Mpa working pressure complete in all respect and all as specified and directed.
Supply, laying , jointing & testing of HT XLPE cable 95 Sqmm 3 core, 11000 volt grade (earthed) screened, PVC bedded, galvanised steel strip armoured (Heavy duty) with aluminium stranded conductor ISI marked IS-7098 (Part-I) 1977 and part-II of 1985 laid in pipe / ducts/ trenches under floor and road or fixed to wall etc including taking down existing cable of any size & type etc complete all as specified & directed.(Note:- Excavation , earthwork, sand filling and brick for protection of cable to be measured & paid under respective item.)
Supply and fix cable jointing kit suitable for HT 11 KV (earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories for HT cable 95 Sqmm ,3 core XLPE, armoured, aluminium stranded conductor complete all as specified & directed.
Supply and fix cable jointing kit suitable for HT 11 KV (earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories for HT cable 95 Sqmm ,3 core XLPE, armoured, aluminium stranded conductor complete all as specified & directed.
Supply and fix cable jointing kit suitable for HT 11 KV (earthed) grade cable for straight through cold shrink type joint complete with jointing material and accessories for HT cable 95 Sqmm ,3 core XLPE, armoured, aluminium stranded conductor complete all as specified & directed.
M&L for Earthing complete with copper earth plate electrode, 600mm x 600mm x 3.15 mm thick, buried directly in the ground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to copper strip of size 25 x 3 mm as earth lead by means of bolts, nuts and washers of GI up to test point, GI tubing 40 mm bore medium grade protection pipe, GI watering pipe 20mm bore medium grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-0 (Nominal mix) cover reinforced with XPM (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-0 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing , all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed. Notes: 1. Earth lead & protection pipes length upto & including 7.50 metre. 2. Earth filling shall be done by vegetable soil. 3. Soil should be free from stone, boulders, aggregate, gravels etc.
Supply, installation, testing and commissioning of 11 KV, 630 Amps, Extensible Outdoor Fixed Type (IP64), RMU (Ring main unit) 3-way comprising of 1 No 630 Amps, Motorised Load Break Switches (Comprising One No. Incomers) & 2 Nos. Vacuum Circuit Breaker as Outgoing, inside robotically / manually welded stainless steel (Non Ferrite Non Magnetic Grade) tank having min. thickness 2 mm having IP 67 Degree of Protection. RMU should be provided with Copper busbars internal, external as well as earthing busbars should be of copper, Resin cast ring core protection CT on cables 100/1 Amp, 5P10, 2.5 VA - 3 No's. & Resin cast ring core metering CT 50/1 Amp, Cl 1.0, 2.5 VA - 3 No's. on cables, one number fault passage indicator per unit, padlock provisions & complete with all accessories. The RMU shall be type tested for Internal arc test of 20kA/1 sec as per IEC62271-200. The unit shall include the following with all necessary standard fitting as required at site. (A) 1 No 630 Amp motorised Load Break Switches triple pole, single break 3 position as incomer (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1,fully rated with earth switch, spring assisted mechanism,Red/Green Push Button for On/Off Operation, Arc proof hinged type cable cover interlocked with Earth Switch, Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95 Sqmm. (B) 2 Nos. 630 Amp Motorised Vacuum Circuit Breaker, triple pole, single break 3 position (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/Green Push Button for On/Off Operation, Arc proof hinged type cable cover interlocked with Earth Switch, Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95 Sqmm. (C ) 3O/C + 1E/F self powered relay with Low and High set for Over current and Earth Fault. Relay should have LCD (16 x 2). Relay should have facility to trip the breaker from remote commands without shunt trip coil, Last 5 Fault Record with Time stamp, battery pack replaceable from front. Transformer VCB should be provided with protection scheme for transformer faults like OTI, WTI & Buchholz's relay alaram & trip, along with annunciation & lock-out function Bus Connected PT Unit -1 No. for Metering consisting of following:-
(i) Type M: Air Insulated metering module 12KV, 630A, 20KA for 3sec. (ii) 3 Voltage Transformers of the ratio 11kV/√3 / 110 V/√3, 25 VA, Class 1 with HT fuses on primary side and MCB on secondary side. (iii) 1 Digital MFM to measure Amps,Volts,Frequency,PF,KWH,KVAR. (iii) 1 LED Illumination. (iv) 1 Space Heater with thermostat. (v) 1 RYB phase indications. (vi) 1 set Bushings for external busbar connection along with Busbar cover & Sleeved busbars for coupling. (vii) 2x12 V Battery with battery charger with suitable burden for motor operation. Input 230 V AC & Output 24 V DC. Battery make: EXIDE/HBL. (D) LED based Capacitive voltage indication fixed type VPIS 9-15 kV Necessay interclocking arrangement for safety and operations LBS shall be of ratings 12 KV, 630 A, 20 KA for 3 Sec. (E) One No. Operationg Handle for Manual Operation. (F) One No. Manometer. (G) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (H) Above switchgear shall confirm to all relevant IEC/IS Standards. (I) Manual operation of Load Break switch should be possible without dismantling the motor from RMU. The motor should be fitted in such a way that it should not be outside front covers of RMU. Coupling of RMU and Metering module should be with the help of Bolted type arrangement, so that the coupling at site shall be easy. Plug-in type bushing shall not be acceptable. (J) The Cable termination of RMU should be rear accessible only. And minimum 3 module should accommodate in one tank to avoid multiple coupling at site (K) PCC 1:2:4. type B1 using 20 mm graded aggregate for foundation of RMU as per recommendations of manufacturers of directed by EIC. Note (i) Any other parts/items not specified above but have been required essential for smooth and safe functioning of the RMU system shall be quoted rate.Make: AREVA/ L&T/SIEMENS/SCHNEIDER (ii) The RMU will be tested at site by primary injection test system and submit the test report.
Supplying, installation, testing & commissioning of 11 KV , HT panel 400 Amps ,minimum 13.10 KA Rupturing Capacity indoor insulated floor mounted, VCB switch gear with copper bus bars comprising 2 incoming, 2 bus coupler and 2 outgoing, the coupling should be at the top of panel through bolted connection & Sleeves bus bars covered with insulated boots. All live parts, bus bar , VCB will be enclosed in steel tank filled with IP class IP 67 , as per latest IEC 62271-200. Make:Siemens/Schneider/Areva/Alsthom (a) All VCB's shall be motorized with 110 V DC control voltage to operate two position double spring mechanism. Each VCB shall have green (on)/ Red (off) push buttons to operate & Live cable LED indicators through voltage dividers mounted on the bushing. (b) The earthing shall be provided in each cable compartment to provide solid earthing for the cable shield . Each VCB(except bus Coupler) incoming and outgoing shall be equipped with digital MFM to measure Amps , Volts , Frequency, PF, KWH , KVAR etc & 3 O/C +1 E/F self powered numerical protection relay with low and high set for over current and Earth Fault . Relay should have facility to display the maximum loaded phase current also. Relay shall record minimum 5 faults records with time stamping or as per manufacturer design. © The switch gear shall have built in programming logic using reputed make PLC for automatic changeover between two motorized incomer VCB & one bus coupler VCB and shall derive voltage reference from incoming supply in respective incomer. (d) PLC shall also be wired to all VCB's to monitor open/close status . The unit shall be supported with power pack of 110 Volt battery with battery charger (110 volt DC output ) for supply backup for PLC & motor operation . The unit shall include the following with all necessary standard fitting required at site. (e) TWO Nos. incomer 400 Amp VCB along with off load isolator and fault making type earthing switch. Resin cast ring dual core dual ratio type CT's 100-50/1 or 5 Protection Class 5P10- set and PT 11 KV/110 volt AC on each incoming.
(f) Two Nos. outgoing 400 Amp VCB along with off load isolator and fault making type earthing switch. Resin cast ring dual core dual ratio type CT's 100-50/1 or 5 Protection Class 5P10- & Metering 100-50/1 or 5, CI 1.0-1 sets on each outgoing (g) Two Bus coupler capacity 400 Amp VCB between two incomer and outgoning of with LED type Indicators for On OFF, RYB type Phase Indicators, without CT. PT and Relays Note:(i) Configuration and Schematics arrangement of Panel Shall be got approved from Garrison Engineer before fabrication. (ii) Any other parts/items not specified above but have been required essential for smooth and safe functioning of the Panel system shall be quoted rate (iii) The VCB/RMU will be tested as site as primer.
Supplying, fixing cable path indicator of CI plate of minimum 150 mm dia and 4 mm thick indicating HT cable size and volatge written on it , fixed on MS angle iron of size 25 x 25 mm x 6 mm and length of 600 mm duly painted with one coat of red oxide primer through out length and thereafter it will be painted with two coats of synthetic enamel and bituminus paint of browon clour including PCC (1:3:6) type C1 using 20 mm stone aggreagte of block size 150 x 150 x 450 mm deep complete all as specified and directed
Supply ,install, commissioning and testing step down power transformer indoor type, HT 11 KV , 3 Phase 433 Volts, 4 wire, 50 HZ Delta /Star connected, vector group DYN -II double copper wound , ONAN , manual type off load tap changing facility on HT side to vary secondary voltage of + 7.5% in steps of 2.5%, continuous rating of capacity 160 KVA including bushing on HT and cabel end box on LT side. The transformer shall conforming to IS-1180 part 1 : 2014 and BEE certified complete with all standard fittings and accesssories, gauges, first filling of transformer oil etc complete all as specified and as directed (For S/S No -02).Make :- CG/Schnider/ITE Gurgown (a) Oil conservator with filling hole and cap drain valve and oil level gauge. (b) Silica gel breather with connecting pipe, first fill of dehydrating agent. (c) Explosion relief mounted on tank with double diaphragm and equalizer pipe connected to conservator air spoon (Pressure release valve.) (d) Air release plug. (e) Oil temperature indicator (gauge) having range 00 C to 1200, 100 mm dial type . (f) Thermometer pocket with thermometer dial size 100 mm dia. (g) Drain valve with threaded adapter. (h) Sampling valve. (j) Cover lifting eyes. (k) Jacking pads, handling and lifting lugs. (l) Rollers type four No. Wheels. (m) Rating plate and terminal marking plate. (n) HT bushing on 11 KV side and cable end box on LT side. Also extra bushing for neutral outside the LV side. (o) Hand hole of sufficient size to assess the interior of the tank. (p) First filling of transformer oil.
q) Platform constructed with PCC/Brick work and finished with cement mortar 1:4 as per manufacturer recommendations length, width and height shall be 3000 mm x 3000 mm x 1750 mm. (Foundation depth should be 750 mm from ground level) 125 mm thick RCC slab (1:2:4) Type B-1 (Nominal mix) using 20 mm graded stone aggregate on top of the platform. Reinforcement should be 10 mm dia @ 150 mm c/c both way. 2 Nos ISMB 150 of length should be place below the wheel of transformer. Make of Transformer : Schneider/AREVA/Crompton Greaves/ VOLTAMP/ITE Gurgaon Note No1: Contractor shall arrange for factory visit for Rep of Accepting Officer to check Routine tests as Per IS: 2026 and including the following. (i) Double voltage /Double frequency Test (ii) Full load Test (iii) Regulation Test (iv) Efficiency Test (v) Polarity Test &Other Type & Routine test as per IS (vi) Water load test at site. Note No. 2. The cost etc for testing of transformer shall be deemed to be included in the quoted rate.
Supply ,install, commissioning and testing step down transformer indoor type, plinth mounted, HT 11 KV , 3 Phase 433 Volts, 4 wire, 50 HZ Delta /Star connected, vector group DYN -II double copper wound , ONAN , manual type off load tap changing facility on HT side to vary secondary voltage of + 7.5% in steps of 2.5%, continuous rating of capacity 630 KVA including bushing on HT and cabel end box on LT side. The transformer shall conforming to IS-1180 part 1 : 2014 and BEE certified complete with all standard fittings and accesssories, gauges, first filling of transformer oil etc complete including sutiable platfrom with PCC/brick work and finished with cement morter 1:4 as per manufacture recommendeds length, width and height shall be 3000 mm x 3000 mm x 1750 mm (foundation depth shpuld be 750 mm from ground level) 125 mm thick RCC slab (1:2:4) all as specified and as direType b-1 (Nominal mix) using 20 mm graded stone aggregate on top of the platfrom. Reinforcement should be 10 mm dia @ 150 mm C/C both way 02 Nos ISMB 150 of length should place below the wheel of transformer (For Substation No - 02).Make :- CG/Schnider/ITE Gurgown (a) Oil conservator with filling hole and cap drain valve and oil level gauge. (b) Silica gel breather with connecting pipe, first fill of dehydrating agent. (c) Explosion relief mounted on tank with double diaphragm and equalizer pipe connected to conservator air spoon (Pressure release valve.) (d) Air release plug. (e) Oil temperature indicator (gauge) having range 00 C to 1200, 100 mm dial type . (f) Thermometer pocket with thermometer dial size 100 mm dia. (g) Drain valve with threaded adapter. (h) Sampling valve. (j) Cover lifting eyes.
(k) Jacking pads, handling and lifting lugs. (l) Rollers type four No. Wheels. (m) Rating plate and terminal marking plate. (n) HT bushing on 11 KV side and cable end box on LT side. Also extra bushing for neutral outside the LV side. (o) Hand hole of sufficient size to assess the interior of the tank. (p) First filling of transformer oil. (q) Platform constructed with PCC/Brick work and finished with cement mortar 1:4 as per manufacturer recommendations length, width and height shall be 3000 mm x 3000 mm x 1750 mm. (Foundation depth should be 750 mm from ground level) 125 mm thick RCC slab (1:2:4) Type B-1 (Nominal mix) using 20 mm graded stone aggregate on top of the platform. Reinforcement should be 10 mm dia @ 150 mm c/c both way. 2 Nos ISMB 150 of length should be place below the wheel of transformer. Make of Transformer : Schneider/AREVA/Crompton Greaves/ VOLTAMP/ITE Gurgaon Note No1: Contractor shall arrange for factory visit for Rep of Accepting Officer to check Routine tests as Per IS: 2026 and including the following. (i) Double voltage /Double frequency Test (ii) Full load Test (iii) Regulation Test (iv) Efficiency Test (v) Polarity Test &Other Type & Routine test as per IS (vi) Water load test at site. Note No. 2. The cost etc for testing of transformer shall be deemed to be included in the quoted rate.
Supply install testing and commissioning ISOLATION TRANSFORMER Indoor type- suitable for IP 23 enclosure, 415 volts at no load AC 3 phase 50 Hz capacity 160 KVA, core type double copper wound ONAN cooled Oil immersed delta connected on primary side and star connected on secondary side in accordance with vector symbol DYN-II (vector group) with neutral brought out on secondary side (LV side) and having tapping at +5% in steps of 2.5% by means of off circuit tap link board. The maximum temperature rise 115 degree calsius by winding resistance method after continuous full load on an ambient temp of 50 degree Celsius. The transformer shall be confirming to IS: 1180: 2014 and shall comprise of the following:- (a) Rating and diagram plate. (b) Two earthing terminals in two side. (c) Lifting lugs .(d) Off circuit link board. (e) Base channel with Bi- directional Rollers. (f) Danger board (g) 100 mm dial type thermometer. (h) Cable entry boxes etc complete as reqd.
Supply install testing and commissioning ISOLATION TRANSFORMER Indoor type- suitable for IP 23 enclosure, 415 volts at no load AC 3 phase 50 Hz capacity 630 KVA, core type double copper wound ONAN cooled Oil immersed delta connected on primary side and star connected on secondary side in accordance with vector symbol DYN-II (vector group) with neutral brought out on secondary side (LV side) and having tapping at +5% in steps of 2.5% by means of off circuit tap link board. The maximum temperature rise 115 degree calsius by winding resistance method after continuous full load on an ambient temp of 50 degree Celsius. The transformer shall be confirming to IS: 1180: 2014 and shall comprise of the following:- (a) Rating and diagram plate. (b) Two earthing terminals in two side. (c) Lifting lugs .(d) Off circuit link board. (e) Base channel with Bi- directional Rollers. (f) Danger board (g) 100 mm dial type thermometer. (h) Cable entry boxes etc complete as reqd.
Supply install testing and commissioning of Diesel engine driven genrating set 415 Volts, 3 Phase 4 wire, engine as per IS : 10001/10002 and alteranator as per IS 13364 complete with relay panel for automatic starting on mains failure, control panel having meters, sound proof canopy including foundation complete for base of DG Set etc of capacity 160 kVA. Tools and spares complete all as specified and directed and comprising of the following :- (a) Engine: Diesel engine, developing required BHP @ 1500 RPM for continuous duty of suitable for 160 KVA alternator with provision of 10% over load for one hour in every 12 hour running confirming to BS 5514/ISO 3046 standard. Totally enclosed, electric start, compression ignition, 4 stroke. The engine shall consists of following specification :- The scope of supply includes: -Electrical starter motor 12V DC -Battery charging alternator -MICO fuel system with mechanical governor -Dual spin-on fuel filter -Spin-on full flow lub oil filter -Residential silencer -Dry type air cleaner -Recovery bottle -Shut-off coil with safeties for LLOP/HWT -Flywheel and flywheel housing (i) Alternator: suitable for operation at 1500 RPM, 415 Volts, 0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire system, conforming to BS 5000 / IS 4722. The Alternator is brushless type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator has the following features: -+ 1.0 % Voltage regulation (max.) in static conditions -IP: 23 Enclosure -Permissible overload of 10% for one hour in 12 hours of operation as per standards
(ii) Mounting arrangement : Engine & alternator are mounted on a common MS fabricated base frame with AVM pads. (iii) Control panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for a weather-proof, long lasting finish. The control panel consists of following parts: -Standard engine instrumentation -Multi function meter which measures: 1) Individual phase current (Amps) 2) Phase voltages (V) 3) Generator output frequency (Hz) 4) Engine water temperature (Deg.C) 5) Lube oil pressure (kg/cm2) and equipped with hour counter -MCCB of suitable rating -Key switch -Push button (Starter) -LED: Battery charging alternator fail indication -Current transformers -Instrument fuses duly wired and ferruled (iv) Others: -Fuel tank suitable for 8 hours of operation -One charged battery 12V, suitable rating AH with battery leads & cable Acoustic enclosure: The acoustic enclosure is made of 1.6/ 2 mm thick CRCA sheets and structural/ sheet metal base frame duly painted. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1mtr sound levels specified by Ministry of Environment & Forest. The enclosure has the following features: -Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field
conditions, -Single point lifting for easy handling, -Designed to have optimum serviceability -Air inlet louvers specially designed to operate at rated load, -Made on special purpose CNC machines for consistency in quality and workmanship, -Powder coated for long lasting service life and superior finish, -With UV resistant powder coating, can withstand extreme environments, -Use of special hardware for longer life, -Insulation material meets exacting IS 8183 specifications for better sound attenuation, -Flush styling - no projections, -Fluid drains for lube oil and fuel, -Fuel filling point (v) One set of accessories (As per manufacturer's instructions : (a) Level indicator on fuel tank (b) Drain plug (c) MS class "C" piping, suitable dia and length for fuel inlet from tank to engine as per manufacturers instructions. (d) Fuel strainer and fuel tank with air vent. (e) Battery heavy duty 12 Volts lead acid type fully charged, indication of high flow charging changed. - 01 Nos (f) Cable connection from alternator to DG set control panel as directed (vi) Two years spare parts suitable for the DG Set (a) Air filter - 06 Nos (b) Fuel filter - 06 Nos (c) Fuel element - 06 Nos (d) Battery testing meter (Hydro) - 01 No (e) Suitable fan belt set - 01 set (f) Regulator cut out - 06 Nos (vii) Tools (As per manufacturers instructions (aa) 'D' spanners - 01 Set (ab) Ring spanners - 01 Set (ac) Screw driver 5" to 12" - 01 Set (ad) Cutting plier 9" - 01 No (ae) Hammer 2 LBS - 01 No
Supply install test and commissioning back up power supply with 36 volt DC low maintenance type chargeable battery of 18 cell of 02 volts , 40 Amp hour each including battery charger set having Float Cum Boost Charging facility Suitable for 36 Volt Battery Bank of 40 AH each, and control equipment of suitable size in sheet steel cabinet of 2 mm thick floor mounted for input 230 volts (+)(-)10 volt single phase, 50 Hz AC complete for 11 KV VCB Breaker panel with complete control wiring for connecting the DC tripping system to relays wiring shall be copper conductor of single core and size not less than 2.5 sqmm running in PVC conduit, including stand for mounting of batteries in rack formation, made up of slotted angle iron frame , all as specified & directed complete.
INDICATOR DIGITAL :- (i) Power indicator (ii) Voltage indicator (iii) Frequency Meter (iv) Power Factor indicator (v) Ammeter, Temperature Meter, Digital Ammeter& Digital voltmeter. (vi) Phase sequence indicatior. (vii)Oil level indicator
PROTECTION (i) Overload Cut-Off and short circuit Protection (ii) High/Low voltage cut off (iii) Bypass arrangement in case of emergency (iv) Single phase Prevention. (v) Spike and surge protection (vi) Earth Fault protection. INDICATOR DIGITAL :- (i) Power indicator (ii) Voltage indicator (iii) Frequency Meter (iv) Power Factor indicator (v) Ammeter, Temperature Meter, Digital Ammeter& Digital voltmeter. (vi) Phase sequence indicatior. (vii)Oil level indicator
(v) ACB,1250 Amps,50 kA at 433V MDO Type with O/L,S/C,E/L release & NO+NC contact 4 Pole- 02 Nos ( 01Nos as standby) (B) OUTGOING (vi) (a) ACB,1000 Amps,50 kA at 433V MDO Type with O/L,S/C,E/L release & NO+NC contact 4 Pole ( for CCR) - 02 Nos ( 01No. Working and 01 No. standby ) (b) On load Chang over switch of capacity 1000 Amps , 4 pole in sheet metal enclouser complete. - 01 Nos (vii)(a) MCCB, 4 Pole of capacity 32 Amps, 25 kA at 415V ( for ATC and standby ATC)- 04Nos ( 02No. Working and 02 No. standby ) (b) On load Chang over switch of capacity 63 Amps , 4 pole in sheet metal enclouser complete - 02 Nos (viii) (a) MCCB, 4 Pole of capacity 16 Amps, 25 kA at 415V ( for GCA and GP)- 04 Nos ( 02No. Working and 02 No. standby ) (b) On load Chang over switch of capacity 63 Amps , 4 pole in sheet metal enclouser complete. -02 Nos
M&L brick masonary valve pit chamber of size 900 mm x 900 mm x 600 mm( internal dimension), with3.15 mm thick mild steel sheet cover fixed with two Nos stainless steel hinges of 75 mm long on angle iron frame of size 40 mm x 40 mm x 6 mm thick (mild steel sheet cover and angle iron frame shall be painted with two coat black bituminious paint over a coat of red oxide primer) , PCC 1:4:8, type D-2 (using 40 mm graded crushed stone aggregate ) as in foundation, 230 mm thick brick wall built in cement mortar 1:4, 50mm thick coping with PCC 1:3:6 , typeC-0 ( using 12.5mm graded crushed stone agreegate) , 15 mm thick rendering in cement mortar 1:4 to all internal and exposed surfaces of valve pit including necessary excavation and earth work etc all as shown in drawing & as directed.
Supply and fixing wall/surface mounted type LED light fitting complete with LED lamp of 1x 20/22 watt (4 ft), extruded aluminium heat sink provided for efficient heat dissipation & integrated electronic driver complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable suitable size. etc complete all as specified and directed. Make :- Philips cat No BN 550 WLED 20-6500, Wipro cat No LM31-211-XXX-57-CT or equivalent as approved by GE.
Supply & Fixing MCB SP, 6 Amps to 32 Amps ('C' series) having current rating 10 KA complete all as specified and directed.
Supply & Fixing MCB SPN, 6 Amps to 32 Amps 'C' curve 240 V having current rating 10 KA complete all as specified and directed.
Supply & Fixing MCB SPN 63 Amps 'C' curve 240 V having current rating 10 KA complete all as specified and directed.
Supply & Fixing UPS for 30 minute backup single phase AC input 160 to 260 V and output 230 ± 1% of capacity 2 KVA complete all as specified and directed.
Supply and errection of steel tubular pole swaged type 410-SP 31 (LT 9.00 mtr long pole) complete confirming to IS: 2713 complete with CI base plate pole cap bolt nuts & screw with cast iron base plate, pole cap, mild steel bolt, nuts and screws complete all as specified including consisting of following works:- (a) Excavation in trenches not exceeding 1.5 mtr wide & 1.65 mtr deep for pole foundation & getting out in ant type of soil , returning filling in the excavated of soil after fixing the pole in foundation ramming earth around in layer not exceeding 25 cm thick and disposal of surplus soil to a distance not exceeding 50 mtrs complete all as specified and directed. (b) M&L for PCC 1:4:8, type D-2 (using 40mm graded crushed stone aggregate) in foundation filling and mass concrete for padding of size 600mmx600mm x 150 mm cross section under pole foundation complete all as specified and directed. (c) M&L for providing PCC 1:3:6, type C-2 (using 20mm graded crushed stone aggregate) as in foundation, filling and mass concrete for pole of size 600mm x 600mm x 1500 mm complete all as specified and directed. (d) M&L for painting of pole externally with one coat of black bituminous paint (upto planting depth) and above plinth block concrete collar with two coat of aluminum paint over a coat of red oxide primer including preparation of surface including painting of 30 cm wide bands 3 Nos with synthetic enamel paint of appropriate colour in alternate layer upto the height of 1.5mm above plinth block. (e) M&L for writing letter or figures (Block Roman, Italic as Indian) with thick synthetic enamel paint of apprised shade not exceeding 5 cm height including numbering of pole complete all as specified and directed. (f) Painting of coping with cement based paint all as directed. NOTE : Manufacture's test certificate will be produced before execution work. (g) M&L for PCC 1:2:4 type B-1 using 20 mm graded stone aggregate for coping above GL 300 mm height & 150mm tapered.
S&F factory made epoxy powder coated Distribution Board SPN 8 ways, 240 volt grade ,(SPN MCB DB) IP-43 protection, with metal double dooracrylic top cover fabricatred made out of CRCA sheet and fixed flush to wall and suitable for mounting including 200 amp rated copper bus bar with two neutral bar , earth bar & cable ties for cable management fully insulated bus bar with set of wires and door earthing including strandard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts complete all as specified and as directed.
S&F factory made epoxy powder coated Distribution Board TPN 4 ways, 415 volt grade , IP-43 protection, with metal double dooracrylic top cover fabricatred made out of CRCA sheet and fixed flush to wall and suitable for mounting including 200 amp rated copper bus bar with two neutral bar , earth bar & cable ties for cable management fully insulated bus bar with set of wires and door earthing including strandard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts complete all as specified and as directed.
Supplying, erection, testing and commisioning of BBT of 1000 Amp TPN, cooper air Insulated compact BBT with copper earthing including bends, flange, flat elbow, end lpug, interconnection adaptor box between LT panels with BBT (between LT panels of 630 KVA outdoor Transfer, 630 KVA DG set, 630 KVA stabilizer , 630 KVAIsolation transformer with BBT installed at Sub station No 01) and including required canopy for outdoor BBT portion complete all as specified and directed Note:(i) Any other parts/items not specified above but have been required essential for BBT system shall be considered in quoted rate
Supplying, erection, testing and commisioning of BBT of 630 Amp TPN, cooper air Insulated compact BBT with copper earthing including bends, flange, flat elbow, end lpug, interconnection adaptor box between LT panels with BBT (between LT panels of 160 KVA indoor Transfer, 160 KVA DG set, 160 KVA stabilizer , 160 KVAIsolation transformer with BBT installed at Sub station No 02) complete all as specified and directed Note:(i) Any other parts/items not specified above but have been required essential for BBT system shall be considered in quoted rate
Supply & fixing road lighting luminaire with high light emitting diode and unique peanut lens with choice optics to ensure uniform distribution having powder coated pressure die cast aluminium compact energy saving & environmental friendly long life heat resistant toughened glass of rating not less than 70 watt HP LED, 240 volts, 50 Hz with IP66 protection complete all as directed by Engr-in-charge.
Supply and fixing new pole mounted thermoplastic cable junction box for steet light 4.5 module with IP-65 protection, halogen free and weather proof with metric knockouts for cable entry for outdoor installation of size 126mm x 288mm x 111 mm with front door opening system including terminals for one incoming and two outgoing cables of size 16/25 sqmm 4 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed , Make of J/B - Cat Part No. KV PC 8104 HENSEL or equivalent of Syntex / Havells , MCB - Schneider/Havells/L&T .
M&L for twin core PVC insulated sheathed(heavy duty) unarmoured aluminium conductor cable (for phase and neutral) of size 2.50 Sqmm for connection drawing through pole or GI brackets of street light fittings with junction box or OH conductor complete all as directed.
Supply and fixing of street light bracket (with two set of clamp, nuts & bolts) made out of 32 mm medium grade GI pipe bend to shape and with fixing arrangement duly welded all as directed, length of pipe should not be less than 1.2 mtrs complete all as directed.
M & L for supplying, installing, connecting and commisioning of DG set control panel floor mounted indoor type, ACB switch gear with copper bus bar comprising for capacity of 1250 Amps, 01 Nos incoming for main Elcetric supply, 02 Nos incoming for 02 Nos of DG set supply, 01 No Bus coupler and 01 Nos outgoing alongwith control panel PLC, automatic refueling system, parameter displaywith all connected items. The panel shall also included the following capacity of the ACBs with all necessories fittings reuired at site : (i) 01 Nos incoming ACB of capacity 1250 Amps, 50 KA, 4 Pole complete with all necessorry fittings required for main powwr supply (ii) 02 Nos incoming ACB of capacity 1250 Amps, 50 KA 4 pole complete all acceesoories fittings for 02 nos for DG set supply (iii) 01 Nos Bus coupler with ACB of capacity 1250 Amps, 4 pole complete with all required for outgoing coonection. (iv) 01 No outgoing ACB of capacity 1250 Amp, 50 KA, 4 pole complete with all accessories and fittings.
M & L for earthing complete with Galvanised steel earth plate 600 mm x 600 mm x 6.00mm thick buried directly in ground vertically in pit of depth not less than 2.25 mtr below normal ground level with top edge of the earth plate not less than 1.50 mtr below normal ground level connected to contineous (without joint) galvanised wire 4 mm dia as earthing wire (lead) by means of bolts, nuts, check nuts and washers of brass connected including gun metal or phosphorus bronze of size 75 mm x75 mm x 25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screwed all as specified including excavation and earth work and disposal of surplus soil including 15 mm bore Gl tubing medium grade and necessary fitting for protection of Gl wire including laying of charcoal, dust and common salt PCC 1:3:6 type C-1( using 20 mm graded crushed black trap/ granite/ Basalt stone aggregate), 40 mm thick pre-cast cover reinforced cement concrete with 8 mm dia TMT bars@ 75 mm c/c both way with 12 mm dia round bar as handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh, 15mm thick rendering in cement mortar 1:4 internally and upto 150mm below ground level & externally. PGI funnel with wire mesh , complete all as shown on electrical plate No.3 of SSR Part -1( 2009) and connected in earth test including testing complete all specified and directed. NOTE :- (i) The rates quoted shall also deemed to include the cost of Earth test point and earth wire and protection pipe upto 7.5 metre beyond the earth plates electrode and the earth resistance of the whole system shall be as near as possible to 0 but shall not in any case exced one ohm.
S&F Sub main wiring using two runs of single core PVC FRLS insulated, unsheathed stranded copper conductor cable of size 2 x 4 .0 Sq.mm of voltage rating 1100 Volt & drawn in and including concealed PVC conduit of dia not less than 20mm with standard accessories, alongwith one run of PVC FRLS (green colour) insulated, unsheathed, stranded copper conductor of size 1x 4.0 Sq.mm as earth continuity conductor complete all as specified and directed. Note-Two runs of single core PVC cable 4.0 Sq.mm with one run of 4.0 Sq.mm as earth wire conductor and conduit shall be measured as one unit.
Supply and fixing architectural LED luminair provides soft light and glare free symmentrical illumination (with contineuous mounting end cap) ceiling mounted type LED light fitting complete with LED lamp of 1X 20 watt (4 feet) complete with all accessories internally pre- wired and including connecting of with twin core twisted flexible copper conductor cable complete all as specified and directed. Make: Havelles Cat No. CONSTA544LP20WLED830SPMMAWH or equivalent in crompton.
Supply and fixing of wall / surface mounted type LED light fitting for mirror light complete with LED lamp of 1X 10 watt (@ feet) extruded aluminium heat sink provided for efficient heat dissipation & integrated electronic driver complete with all accessories internally prewired and including connecting up with twin core twisted flexible copper conductor cablecomplete all as specified and directed. Make: Havelles Cat No. LHEWEBP7PLIN1W010, Crompton Cat No. LCL-10-CDL, Philips cat No. BN021LED10S-6500
Supply and Installation of ESE type Lightning arrestor Model Tz63 having radius of protection 80 Meters in Level I when installed 6 mtrs above the heighest poin tof the structure,Level of Protection high complete all as specified and directed.Make: Tercel / Indelec/ Ground.
Supply and laying 70 sqmm PVC insulated flexible electrolytic copper down conductor placed in a GI pipe 40mm bore light grade for protective covering upto 3 mt wherever exposed to human intervention including saddles and all accessories as required complete all as specified and directed.
Supply and Installation of 5 mtrs mast on the flat RCC roof of the building , made with GI pipe along with guying arrangement & foundation with all necessary accessories for installation of mast for Lightning arrestor complete all as specified and directed.
SITC of transient event counter having resettable 6 digit LCD display with inbuilt lithium battery in IP67 rating enclosure with transparent lid, counting arrangements etc as required complete all as speciifed & directed.Make: Tercel / Indelec/ Ground.
Supply of material and labour for making High conductive, Non corrosive, Maintenance Free and Repairable 'Chem rod' Electro-Chemical-Gelearhtpit using earth enhancing compound ISOGELof 30kg kit,CPRI tested ISOROD of 3 inch dia,8 ft long and 0.12 inch thick made of Ktype electrolytic copper with top removal gel filling cap, seepage holes, Stainless steel fasteners, HDP Lockable earht pit cover cum inspection chamber and all required accessories including design modifications,to achieve the required earth termination rod resistance value below 2ohms or as per the OEM/ Internation standard recommendation. Make: Tercel / Indelec/ Ground.
Supply and fix in diamond shape high strength steel punched tape concertina coil 1050 mm dia (in specified stretched position) hot dip galvanized coated with CLR anti corrosive paint by making diamond shape with the help of dove tail clips (18 SWG) fixed over razor wire with the help of hog rings (14 SWG) in angle iron bracket/frame over boundary wall etc complete all as specified and shown on drawings/ directed. (Note:- Razor wire and angle iron frame/bracket shall be measured and paid separately)
Supply and fix razor wire 2.6 mm dia with 14 mm wide & 0.5mm thick razor strip fixed with clamps in rows in angle iron bracket/frame over boundary wall etc complete all as specified and shown on drawing and directed. (Note :Each line wire to be measured separately for payment ).
M & L for Construction of Septic Tank for 10 users including necessary earth work in excavation in any type of soil , plain cement concrete 1:2:4 type B-2 ( using 40 mm graded crushed stone aggregate ) as in foundation , brick work in cement mortar 1:4 , ,reinforced cement concrete M-25 ( design mix) as in slab cover including pre-cast man hole cover slab having 8 mm dia TMT bar reinforcemement @ 75 mm c/c & 6 mm thick mild steel plate embedded all around of cover slab , 15 mm thick plaster in cement sand mortar in 1:4 on wall, vent shaft, sludge chamber , form work to sides and soffits, 150 mm dia SGSW inlet & out let pipes up to 3 m from outer face of wall, CI vent pipe, sludge chamber, RCC baffle wall, returning filling & removal etc, complete all as shown on drawings & as specified.
M&L for soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonary with top ring M-25 concrete including intercepting chamber and screen chamber made of brick masonary in CM, RCC cover slab in M-25 (Using 20 mm graded stone aggregate ) cover, interconnecting pipes of RCC complete filled with brick bats of size 1.20 m X 3.00 m complete all as specified and as directed by Engineer-in-charge
GUPTA ENGINEERING WORKS
HI TECH COLONISERS PRIVATE LIMITED
yash enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .